Manual 7960-811
Page
9 of 13
1
V
alues listed are with ventilation package disabled
2
Return air temperature °F @ Rated CFM
3
Below 50°F
, unit requires a factory or field installed low ambient control.
4
Suction pr/- 4 psi, Discharge pr/- 10 psi
DB/WB
2
OD T
emp.
65°F
3
70°F
75°F
80°F
85°F
90°F
95°F
100°F
105°F
Mode
A/C
Dehum
A/C
Dehum
A/C
Dehum
A/C
Dehum
A/C
Dehum
A/C
Dehum
A/C
Dehum
A/C
Dehum
A/C
Dehum
75/62.5 (50% RH)
Total Cooling Btuh
65,400
31,900
63,800
28,500
62,100
24,700
60,500
21,600
58,800
18,000
57,000
14,300
55,200
10,500
53,300
6,600
51,400
2,600
Sensible Btuh
47,600
13,600
46,900
11,200
46,200
8,700
45,400
6,400
44,700
3,800
43,900
1,300
43,100
(1,300)
42,300
(4,000)
41,500
(6,700)
S/T
0.728
0.426
0.735
0.393
0.744
0.352
0.750
0.296
0.760
0.211
0.770
0.091
0.781
0
0.794
0
0.807
0
Latent Btuh
17,800
18,300
16,900
17,300
15,900
16,000
15,100
15,200
14,100
14,200
13,100
13,000
12,100
11,800
11,000
10,600
9,900
9,300
Lbs. H20/hr
.
16.8
17.3
15.9
16.3
15.0
15.1
14.2
14.3
13.3
13.4
12.4
12.3
11.4
11.1
10.4
10.0
9.3
8.8
Supply Air DB
75.1
75.1
75.1
75.1
75.1
75.1
75.1
75.1
75.1
75.1
75.1
75.1
75.1
75.1
75.0
75.1
75.0
75.1
Supply Air WB
62.6
62.8
62.7
62.8
62.7
62.8
62.7
62.6
62.7
62.6
62.7
62.6
62.7
62.6
62.7
62.6
62.7
62.8
Suction PSIG
4
126
118
127
119
127
120
128
122
130
123
131
124
132
125
133
127
135
128
Discharge PSIG
4
296
278
316
291
339
305
359
318
382
333
405
348
430
364
455
381
481
398
75/64.1 (55% RH)
Total Cooling Btuh
66,800
33,600
65,200
30,300
63,600
26,800
61,900
23,300
60,200
19,700
58,400
16,000
56,600
12,200
54,700
8,300
52,800
4,400
Sensible Btuh
45,000
12,000
44,300
9,600
43,500
7,200
42,800
4,700
42,000
2,200
41,200
(300)
40,400
(3,000)
39,600
(5,600)
38,800
(8,400)
S/T
0.674
0.36
0.679
0.32
0.684
0.27
0.691
0.20
0.698
0.11
0.705
0
0.714
0
0.724
0
0.735
0
Latent Btuh
21,800
21,600
20,900
20,700
20,100
19,600
19,100
18,600
18,200
17,500
17,200
16,300
16,200
15,200
15,100
13,900
14,000
12,800
Lbs. H20/hr
.
20.6
20.4
19.7
19.5
19.0
18.5
18.0
17.5
17.2
16.5
16.2
15.4
15.3
14.3
14.2
13.1
13.2
12.1
Supply Air DB
75.1
75.1
75.1
75.1
75.1
75.1
75.1
75.1
75.1
75.1
75.0
75.1
75.0
75.1
75.0
75.1
75.0
75.1
Supply Air WB
64.1
64.2
64.1
64.1
64.1
64.1
64.1
64.1
64.1
64.1
64.1
64.1
64.1
64.1
64.1
64.1
64.1
64.1
Suction PSIG
4
129
121
130
122
131
124
132
125
133
126
134
127
135
129
137
130
138
132
Discharge PSIG
4
298
282
318
295
340
308
362
322
384
337
408
352
432
368
458
385
484
402
75/65.5 (60% RH)
Total Cooling Btuh
68,200
35,300
66,600
32,000
65,000
28,100
63,300
25,000
61,600
21,400
59,800
17,700
58,000
13,900
56,100
10,100
54,200
6,100
Sensible Btuh
42,300
10,300
41,600
8,000
40,900
5,400
40,100
3,100
39,400
600
38,600
(2,000)
37,800
(4,600)
37,000
(7,300)
36,100
(10,000)
S/T
0.620
0.292
0.625
0.250
0.629
0.192
0.633
0.124
0.640
0.028
0.645
0
0.652
0
0.660
0
0.666
0
Latent Btuh
25,900
25,000
25,000
24,000
24,100
22,700
23,200
21,900
22,200
20,800
21,200
19,700
20,200
18,500
19,100
17,400
18,100
16,100
Lbs. H20/hr
.
24.4
23.6
23.6
22.6
22.7
21.4
21.9
20.7
20.9
19.6
20.0
18.6
19.1
17.5
18.0
16.4
17.1
15.2
Supply Air DB
75.1
75.0
75.1
75.0
75.1
75.0
75.0
75.0
75.0
75.0
75.0
75.0
75.0
75.0
75.0
75.0
75.0
75.1
Supply Air WB
65.3
65.5
65.4
65.5
65.4
65.4
65.4
65.3
65.4
65.3
65.4
65.3
65.4
65.3
65.4
65.3
65.4
65.5
Suction PSIG
4
132
125
133
126
134
127
135
128
136
129
137
131
139
132
140
133
141
135
Discharge PSIG
4
301
286
321
299
344
313
364
326
387
341
410
356
435
372
460
389
486
406
75/66.7 (65% RH)
Total Cooling Btuh
69,600
37,100
68,000
33,700
66,400
29,900
64,700
26,800
63,000
23,100
61,200
19,400
59,400
15,700
57,600
11,800
55,600
7,800
Sensible Btuh
39,700
8,700
38,900
6,400
38,200
3,800
37,500
1,500
36,700
(1,000)
35,900
(3,600)
35,100
(6,200)
34,300
(8,900)
33,500
(11,600)
S/T
0.570
0.23
0.572
0.19
0.575
0.13
0.580
0.06
0.583
0
0.587
0
0.591
0
0.595
0
0.603
0
Latent Btuh
29,900
28,400
29,100
27,300
28,200
26,100
27,200
25,300
26,300
24,100
25,300
23,000
24,300
21,900
23,300
20,700
22,100
19,400
Lbs. H20/hr
.
