TABLE 12 

Cooling Pressure – Balanced Climate Airflow

Air Temperature Entering Outdoor Coil °F

Low side pressure ± 4 PSIG                                                         
High side pressure ± 10 PSIG

Tables are based upon Balanced Climate CFM (airflow) across the evaporator coil. If there is any doubt as to correct 
operating charge being in the system, the charge should be removed and system evacuated and recharged to serial plate 
charge weight.

NOTE:

  Pressure table based on high speed condenser fan operation. If condensing pressures appear elevated check 

condenser fan wiring. See 

Condenser Fan Operation

 on page 24.

* Operating at these conditions would be outside the compressor operating envelope and is not recommended.

Model

Return Air Temp 

(DB/WB)

Pressure

75

80

85

90

95

100

105

110

115

120

125

131

W42HC

75/62

Low Side

High Side

116
307

118
331

121
355

123
380

126
406

128
432

130
459

132
487

134
515

136
544

138
574

140
611

80/67

Low Side

High Side

124
315

127
339

129
364

132
390

134
416

137
443

139
471

141
499

143
529

145
558

147
589

150
626

85/72

Low Side

High Side

128
326

131
351

134
377

136
404

139
431

141
459

144
488

146
517

148
547

151
578

153
609

--*

W48HC

75/62

Low Side

High Side

122
314

123
335

125
358

127
381

129
405

131
431

133
457

135
484

137
513

139
542

141
572

143
610

80/67

Low Side

High Side

130
322

132
344

134
367

136
391

138
416

140
442

142
469

144
497

146
526

148
556

150
587

153
625

85/72

Low Side

High Side

134
333

136
356

139
380

141
405

143
430

145
457

147
485

149
514

151
544

153
575

156
607

--*

W60HC

75/62

Low Side

High Side

115
307

118
329

120
352

123
376

125
401

127
427

129
454

131
482

132
512

134
542

135
573

136
611

80/67

Low Side

High Side

123
314

126
337

129
361

131
386

134
411

136
438

138
466

140
495

142
525

143
555

144
587

145
627

85/72

Low Side

High Side

127
325

130
349

133
374

136
399

139
426

141
454

143
482

145
512

147
543

148
575

149
608

--*

Содержание 11EER WH Series

Страница 1: ...NSTRUCTIONS W42HC A W42HC B W42HC C W48HC A W48HC B W48HC C Bard Manufacturing Company Inc Bryan Ohio 43506 www bardhvac com Manual 2100 711C Supersedes 2100 711B Date 9 8 20 W60HC A W60HC B W60HC C W...

Страница 2: ...eration 24 Cooling Heating 24 Balanced ClimateTM Mode 25 Defrost Cycle 25 Low Pressure Switch Bypass Operation 26 High Pressure Switch Operation 27 Vent Connection Plug 27 Pressure Service Ports 27 Se...

Страница 3: ...3555 Fax 617 984 7057 Figure 21 Non Programmable Thermostat Connections 22 Figure 22 Defrost Control Board 26 Figure 23 Motor Connections 30 Figure 24 Motor Connections 31 Figure 25 Fan Blade Setting...

Страница 4: ...y read before beginning the installation Note particularly Starting Procedure and any tags and or labels attached to the equipment While these instructions are intended as a general recommended guide...

Страница 5: ...s on page 10 and Figures 14 18 pages 13 16 for further details Ducts through the walls must be insulated and all joints taped or sealed to prevent air or moisture entering the wall cavity Some install...

Страница 6: ...see Figure 7 FIGURE 6 Remove Four Screws 5 Re install the four 4 hex head screws into the upper screw holes on the filter support brackets Then bend the tab up out of the way see Figure 8 FIGURE 7 Re...

Страница 7: ...r blade FIGURE 9 Install Right 2 Filter FIGURE 10 Install Left 2 Filter There is an adjustable slide on the side of the fresh air intake that can be adjusted to limit how far the damper opens so that...

Страница 8: ...drainage A clear flexible PVC drain hose 3 4 ID 1 OD extends from the drain pan in the upper section of the unit and extends down to the unit base An opening is supplied towards the back of the unit b...

Страница 9: ...cable installation codes may limit this cabinet to installation only in a single story structure Thermostat or Indoor Temperature Sensor Placement The location and installation of the thermostat or te...

Страница 10: ...s and bottom mounting bracket location Install bottom mounting bracket with field supplied fasteners to wall if it is to be used optional Bracket must be level and installed in the correct location to...

