1
Non-flammable hearth
2
Convection air inlet
3
Steel studs
4
TV wall mount bracket
5
TV
6
Convection air outlet
7
Concentric flue
8
Non-flammable material
4
9
Air gap and spacers
10
Non-flammable insulation plate
11
Cable duct
Figure 21. TV installation - flush mounted
A
Minimum 30 cm
B
Minimum 2.5 cm horizontal clearance between front of TV and front of the fireplace
enclosure
C
Minimum 5 cm clearance at all 4 sides of the TV
D
Minimum 2.5 cm
E
Minimum thickness 4 cm
F
Minimum 3 mm clearance between appliance and surrounding construction
4
Specifications according the installation instructions of the manufacturer of the concentric flue system
and local regulations.
Clearances
Gas Fire Front 70-60
33
Содержание Gas Fire Front 70-60 PF2
Страница 10: ...2 5 Overview of the ceramic log set Figure 3 Overview of ceramic log set Description 10 Gas Fire Front 70 60...
Страница 60: ...3 Slide the strip downwards 4 Tighten the nut wings Maintenance 60 Gas Fire Front 70 60...
Страница 61: ...5 Tilt the top panel upwards 6 Install the front panel and side panels Maintenance Gas Fire Front 70 60 61...
Страница 70: ...9 Dimensions 9 1 Gas Fire Front 70 60 PF2 with Floating Frame Gas connection Dimensions 70 Gas Fire Front 70 60...
Страница 71: ...9 2 Gas Fire Front 70 60 PF2 with Floating Frame Gas connection Dimensions Gas Fire Front 70 60 71...
Страница 74: ...9 5 Gas Fire Front 70 60 PF2 with Hidden Door Gas connection Dimensions 74 Gas Fire Front 70 60...
Страница 75: ...9 6 Gas Fire Front 70 60 PF2 with Hidden Door Gas connection Dimensions Gas Fire Front 70 60 75...
Страница 78: ...9 9 BARBAS Airbox 160 with 4 insert models Dimensions 78 Gas Fire Front 70 60...
Страница 79: ...9 10 BARBAS Airbox 320 with 4 insert models Dimensions Gas Fire Front 70 60 79...
Страница 82: ...11 EU Declaration of Conformity EU Declaration of Conformity 82 Gas Fire Front 70 60...
Страница 83: ...EU Declaration of Conformity Gas Fire Front 70 60 83...
Страница 84: ...Your Barbas dealer 002 21 07 2022 352402 248 002...