Manual 7960-811
Page
7 of 13
1
V
alues listed are with ventilation package disabled
2
Return air temperature °F @ Rated CFM
3
Below 50°F
, unit requires a factory or field installed low ambient control.
4
Suction pr/- 4 psi, Discharge pr/- 10 psi
DB/WB
2
OD T
emp.
65°F
3
70°F
75°F
80°F
85°F
90°F
95°F
100°F
105°F
Mode
A/C
Dehum
A/C
Dehum
A/C
Dehum
A/C
Dehum
A/C
Dehum
A/C
Dehum
A/C
Dehum
A/C
Dehum
A/C
Dehum
75/62.5 (50% RH)
Total Cooling Btuh
45,900
22,500
44,500
19,700
43,200
16,800
41,800
14,000
40,600
11,000
39,300
8,000
38,100
4,900
36,900
1,700
35,700
Sensible Btuh
33,300
9,200
32,600
7,000
32,100
4,900
31,500
2,500
30,900
300
30,300
(2,000)
29,800
(4,300)
29,300
(6,600)
28,800
(9,000)
S/T
0.725
0.409
0.733
0.355
0.743
0.292
0.754
0.179
0.761
0.027
0.771
0
0.782
0
0.794
0
0.807
0
Latent Btuh
12,600
13,300
11,900
12,700
11,100
11,900
10,300
11,500
9,700
10,700
9,000
10,000
8,300
9,200
7,600
8,300
6,900
7,500
Lbs. H20/hr
.
11.9
12.5
11.2
12.0
10.5
11.2
9.7
10.8
9.2
10.1
8.5
9.4
7.8
8.7
7.2
7.8
6.5
7.1
Supply Air DB
52.6
66.1
53.0
68.3
53.3
70.4
53.8
72.6
54.2
74.8
54.5
76.9
54.9
79.1
55.3
81.4
55.6
83.6
Supply Air WB
50.8
54.9
51.2
55.9
51.6
56.8
51.9
58.0
52.3
59.0
52.6
60.1
52.9
61.1
53.3
62.1
53.6
63.2
Suction PSIG
4
119
108
120
109
121
110
122
112
123
114
125
116
126
118
127
121
129
124
Discharge PSIG
4
274
243
295
260
315
273
339
292
362
307
384
322
407
335
431
348
455
360
75/64.1 (55% RH)
Total Cooling Btuh
47,200
24,000
45,800
21,200
44,500
18,300
43,200
15,400
41,900
12,400
40,600
9,400
39,400
6,300
38,200
3,200
37,000
Sensible Btuh
31,500
8,200
30,900
6,000
30,300
3,800
29,700
1,500
29,100
(700)
28,600
(3,000)
28,000
(5,300)
27,500
(7,600)
27,000
(10,000)
S/T
0.667
0.34
0.675
0.28
0.681
0.21
0.688
0.10
0.695
0
0.704
0
0.711
0
0.720
0
0.730
0
Latent Btuh
15,700
15,800
14,900
15,200
14,200
14,500
13,500
13,900
12,800
13,100
12,000
12,400
11,400
11,600
10,700
10,800
10,000
10,000
Lbs. H20/hr
.
14.8
14.9
14.1
14.3
13.4
13.7
12.7
13.1
12.1
12.4
11.3
11.7
10.8
10.9
10.1
10.2
9.4
9.4
Supply Air DB
53.8
67.1
54.2
69.2
54.6
71.4
54.9
73.5
55.3
75.7
55.7
77.9
56.1
80.1
56.4
82.3
56.8
84.5
Supply Air WB
52.2
56.0
52.6
57.0
53.0
58.0
53.3
59.0
53.7
60.1
54.0
61.1
54.3
62.2
54.6
63.2
54.9
64.3
Suction PSIG
4
122
111
123
112
124
113
125
115
126
117
128
119
129
122
130
124
132
128
Discharge PSIG
4
275
246
297
263
319
280
341
295
363
310
386
325
409
338
433
351
456
363
75/65.5 (60% RH)
Total Cooling Btuh
48,500
25,400
47,100
22,600
45,800
19,700
44,500
16,900
43,200
13,900
41,900
10,900
40,700
7,800
39,500
4,600
38,400
1,400
Sensible Btuh
29,700
7,200
29,100
5,000
28,500
2,900
27,900
500
27,400
(1,700)
26,800
(4,000)
26,300
(6,300)
25,700
(8,600)
25,200
(11,000)
S/T
0.612
0.283
0.618
0.221
0.622
0.147
0.627
0.030
0.634
0
0.640
0
0.646
0
0.651
0
0.656
0
Latent Btuh
18,800
18,200
18,000
17,600
17,300
16,800
16,600
16,400
15,800
15,600
15,100
14,900
14,400
14,100
13,800
13,200
13,200
12,400
Lbs. H20/hr
.
17.7
17.2
17.0
16.6
16.3
15.8
15.7
15.5
14.9
14.7
14.2
14.1
13.6
13.3
13.0
12.5
12.5
11.7
Supply Air DB
54.9
68.0
55.3
70.2
55.6
72.3
56.1
74.5
56.5
76.7
56.9
78.8
57.2
81.0
57.6
83.3
58.0
85.5
Supply Air WB
53.6
57.0
54.0
58.1
54.3
59.0
54.7
60.1
55.0
61.1
55.4
62.2
55.7
63.2
56.0
64.3
56.3
65.3
Suction PSIG
4
125
114
126
115
127
117
128
118
129
120
131
122
132
125
134
128
135
131
Discharge PSIG
4
277
249
298
266
318
279
342
298
365
313
387
328
411
341
434
354
458
366
75/66.7 (65% RH)
Total Cooling Btuh
49,800
26,800
48,400
24,000
47,100
21,100
45,800
18,300
44,500
15,300
43,300
12,300
42,000
9,200
40,800
6,100
39,700
2,800
Sensible Btuh
28,000
6,200
27,300
4,000
26,800
1,900
26,200
(500)
25,600
(2,700)
25,000
(5,000)
24,500
(7,300)
24,000
(9,600)
23,500
(12,000)
S/T
0.562
0.23
0.564
0.17
0.569
0.09
0.572
0
0.575
0
0.577
0
0.583
0
0.588
0
0.592
0
Latent Btuh
21,800
20,600
21,100
20,000
20,300
19,200
19,600
18,800
18,900
18,000
18,300
17,300
17,500
16,500
16,800
15,700
16,200
14,800
Lbs. H20/hr
.
