Installation & Operating Instructions
“BAPI-Stat 3” Room Sensor
Building Automation Products, Inc., 750 North Royal Avenue, Gays Mills, WI 54631 USA
Tel:+1-608-735-4800 • Fax+1-608-735-4804 • E-mail:[email protected] • Web:www.bapihvac.com
Specifications subject to change without notice.
rev. 01/30/14
24694_ins_BS3
2 of 6
JUNCTION BOX
1. Pull the wire through the wall and out of the junction box, leaving about six
inches free.
2. Pull the wire through the hole in the base plate.
3. Secure the backplate to the box using the #6-32 x 1/2 inch mounting
screws provided.
4. Terminate the unit according to the guidelines in the
Termination
section.
5. Attach Cover by latching it to the top of the base, rotating the cover down
and snapping it into place.
6. Secure the cover by backing out the lock-down screw using a 1/16” allen
wrench until it is flush with the bottom of the cover.
DRYWALL MOUNTING
1. Place the base plate against the wall where you want to mount the sensor.
2. Using a pencil, mark out the two mounting holes and the area where the
wires will come through the wall.
3. Drill two 3/16” holes in the center of each marked mounting hole. Insert a
drywall anchor into each hole.
4. Drill one 1/2” hole in the middle of the marked wiring area.
5. Pull the wire through the wall and out the 1/2” hole, leaving about six inches free.
6. Pull the wire through the hole in the base plate.
7. Secure the base to the drywall anchors using the #6 x 1” mounting screws provided.
8. Terminate the unit according to the guidelines in the
Termination
section.
9. Attach cover by latching it to the top of the base, rotating the cover down and snapping it into place.
10. Secure the cover by backing out the lock-down screw using a 1/16” allen wrench until it is flush with the sides of
the cover.
Note: In any wall-mount application, the wall temperature and the temperature of the air within the wall cavity can cause
erroneous readings. The mixing of room air and air from within the wall cavity can lead to condensation, erroneous
readings and sensor failure. To prevent these conditions, BAPI recommends sealing the conduit leading to the junction
box with fiberglass insulation.
Mounting
Fig. 3:
Front View
of BAPI-Stat 3
Front Panel Description
Fig. 2:
Mounting hardware is
provided for both junction
box and drywall
installation (junction box
installation shown).
Humidity Setpoint:
When the left set of
s
or
t
buttons are pressed, the relative humidity
setpoint will display. As the buttons are pressed again, the display will change in 1%
increments with each press. The setpoint will change only within the specified range ordered.
Temperature Setpoint:
When the right set of
s
or
t
buttons are pressed, the temperature
setpoint will display. As the buttons are pressed again, the display will change in one degree
increments with each press. The setpoint will change only within the specified range ordered.
Pressing and holding any setpoint button will auto increment/decrement the setpoint value
The setpoint will change only within the specified range (as ordered).
Override:
When the button is pressed, the Occupied/Unoccupied Icon will show
for a few seconds.
To retain the Occupied/Unoccupied Icon , you must energize J6*.
(*For more information on Occupied/Unoccupied Icon, see the “Termination” and the
“Display Occupancy Mode Termination” sections)