Страница 11: ...GURE 12 Vent Installation Removal Clearance Required 20 3 4 2 37 1 4 17 3 4 45 MIS 4042 KEEP AREA CLEAR FOR 45 IN FRONT OF SIDE PANEL OBJECT OR WALL IN THIS SECTION OR ANY OTHER OBSTRUCTION OF UNIT OR...

Страница 12: ...ings are not to scale 2 000 Return Air Opening Supply Air Opening MIS 3978 A Condenser Air Outlet Ventilation Air Inlet Cond Air Exhaust Air Brackets Built In Mounting Side Wall Location Shipping Flas...

Страница 13: ...ening and Hole Location View Supply Opening Return Opening UNITS REQUIRED DIMESIONS A B C D E F G W42HC W48HC UNITS REQUIRED DIMESIONS TO MAINTAIN 1 4 MIN CLEARANCE FROM COMBUSTIBLE MATERIALS 30 1 2 1...

Страница 14: ...W OF SUPPLY AIR DUCT FOR WALL MOUNTED UNIT SHOWING 1 4 CLEARANCE TO COMBUSTIBLE SURFACES Fire hazard Maintain minimum 1 4 clearance between the supply air duct and combustible materials in the first 3...

Страница 15: ...ALL AROUND DUCT MIS 3982 A THIS STRUCTURAL MEMBER LOCATED TO MATCH STUD SPACING FOR REST OF WALL A SECOND MEMBER MAY BE REQUIRED FOR SOME WALLS SUPPY DUCT OPENING RETURN DUCT OPENING See Figure 14 Mo...

Страница 16: ...VE RAFTERS GRILLE FLASHING OR BELOW CEILING RAFTERS AS SHOWN OR BELOW CEILING RAFTERS AS SHOWN FLASHING OUTSIDE SURFACE RAIN FLASHING SLEEVE FINISHED SUPPLY DUCT MAYBE LOCATED IN AN ATTIC GRILLE OUTSI...

Страница 17: ...ocument regarding the phase monitor High Voltage Connections Route field wires under the field wire shield shown in Figure 19 The field wire shield can be removed for wire installation If field power...

Страница 18: ...tion only 12 terminal is filter switch normally open contact on auxiliary terminal strip F Control option only Unit Shutdown Feature Standard on All Models The RT terminal is the 24VAC transformer out...

Страница 19: ...e Controls Option The DDC controls option provides additional sensors that can be used with a field supplied advanced logic controller The DDC controls option contains the following installed componen...

Страница 20: ...A use 8403 092 T6 Pro Wi Fi 2 stage Cool 3 stage Heat Heat Pump 2 stage Cool 2 stage Heat Conventional Programmable Non Programmable Electronic Auto or Manual changeover Wi Fi TABLE 5 Humidity Control...

Страница 21: ...CO2 controller is used control optional for ECON only see vent instruction manuals 0 10 VDC modulating C02 control signal for modulating ventilation 6 8 7 Do not add these wires if setting up for mod...

Страница 22: ...See vent installation manual 6 For vent operation add jumper if optional CO2 controller is not used Vent will run while blower is energized For ECON CRV V an additional wire change is required See ins...

Страница 23: ...A refrigerant it must come out of the charging cylinder tank as a liquid to avoid any fractionation and to ensure optimal system performance Refer to instructions for the cylinder that is being utiliz...

Страница 24: ...operating pressure builds up After starting the fan motor may or may not cycle depending upon ambient conditions This is normal operation Service Hints 1 Caution owner operator to maintain clean air...

Страница 25: ...ol and the defrost timer will start accumulating run time After 30 60 or 90 minutes of heat pump operation at 30 F or below the heat pump control will place the system in the defrost mode During the d...

Страница 26: ...ompressor time delay In some instances it is helpful to the service technician to override or speed up this timing period and shorting out the SPEEDUP terminals for a few seconds can do this Low Press...

Страница 27: ...the supplied jumper plug is in place The unit will not operate without anything plugged in This plug is located on the side of the control panel behind the front vent door behind the filter access do...

Страница 28: ...rmer is bad or the unit wiring is incorrect 10 Check for Compressor output signal Is there 24 volts AC between CC C Yes go to Step 12 No go to Step 13 11 No Y compressor input signal Check thermostat...