20.6
19.4
19.9
18.9
19.2
18.1
18.5
17.7
17.8
17.0
17.3
16.3
16.5
15.6
15.8
14.8
15.3
14.0
Supply Air DB
56.1
69.0
56.5
71.1
56.8
73.3
57.3
75.4
57.7
77.6
58.0
79.8
58.4
82.0
58.8
84.2
59.1
86.4
Supply Air WB
55.0
58.1
55.3
59.1
55.7
60.0
56.1
61.2
56.4
62.2
56.8
63.2
57.1
64.3
57.4
65.3
57.7
66.4
Suction PSIG
4
128
118
129
119
130
120
131
121
133
123
134
126
135
128
137
131
138
134
Discharge PSIG
4
279
252
300
269
320
282
344
301
366
316
389
331
412
344
436
357
459
369
75/68 (70%
RH)
Total Cooling Btuh
51,100
28,300
49,800
25,500
48,500
22,500
47,100
19,700
45,800
16,800
44,600
13,700
43,400
10,600
42,200
7,500
41,000
4,300
Sensible Btuh
26,200
5,200
25,600
3,000
25,000
900
24,400
(1,500)
23,800
(3,700)
23,300
(6,000)
22,700
(8,300)
22,200
(10,600)
21,700
(13,000)
S/T
0.513
0.184
0.514
0.118
0.515
0.040
0.518
0
0.520
0
0.522
0
0.523
0
0.526
0
0.529
0
Latent Btuh
24,900
23,100
24,200
22,500
23,500
21,600
22,700
21,200
22,000
20,500
21,300
19,700
20,700
18,900
20,000
18,100
19,300
17,300
Lbs. H20/hr
.
23.5
21.8
22.8
21.2
22.2
20.4
21.4
20.0
20.8
19.3
20.1
18.6
19.5
17.8
18.9
17.1
18.2
16.3
Supply Air DB
57.3
69.9
57.7
72.1
58.0
74.2
58.5
76.4
58.8
78.6
59.2
80.8
59.6
83.0
59.9
85.2
60.3
87.4
Supply Air WB
56.4
59.2
56.7
60.2
57.1
61.1
57.5
62.2
57.8
63.3
58.1
64.3
58.5
65.4
58.8
66.4
59.1
67.5
Suction PSIG
4
131
121
132
122
133
123
134
125
136
127
137
129
138
131
140
134
141
137
Discharge PSIG
4
280
255
302
272
322
285
345
304
368
319
391
334
414
347
437
360
461
372
80/68.3 (55% RH)
Total Cooling Btuh
51,700
29,200
50,300
26,400
49,000
23,400
47,600
20,600
46,400
17,700
45,100
14,600
43,900
11,500
42,700
8,400
41,500
5,200
Sensible Btuh
32,900
9,900
32,200
7,700
31,700
5,600
31,100
3,200
30,500
1,000
29,900
(1,300)
29,400
(3,600)
28,900
(5,900)
28,400
(8,300)
S/T
0.636
0.34
0.640
0.29
0.647
0.24
0.653
0.16
0.657
0.06
0.663
0
0.670
0
0.677
0
0.684
0
Latent Btuh
18,800
19,300
18,100
18,700
17,300
17,800
16,500
17,400
15,900
16,700
15,200
15,900
14,500
15,100
13,800
14,300
13,100
13,500
Lbs. H20/hr
.
17.7
18.2
17.1
17.6
16.3
16.8
15.6
16.4
15.0
15.8
14.3
15.0
13.7
14.2
13.0
13.5
12.4
12.7
Supply Air DB
58.0
70.4
58.4
72.5
58.7
74.6
59.2
76.8
59.6
79.0
60.0
81.2
60.4
83.4
60.7
85.6
61.1
87.8
Supply Air WB
56.3
59.2
56.7
60.2
57.0
61.2
57.4
62.3
57.7
63.3
58.1
64.4
58.4
65.4
58.7
66.4
59.0
67.5
Suction PSIG
4
131
121
132
122
133
123
135
125
136
127
137
129
139
132
140
135
141
138
Discharge PSIG
4
280
255
302
273
322
285
346
305
368
320
391
334
414
348
437
360
461
373
W42ACDA Cooling and Dehumidification Application Data
1
Содержание 11EER WA W18AB-A
Страница 2: ......
Страница 24: ......
Страница 67: ......
Страница 71: ...Manual 2110 1449H Page 4 of 12 FUNCTIONAL COMPONENTS 10 11 2 3 1 4 5 6 9 8 7 12 13 14 15 SEXP 949...
Страница 75: ...Manual 2110 1449H Page 8 of 12 CONTROL PANEL 14 13 6 15 18 16 4 11 7 10 9 1 3 12 17 5 2 SEXP 908...
Страница 77: ...Manual 2110 1449H Page 10 of 12 CONTROL PANEL 7 17 11 12 16 3 10 8 13 15 14 9 4 5 6 18 1 2 SEXP 948...
Страница 80: ......
Страница 83: ......
Страница 97: ......