28.2
26.8
27.5
25.8
26.6
24.6
25.7
23.9
24.8
22.7
23.9
21.7
22.9
20.7
22.0
19.5
20.8
18.3
Supply Air DB
75.0
75.0
75.1
75.0
75.1
75.0
75.0
75.0
75.0
75.0
75.0
75.0
75.0
75.0
75.0
75.0
74.9
75.0
Supply Air WB
66.7
66.8
66.8
66.8
66.8
66.8
66.8
66.7
66.8
66.7
66.8
66.7
66.8
66.7
66.8
66.7
66.8
66.8
Suction PSIG
4
136
128
137
129
138
130
139
131
140
133
141
134
142
135
143
137
145
138
Discharge PSIG
4
303
290
324
303
347
317
367
330
389
345
413
360
437
376
463
393
489
410
75/68 (70%
RH)
Total Cooling Btuh
71,000
38,800
69,400
35,500
67,800
31,600
66,100
28,500
64,400
24,900
62,700
21,200
60,800
17,400
59,000
13,500
57,100
9,600
Sensible Btuh
37,000
7,100
36,300
4,700
35,600
2,200
34,800
(100)
34,000
(2,600)
33,300
(5,200)
32,500
(7,800)
31,600
(10,500)
30,800
(13,200)
S/T
0.521
0.183
0.523
0.132
0.525
0.070
0.526
0
0.528
0
0.531
0
0.535
0
0.536
0
0.539
0
Latent Btuh
34,000
31,700
33,100
30,800
32,200
29,400
31,300
28,600
30,400
27,500
29,400
26,400
28,300
25,200
27,400
24,000
26,300
22,800
Lbs. H20/hr
.
32.1
29.9
31.2
29.1
30.4
27.7
29.5
27.0
28.7
25.9
27.7
24.9
26.7
23.8
25.8
22.6
24.8
21.5
Supply Air DB
75.0
75.0
75.0
75.0
75.0
75.0
75.0
75.0
75.0
75.0
75.0
75.0
75.0
75.0
74.9
75.0
74.9
75.0
Supply Air WB
68.0
68.2
68.1
68.2
68.1
68.1
68.1
68.0
68.1
68.0
68.1
68.0
68.1
68.0
68.1
68.0
68.1
68.1
Suction PSIG
4
139
131
140
132
141
134
142
135
143
136
144
137
146
139
147
140
148
142
Discharge PSIG
4
306
294
326
307
349
321
369
334
392
349
416
364
440
380
465
397
491
414
80/68.3 (55% RH)
Total Cooling Btuh
71,300
39,200
69,700
35,900
68,100
32,000
66,400
28,900
64,700
25,300
63,000
21,600
61,100
17,800
59,300
14,000
57,400
10,000
Sensible Btuh
45,900
13,600
45,100
11,200
44,400
8,700
43,600
6,400
42,900
3,800
42,100
1,300
41,300
(1,300)
40,500
(4,000)
39,700
(6,700)
S/T
0.644
0.35
0.647
0.31
0.652
0.27
0.657
0.22
0.663
0.15
0.668
0.06
0.676
0
0.683
0
0.692
0
Latent Btuh
25,400
25,600
24,600
24,700
23,700
23,300
22,800
22,500
21,800
21,500
20,900
20,300
19,800
19,100
18,800
18,000
17,700
16,700
Lbs. H20/hr
.
24.0
24.2
23.2
23.3
22.4
22.0
21.5
21.2
20.6
20.3
19.7
19.2
18.7
18.0
17.7
17.0
16.7
15.8
Supply Air DB
84.0
80.1
84.0
80.1
84.0
80.1
84.0
80.1
84.0
80.1
83.9
80.1
83.9
80.1
83.9
80.1
83.9
80.1
Supply Air WB
68.3
68.4
68.4
68.4
68.4
68.3
68.5
68.2
68.5
68.2
68.5
68.2
68.5
68.2
68.5
68.2
68.5
68.3
Suction PSIG
4
140
132
141
133
142
134
143
135
144
137
145
138
146
139
148
141
149
142
Discharge PSIG
4
306
295
326
308
349
322
369
336
392
350
416
366
440
381
465
398
491
415
W60ACDA Cooling and Dehumidification Application Data
1
Содержание 11EER WA W18AB-A
Страница 2: ......
Страница 24: ......
Страница 67: ......
Страница 71: ...Manual 2110 1449H Page 4 of 12 FUNCTIONAL COMPONENTS 10 11 2 3 1 4 5 6 9 8 7 12 13 14 15 SEXP 949...
Страница 75: ...Manual 2110 1449H Page 8 of 12 CONTROL PANEL 14 13 6 15 18 16 4 11 7 10 9 1 3 12 17 5 2 SEXP 908...
Страница 77: ...Manual 2110 1449H Page 10 of 12 CONTROL PANEL 7 17 11 12 16 3 10 8 13 15 14 9 4 5 6 18 1 2 SEXP 948...
Страница 80: ......
Страница 83: ......
Страница 97: ......