Страница 29: ...6 0 144374 22 0 43554 60 0 15310 98 0 6098 15 0 139576 23 0 42295 61 0 14921 99 0 5961 14 0 134956 24 0 41077 62 0 14544 100 0 5827 13 0 130506 25 0 39898 63 0 14177 101 0 5697 12 0 126219 26 0 38757...

Страница 30: ...onnections Manual 2100 467H FIGURE 10 NOTE Bard Models PA13242 PA13302 PA13362 A B PA13422 A B C PA13482 A B C PA13602 A B C contain the X13 Series Motors TROUBLESHOOTING GE X13 SERIES ECM2 3 MOTORS I...

Страница 31: ...tor is failed and will require replacement 24VAC R Signal through thermostat output 24VAC Common 24VAC Common 24VAC R Signal through thermostat output Model SelecTech Communication Diagnostics The Sel...

Страница 32: ...nser coil for cleaning or to service the outdoor fan first remove the side grilles 3 The fan shroud sides can then be removed for ease of access to the coil and the back side of the shroud by removing...

Страница 33: ...70 Low Side High Side 32 297 38 303 45 310 51 317 58 324 65 332 72 339 79 348 87 356 94 365 102 374 110 383 118 393 126 403 Model Return Air Temp DB WB Pressure 75 80 85 90 95 100 105 110 115 120 125...

Страница 34: ...123 380 126 406 128 432 130 459 132 487 134 515 136 544 138 574 140 611 80 67 Low Side High Side 124 315 127 339 129 364 132 390 134 416 137 443 139 471 141 499 143 529 145 558 147 589 150 626 85 72 L...

Страница 35: ...uit Ampacity Maximum External Fuse or Ckt Brkr Field Power Wire Size Ground Wire Minimum Circuit Ampacity Maximum External Fuse or Ckt Breaker Field Power Wire Size Ground Wire Size Ckt A Ckt B Ckt A...

Страница 36: ...16 on page 40 for the corresponding airflow of each tap Set the unit duct static based on the highest airflow that the unit will run at NOTE Be sure to adjust the system static or blower speed to mai...

Страница 37: ...in the ECM motor This is a user selectable airflow amount that will be higher than rated airflow Tap 4 is used for cooling operation if the orange black wire on the blower speed selection terminal blo...

Страница 38: ...With air filters installed and switch initially set at 0 4 W C see Step 2 under Dirty Filter Switch begin restricting the air filter of the unit using a piece of cardboard under the filters until the...

Страница 39: ...WISE TO DECREASE RESTRICTION AMOUNT MIS 4086 B 5 Replace the upper front panel and repeat Steps 1 3 Continue to make adjustments described in Step 4 until the desired restriction is obtained 6 Remove...

Страница 40: ...5 1435 1355 W48HC 0 00 1320 1270 1745 1665 1895 1800 1985 1860 0 10 1225 1160 1700 1615 1850 1760 1915 1810 0 15 1180 1110 1675 1585 1825 1735 1880 1780 0 20 1130 1060 1650 1555 1795 1705 1845 1755 0...

Страница 41: ...4 4 10239 5 20 8 17065 18 0 12799 12 0 17065 9 21 7 30717 18 7 23038 10 4 28260 10 41 7 34130 36 1 25598 15 62 5 51195 54 1 38396 36 1 51195 31 2 38396 17 3 47099 18 43 3 61434 37 5 46076 20 8 56519 2...

Страница 42: ...Control and Outdoor Thermostat Heat Pump LAC ODT X X BOP5 Blank Off Plate X X FAD NE5 Fresh Air Damper No Exhaust X X FAD BE5 Fresh Air Damper Barometric Exhaust X X CRV F5 Commercial Ventilator On O...

Страница 43: ...EHW3HC B15 X EHW3HC C05 X X EHW3HC C15 X EHW3HCDA10 X EHW3HCDA15 X EHW3HCDB09 X EHW3HCDB15 X EHW3HCDC05 X EHW3HCDC09 X EHW3HCDC15 X X EHW4HC A04 X EHW4HC A05 X EHW4HC A15 X EHW4HC B09 X X X EHW4HC C05...

Страница 44: ...Manual 2100 711C Page 44 of 45 GRAPH 1 W42HC FAD NE5 W O Exhaust Ventilation Delivery GRAPH 2 W48HC FAD NE5 W O Exhaust Ventilation Delivery...

Страница 45: ...Manual 2100 711C Page 45 of 45 GRAPH 3 W60HC FAD NE5 W O Exhaust Ventilation Delivery...

Отзывы: