Standard Range ZPM - Zone Pressure Sensor
in a BAPI-Box Enclosure
Building Automation Products, Inc., 750 North Royal Avenue, Gays Mills, WI 54631 USA
Tel:+1-608-735-4800 • Fax+1-608-735-4804 • E-mail:[email protected] • Web:www.bapihvac.com
2 of 5
Installation & Operations
47138_ins_ZPM_SR_BB
rev. 04/13/22
Attach the unit to its mounting surface with the four self-tapping #10x3/4” sheet
metal screws through the holes in the mounting feet. The preferred mounting
orientation is with the pressure ports facing down to prevent condensation
from entering the pressure transducer. Do not mount to a vibrating surface
as vibration may cause issues with the accuracy of the sensing element. See
page 3 for an actual size mounting template for the unit.
The two cover latch screws must be installed to achieve an IP66 rating.
After Auto-Zeroing, remove the deadhead tubing and push the system tubing
onto the port nipple without creating any kinks or holes.
If a hole must be cut into the plastic plugs in the ½” NPSM
threaded ports of the BAPI-Box enclosure, it’s recommended
to use BAPI’s Clean-Cut Tool. Not using this tool could cause
damage to the electronics of the sensor. See the Accessories
section of BAPI’s website or product catalog for more info on
the Clean-Cut Tool.
Fig. 3:
ZPM BAPI-Box Mounting
(for units without Attached Tube
option)
Fig. 5:
Cover
Latch Screws
Fig. 4:
ZPM BAPI-Box Mounting
(for units with Attached Tube option)
Mounting
Unit includes
two screws
for the hinged
cover
Unit includes a
conduit fitting and
foam pad to seal
the conduit.