background image

Manual 2100-711C 

Page 

36 of 45

TABLE 14

Recommended Airflow

FIGURE 27

Speed Taps

Speed Tap 1: Vent Speed
Speed Tap 2: Balanced Climate Speed
Speed Tap 3: Default Speed
Speed Tap 4: Medium Speed
Speed Tap 5: High Speed

Manual

2100-467H

Page

23 of 23

FIGURE  11

TROUBLESHOOTING  GE  X13-SERIES ECM2.3

 MOTORS 

CONT’D.

Model X13 Communication Diagnostics

The X13 motor is communicated through 24 VAC low voltage

(Thermostat Control Circuit Wiring).

1.

Start with unit wiring diagram to confirm proper

connections and voltage (see Figure 11).

2. Initiate a demand from the thermostat and check the

voltage between the common and the appropriate motor

terminal (1-5).  ("G" input is typically on terminal #1, but

refer to wiring diagram!)

a. If the low voltage communication is not present, check

the demand from the thermostat.  Also check the

output terminal and wire(s) from the terminal strip or

control relay(s) to the motor.

b. If the motor has proper high voltage as identified

above (Motor not Running #1), and proper low voltage

to a programmed terminal, and is not operating, the

motor is failed, and will require replacement.

24VAC "R" Sig nal thro ug h 

thermo stat o utp ut.

24VAC Co mmo n

24VAC Co mmo n

24VAC "R" Sig nal thro ug h 

thermo stat o utp ut.

24VAC Common

24VAC "R" 

signal through 

thermostat output

FIGURE 28

Speed Taps

Orange Wire 

w/Black Stripe

Model

Nominal 

Rated 

CFM*

Nominal 

Rated 

ESP*

Recommended 

Airflow Range

Factory 

Speed 

Connection

W42HC

1350

.15

1250 - 1600

Default

W48HC

1550

.20

1450 - 1750

W60HC

1750

.20

1650 - 2000

* Rated CFM and ESP on factory speed connection.

Setting Unit Airflow

The unit is set from the factory at the default speed. 
Most units have three selectable cooling speed taps 
that can be utilized. The default speed is the lowest 
cooling speed. The two higher speed taps can be used 
for higher duct static applications so that the unit can 
maintain the recommended airflow as shown in Table 
14. The higher speeds can also be used when higher 
sensible cooling is desired. To change to the higher 
speed taps, move the orange/black wire on the blower 
speed terminal block to either MED or HI. Refer to 
Table 16 on page 40 for the corresponding airflow of 
each tap. Set the unit duct static based on the highest 
airflow that the unit will run at.

NOTE:

 Be sure to adjust the system static or 

blower speed to maintain airflows above the 

minimum recommendations to prevent freeze 

up conditions if Balanced Climate mode is 

activated.

Do not operate the unit in Balanced Climate mode 
if running high static applications as indicated in 
the blower performance table. If Balanced Climate 
mode is activated as described on page 18, the unit 
will run in this mode at all times unless there is a 
call for ventilation, electric heat or 2nd stage cooling 
from a 2-stage thermostat. At that time, the unit will 
automatically activate a higher speed tap.

Blower Speeds

Five factory programmed speed taps (torque settings) 
are available for the motor, and are selected through 
different unit modes of operation. These modes are 
energized by 24VAC signals from the low voltage 
terminal block located inside the control panel by a 
thermostat or other controlling device. Each speed tap 
is programmed by Bard at the factory to different motor 
torque settings (see Figure 27).

Multiple motor speed taps may be energized 
simultaneously by 24VAC power during different modes 
of operation. The highest number speed tap energized 
takes priority with 5 being the highest and 1 being 
the lowest. See Table 15 for the corresponding blower 
speeds with the different modes of operation.
Programmed blower speed taps are as follows (see also 
Figure 28):
Speed Tap 1: 

Vent/blower only

 speed 

Speed Tap 2: 

Balanced Climate

 speed

Speed Tap 3: 

Default LO cooling & heating

 speed. 

Energized by default for cooling operation through the 
blower speed tap selection and is labeled as LO.
Speed Tap 4: 

Optional MED Cooling & heating

 speed. 

Selected manually through the blower speed tap 
selection and is labeled as MED.
Speed Tap 5: 

Optional HI cooling & heating

 speed. 

Selected manually through the blower speed tap 
selection and is labeled as HI.

Содержание 11EER WH Series

Страница 1: ...NSTRUCTIONS W42HC A W42HC B W42HC C W48HC A W48HC B W48HC C Bard Manufacturing Company Inc Bryan Ohio 43506 www bardhvac com Manual 2100 711C Supersedes 2100 711B Date 9 8 20 W60HC A W60HC B W60HC C W...

Страница 2: ...eration 24 Cooling Heating 24 Balanced ClimateTM Mode 25 Defrost Cycle 25 Low Pressure Switch Bypass Operation 26 High Pressure Switch Operation 27 Vent Connection Plug 27 Pressure Service Ports 27 Se...

Страница 3: ...3555 Fax 617 984 7057 Figure 21 Non Programmable Thermostat Connections 22 Figure 22 Defrost Control Board 26 Figure 23 Motor Connections 30 Figure 24 Motor Connections 31 Figure 25 Fan Blade Setting...

Страница 4: ...y read before beginning the installation Note particularly Starting Procedure and any tags and or labels attached to the equipment While these instructions are intended as a general recommended guide...

Страница 5: ...s on page 10 and Figures 14 18 pages 13 16 for further details Ducts through the walls must be insulated and all joints taped or sealed to prevent air or moisture entering the wall cavity Some install...

Страница 6: ...see Figure 7 FIGURE 6 Remove Four Screws 5 Re install the four 4 hex head screws into the upper screw holes on the filter support brackets Then bend the tab up out of the way see Figure 8 FIGURE 7 Re...

Страница 7: ...r blade FIGURE 9 Install Right 2 Filter FIGURE 10 Install Left 2 Filter There is an adjustable slide on the side of the fresh air intake that can be adjusted to limit how far the damper opens so that...

Страница 8: ...drainage A clear flexible PVC drain hose 3 4 ID 1 OD extends from the drain pan in the upper section of the unit and extends down to the unit base An opening is supplied towards the back of the unit b...

Страница 9: ...cable installation codes may limit this cabinet to installation only in a single story structure Thermostat or Indoor Temperature Sensor Placement The location and installation of the thermostat or te...

Страница 10: ...s and bottom mounting bracket location Install bottom mounting bracket with field supplied fasteners to wall if it is to be used optional Bracket must be level and installed in the correct location to...

Страница 11: ...GURE 12 Vent Installation Removal Clearance Required 20 3 4 2 37 1 4 17 3 4 45 MIS 4042 KEEP AREA CLEAR FOR 45 IN FRONT OF SIDE PANEL OBJECT OR WALL IN THIS SECTION OR ANY OTHER OBSTRUCTION OF UNIT OR...

Страница 12: ...ings are not to scale 2 000 Return Air Opening Supply Air Opening MIS 3978 A Condenser Air Outlet Ventilation Air Inlet Cond Air Exhaust Air Brackets Built In Mounting Side Wall Location Shipping Flas...

Страница 13: ...ening and Hole Location View Supply Opening Return Opening UNITS REQUIRED DIMESIONS A B C D E F G W42HC W48HC UNITS REQUIRED DIMESIONS TO MAINTAIN 1 4 MIN CLEARANCE FROM COMBUSTIBLE MATERIALS 30 1 2 1...

Страница 14: ...W OF SUPPLY AIR DUCT FOR WALL MOUNTED UNIT SHOWING 1 4 CLEARANCE TO COMBUSTIBLE SURFACES Fire hazard Maintain minimum 1 4 clearance between the supply air duct and combustible materials in the first 3...

Страница 15: ...ALL AROUND DUCT MIS 3982 A THIS STRUCTURAL MEMBER LOCATED TO MATCH STUD SPACING FOR REST OF WALL A SECOND MEMBER MAY BE REQUIRED FOR SOME WALLS SUPPY DUCT OPENING RETURN DUCT OPENING See Figure 14 Mo...

Страница 16: ...VE RAFTERS GRILLE FLASHING OR BELOW CEILING RAFTERS AS SHOWN OR BELOW CEILING RAFTERS AS SHOWN FLASHING OUTSIDE SURFACE RAIN FLASHING SLEEVE FINISHED SUPPLY DUCT MAYBE LOCATED IN AN ATTIC GRILLE OUTSI...

Страница 17: ...ocument regarding the phase monitor High Voltage Connections Route field wires under the field wire shield shown in Figure 19 The field wire shield can be removed for wire installation If field power...

Страница 18: ...tion only 12 terminal is filter switch normally open contact on auxiliary terminal strip F Control option only Unit Shutdown Feature Standard on All Models The RT terminal is the 24VAC transformer out...

Страница 19: ...e Controls Option The DDC controls option provides additional sensors that can be used with a field supplied advanced logic controller The DDC controls option contains the following installed componen...

Страница 20: ...A use 8403 092 T6 Pro Wi Fi 2 stage Cool 3 stage Heat Heat Pump 2 stage Cool 2 stage Heat Conventional Programmable Non Programmable Electronic Auto or Manual changeover Wi Fi TABLE 5 Humidity Control...

Страница 21: ...CO2 controller is used control optional for ECON only see vent instruction manuals 0 10 VDC modulating C02 control signal for modulating ventilation 6 8 7 Do not add these wires if setting up for mod...

Страница 22: ...See vent installation manual 6 For vent operation add jumper if optional CO2 controller is not used Vent will run while blower is energized For ECON CRV V an additional wire change is required See ins...

Страница 23: ...A refrigerant it must come out of the charging cylinder tank as a liquid to avoid any fractionation and to ensure optimal system performance Refer to instructions for the cylinder that is being utiliz...

Страница 24: ...operating pressure builds up After starting the fan motor may or may not cycle depending upon ambient conditions This is normal operation Service Hints 1 Caution owner operator to maintain clean air...

Страница 25: ...ol and the defrost timer will start accumulating run time After 30 60 or 90 minutes of heat pump operation at 30 F or below the heat pump control will place the system in the defrost mode During the d...

Страница 26: ...ompressor time delay In some instances it is helpful to the service technician to override or speed up this timing period and shorting out the SPEEDUP terminals for a few seconds can do this Low Press...

Страница 27: ...the supplied jumper plug is in place The unit will not operate without anything plugged in This plug is located on the side of the control panel behind the front vent door behind the filter access do...

Страница 28: ...rmer is bad or the unit wiring is incorrect 10 Check for Compressor output signal Is there 24 volts AC between CC C Yes go to Step 12 No go to Step 13 11 No Y compressor input signal Check thermostat...

Страница 29: ...6 0 144374 22 0 43554 60 0 15310 98 0 6098 15 0 139576 23 0 42295 61 0 14921 99 0 5961 14 0 134956 24 0 41077 62 0 14544 100 0 5827 13 0 130506 25 0 39898 63 0 14177 101 0 5697 12 0 126219 26 0 38757...

Страница 30: ...onnections Manual 2100 467H FIGURE 10 NOTE Bard Models PA13242 PA13302 PA13362 A B PA13422 A B C PA13482 A B C PA13602 A B C contain the X13 Series Motors TROUBLESHOOTING GE X13 SERIES ECM2 3 MOTORS I...

Страница 31: ...tor is failed and will require replacement 24VAC R Signal through thermostat output 24VAC Common 24VAC Common 24VAC R Signal through thermostat output Model SelecTech Communication Diagnostics The Sel...

Страница 32: ...nser coil for cleaning or to service the outdoor fan first remove the side grilles 3 The fan shroud sides can then be removed for ease of access to the coil and the back side of the shroud by removing...

Страница 33: ...70 Low Side High Side 32 297 38 303 45 310 51 317 58 324 65 332 72 339 79 348 87 356 94 365 102 374 110 383 118 393 126 403 Model Return Air Temp DB WB Pressure 75 80 85 90 95 100 105 110 115 120 125...

Страница 34: ...123 380 126 406 128 432 130 459 132 487 134 515 136 544 138 574 140 611 80 67 Low Side High Side 124 315 127 339 129 364 132 390 134 416 137 443 139 471 141 499 143 529 145 558 147 589 150 626 85 72 L...

Страница 35: ...uit Ampacity Maximum External Fuse or Ckt Brkr Field Power Wire Size Ground Wire Minimum Circuit Ampacity Maximum External Fuse or Ckt Breaker Field Power Wire Size Ground Wire Size Ckt A Ckt B Ckt A...

Страница 36: ...16 on page 40 for the corresponding airflow of each tap Set the unit duct static based on the highest airflow that the unit will run at NOTE Be sure to adjust the system static or blower speed to mai...

Страница 37: ...in the ECM motor This is a user selectable airflow amount that will be higher than rated airflow Tap 4 is used for cooling operation if the orange black wire on the blower speed selection terminal blo...

Страница 38: ...With air filters installed and switch initially set at 0 4 W C see Step 2 under Dirty Filter Switch begin restricting the air filter of the unit using a piece of cardboard under the filters until the...

Страница 39: ...WISE TO DECREASE RESTRICTION AMOUNT MIS 4086 B 5 Replace the upper front panel and repeat Steps 1 3 Continue to make adjustments described in Step 4 until the desired restriction is obtained 6 Remove...

Страница 40: ...5 1435 1355 W48HC 0 00 1320 1270 1745 1665 1895 1800 1985 1860 0 10 1225 1160 1700 1615 1850 1760 1915 1810 0 15 1180 1110 1675 1585 1825 1735 1880 1780 0 20 1130 1060 1650 1555 1795 1705 1845 1755 0...

Страница 41: ...4 4 10239 5 20 8 17065 18 0 12799 12 0 17065 9 21 7 30717 18 7 23038 10 4 28260 10 41 7 34130 36 1 25598 15 62 5 51195 54 1 38396 36 1 51195 31 2 38396 17 3 47099 18 43 3 61434 37 5 46076 20 8 56519 2...

Страница 42: ...Control and Outdoor Thermostat Heat Pump LAC ODT X X BOP5 Blank Off Plate X X FAD NE5 Fresh Air Damper No Exhaust X X FAD BE5 Fresh Air Damper Barometric Exhaust X X CRV F5 Commercial Ventilator On O...

Страница 43: ...EHW3HC B15 X EHW3HC C05 X X EHW3HC C15 X EHW3HCDA10 X EHW3HCDA15 X EHW3HCDB09 X EHW3HCDB15 X EHW3HCDC05 X EHW3HCDC09 X EHW3HCDC15 X X EHW4HC A04 X EHW4HC A05 X EHW4HC A15 X EHW4HC B09 X X X EHW4HC C05...

Страница 44: ...Manual 2100 711C Page 44 of 45 GRAPH 1 W42HC FAD NE5 W O Exhaust Ventilation Delivery GRAPH 2 W48HC FAD NE5 W O Exhaust Ventilation Delivery...

Страница 45: ...Manual 2100 711C Page 45 of 45 GRAPH 3 W60HC FAD NE5 W O Exhaust Ventilation Delivery...

Отзывы: