background image

Standard Range ZPM - Zone Pressure Sensor

in a BAPI-Box Enclosure

Building Automation Products, Inc., 750 North Royal Avenue, Gays Mills, WI  54631 USA

Tel:+1-608-735-4800 • Fax+1-608-735-4804 • E-mail:[email protected] • Web:www.bapihvac.com

2 of 5

 Installation & Operations

47138_ins_ZPM_SR_BB

rev. 04/13/22

Attach the unit to its mounting surface with the four self-tapping #10x3/4” sheet 

metal screws through the holes in the mounting feet. The preferred mounting 

orientation is with the pressure ports facing down to prevent condensation 

from entering the pressure transducer. Do not mount to a vibrating surface 

as vibration may cause issues with the accuracy of the sensing element. See 

page 3 for an actual size mounting template for the unit.

The two cover latch screws must be installed to achieve an IP66 rating. 

After Auto-Zeroing, remove the deadhead tubing and push the system tubing 

onto the port nipple without creating any kinks or holes. 

If a hole must be cut into the plastic plugs in the ½” NPSM 

threaded ports of the BAPI-Box enclosure, it’s recommended 

to use BAPI’s Clean-Cut Tool. Not using this tool could cause 

damage to the electronics of the sensor. See the Accessories 

section of BAPI’s website or product catalog for more info on 

the Clean-Cut Tool.  

Fig. 3: 

ZPM BAPI-Box Mounting

(for units without Attached Tube 

option) 

Fig. 5: 

Cover 

Latch Screws

Fig. 4: 

ZPM BAPI-Box Mounting

(for units with Attached Tube option) 

Mounting

Unit includes 

two screws 

for the hinged 

cover

Unit includes a 

conduit fitting and 

foam pad to seal 

the conduit.

Отзывы: