Operating Instructions
bar-positurn2 and bar-positrol
Left-rotating actuator in switch position ccw
(L)
Input and Output signal ccw increasing
Right-rotating actuator in switch position cw
(R)
Input and output signal cw increasing
Individual Settings:
Initialising / Commissioning:
Set operating direction switch according to the direction of actuation for the valve actuator.
Automatic initialisation of Positioner- and 3P-mode (Learning the end-positions and other
specific values). The automatic initialising is recommended. If it is not satisfying, initiate the
positioner manually.
When initialising, the operating direction switch must be set in accordance
with the operating direction of the valve actuator, in order to ascertain the real
function correctly. In real operation, the operating direction switch may be adjus-
ted when the increase in signal for special cases is to be changed.
1. Check whether the
operating direction
switch
has been set in accordance with
the operating direction of the actuator (L/
ccw or R/cw).
2. Make the electrical connection accor-
ding to the connection diagram.
3. Select program by the program switch:
Choose between „analog“ or „3P“ (see
also „individual settings”) .
4. Choose type of signal.
5. Set the initialisation
switch to
„Init“
.