Installation & Operating Instructions

“BAPI-Stat 3” Room Sensor

Building Automation Products, Inc., 750 North Royal Avenue, Gays Mills, WI  54631 USA

Tel:+1-608-735-4800 • Fax+1-608-735-4804 • E-mail:[email protected] • Web:www.bapihvac.com

Specifications subject to change without notice.

rev. 01/30/14

24694_ins_BS3

6 of 6

POSSIBLE SOLUTIONS:

- Determine that the input is set up correctly in the controller’s and building automation 

software.

- Check wiring for proper termination
- Check for corrosion at either the controller or the sensor. Clean off the corrosion, re-strip 

the interconnecting wire and reapply the connection.  In extreme cases, replace the 

controller, interconnecting wire and/or sensor.

- Label the terminals that the interconnecting wires are connected to at the sensor end 

and the controller end. Disconnect the interconnecting wires from the controller and the 

sensor.  With the interconnecting wires separated at both ends measure the resistance 

from wire-to-wire with a multimeter. The meter should read greater than 10 Meg-ohms, 

open or OL depending on the meter you have.  Short the interconnecting wires together 

at one end.  Go to the other end and measure the resistance from wire-to-wire with a 

multimeter. The meter should read less than 10 ohms (22 gauge or larger, 250 feet or 

less).  If either test fails, replace the wire.

- Check power for proper polarity.
- Disconnect the power wires at the controller. Measure controller output for proper 

power (see specifications), if the voltage is outside the limits trouble shoot controller.  

Reconnect power wires to controller when finished. If the measured voltage is above 

the specification limit, you may have damaged the BAPI-Stat, contact your BAPI 

representative.

- Disconnect the power wires at the sensor. Measure the wires for the same voltage as 

at controller. If the voltage is different from that measured at the controller troubleshoot 

wire. Reconnect power wires to sensor when finished.

- Measure the power at the sensor with the power connected for proper power 

(see specifications), if the voltage is outside the specification limits call your BAPI 

representative.

POSSIBLE PROBLEMS

General Diagnostics

If you need more help troubleshooting a BAPI-Stat problem, see the BAPI-Stat page on our website http://www.bapihvac.com/

BapiStat_Temp.htm for the advanced trouble shooting guide.

Diagnostics

Unit does not operate