AUTO-ZERO FOR STANDARD UNITS

Auto-Zeroing must be done after the initial setup, changing mounting orientation or changing any settings. For most 

applications, perform an auto-zero whenever it appears that the sensor has drifted. For critical applications, the unit 

should be zeroed 2-3 times a year.

1. Power must be on.

2. Detach system tubing and deadhead ports using the supplied 

tubing or other short length of tubing. Do not kink tubing.

3. Press and hold the Auto-Zero button for 1-2 seconds.  The 

Status LED will stop flashing when completed.

4. Remove deadhead tubing and reattach system tubing.

AUTO-ZERO FOR UNITS WITH ATTACHED TUBE

1. Power must be on.
2. Disconnect system tubing from the Low Pressure brass fitting 

and attach the supplied 6” deadhead tubing to the brass fitting.

3. Disconnect the short clear tubing from the 90° black Attached 

Tube fitting with your fingers (Fig. 9). A pliers may cut the tubing.

4. Connect the clear tubing to the supplied straight black fitting on the 6” 

tubing (Fig. 9).  Do not kink the tubing.

5. Press and hold the Auto-Zero button for 1-2 seconds.  The Status 

LED will stop flashing when completed.

6. Disconnect the deadhead tubing and reattach the clear tubing and 

system tubing.  Confirm that the clear tubing is pressed all of the way 

onto the fitting and that it is not kinked.

Fig 8:

 Auto-Zero and Status LEDs

Auto-Zero 

LED

Status 

LED

STATUS LED OPERATION

LED Off:

 No power is applied or the unit is in 4 to 20 mA Mode

LED Solid (On):

 LED is on when power is applied and a VDC 

output is selected. When 4 to 20 mA output is selected, the light is 

on for 2 seconds at power up then goes off.

LED Flashing:

 Auto-Zero. The LED will flash for about 20 seconds.

Output Termination

BAPI recommends wiring the product with power disconnected. 

Proper supply voltage, polarity and wiring connections are 

important to a successful installation.  Not observing these 

recommendations may damage the product and void the warranty.

PWR

Terminal

GND

Terminal

OUT

Terminal

Fig. 7: 

ZPM Wiring Terminals

To ensure that all wires are properly terminated, twist the stripped ends of each 

wire together before inserting into the terminals. Gently tug on the wire after 

inserting into the terminal to verify a good connection.

Auto-Zero Procedure and Status LED Operation

Output Signal

PWR Terminal

GND Terminal

OUT Terminal

4 to 20 mA

7 to 40 VDC

4 to 20 mA Signal To 

Controller Analog Input Not Used

0 to 5 or 1 to 5 VDC

7 to 40 VDC

or 18 to 32 VAC

To Controller Ground

VDC Signal To Controller 

Analog Input

0 to 10 or 2 to 10 VDC

13 to 40 VDC

or 18 to 32 VAC

To Controller Ground

VDC Signal To Controller 

Analog Input

Table 1: ZPM Termination

Fig 9:

 Deadheading 

ports on units with 

attached tube (-AT)

Supplied 

6” tubing 

Supplied 

straight 

black fitting 

for dead-

heading

High 

Port

Low 

Port

High 

Pressure 

Port

Low 

Pressure 

Port

Отзывы: