Installation & Operating Instructions

BAPI-Stat 4 Sensor, w/Display, Button Setpoint, Fan or System Mode Control

BA/BS4M  Temperature Sensor

Specifications subject to change without notice.

rev. 01/18/16

25188_ins_BS4M

2 of 8

Termination

BAPI recommends using twisted pair of at least 22AWG and sealant filled connectors for all wire connections. Larger 

gauge wire may be required for long runs. All wiring must comply with the National Electric Code (NEC) and local codes. 

Do NOT run this device’s wiring in the same conduit as AC power wiring.  BAPI’s tests show fluctuating and inaccurate 

signals are possible when AC power wiring is in the same conduit as the signal lines.  If you are experiencing any of these 

difficulties, please contact your BAPI representative

.

Fig. 6:

 BAPI-Stat 4M Circuit Board

TERMINAL 

DESCRIPTION

GND ........................Power Supply Ground (Common to the controller)
V+ ...........................Power Supply Hot (See specifications for voltage 

details) 

FAN.........................Fan Speed/System Mode (Resistive Output)
EXT OVR ................BAPI-Man Occ/Un-Occ indicator Input. 

Ground terminal to fill in the BAPI-Man icon for 

Occupied.

SEN1 & SEN2 ........Sensor output per order (resistive). No polarity.  *If 

the unit is a common ground configuration (-CG), 

see “Grounding Note” below.  

SET1 & SET2 .........A)  Setpoint output per order (resistive). *If the unit 

is a common ground configuration (-CG), see 

“Grounding Note” below.

 

B)  Setpoint output per order (voltage). SET1 is 

“+”, SET2 is “-”. *If the unit is a common ground 

configuration (-CG), see “Grounding Note” 

below.

OVR1 & OVR2........Override output (Dry contact)  The contact can be 

ordered as a momentary shunt across the sensor 

(-N) or as a momentary shunt across the setpoint 

(-P) or as a separate momentary contact (-J) or 

as a separate latching contact (-L#).  *If the unit 

is a common ground configuration (-CG), see 

“Grounding Note” below.  

RSEN1 & RSEN2 ...Remote sensor option (-ES).  No polarity.  *If the 

unit is a common ground configuration (-CG), 

see “Grounding Note” below.  A 10K-2 thermistor 

sensor must be ordered separately and the 

temperature value is displayed on the LCD.  Note: 

If a temperature reading is needed at the controller, 

then a second sensor must be ordered and wired 

independently.

*Grounding Note:

 

Common Ground (-CG) or Differential Ground (-DF) configurations are selected per order.  The Differential Ground 

configuration (-DF) indicates that SEN2, SET2, OVR2 and RSEN2 must all be wired separately (No internal common 

connection).  The Common Ground configuration (-CG) indicates that SEN2, SET2, OVR2 and RSEN2 are connected to 

GND internally (All internally common). This is true of all Common Ground units except when ordered with the Override as 

a Latching Switch option (-L#). In this case, OVR2 is isolated and not internally connected to SEN2, SET2 and RSEN2.

BAPI recommends wiring the product with power disconnected. Proper supply voltage, polarity and wiring 

connections are important to a successful installation.  Not observing these recommendations may damage the 

product and void the warranty.

Содержание BAPI-Stat 4M

Страница 1: ... lock down screws using a 1 16 Allen wrench until they are flush with the bottom of the cover DRYWALL MOUNTING 1 Place the base plate against the wall where you want to mount the sensor 2 Using a pencil mark out the two mounting holes and the area where the wires will come through the wall 3 Drill two 3 16 holes in the center of each marked mounting hole Insert a drywall anchor into each hole 4 Dr...

Страница 2: ...der voltage SET1 is SET2 is If the unit is a common ground configuration CG see Grounding Note below OVR1 OVR2 Override output Dry contact The contact can be ordered as a momentary shunt across the sensor N or as a momentary shunt across the setpoint P or as a separate momentary contact J or as a separate latching contact L If the unit is a common ground configuration CG see Grounding Note below R...

Страница 3: ...hermistor 7 32KΩ 43 7 F 3 65Ω 105 2 F Test and Balance Switch S1 NORM Sensor operates normally LOW Sets the sensor value low HIGH Sets the sensor value high On the Test and Balance Switch the NORM position allows the real sensor to be monitored The HIGH position forces the output to a very hot reading and the LOW position forces a very cold reading see Table below Optional Fan Speed and System Mod...

Страница 4: ...shows a fully featured sensor NUMERICAL DISPLAY The default display shows current temperature When the up down buttons are pushed then the display will show and adjust the current setpoint and hold the display for 3 to 4 seconds The unit can also be set up to display setpoint only or for setpoint lockout See Optional Technicians Adjustments section BAPI MAN ICON The BAPI Man Icon shows the status ...

Страница 5: ... Override S5 Up Adjust and S6 Down Adjust See Fig 14 After adjustment place the board back into the cover and insert the center mounting screw Do not over tighten MODE MENUS The setup mode consists of menu pages P1 through P6 for configuring the sensor The following adjustments can be done with the program jumper J16 installed P1 Temperature offset Adjust Up or Down 5 to 5 in 0 1 increments P2 Set...

Страница 6: ...d when there is a ground signal to the EXT OVR terminal of the unit For Option 9 the BAPI Man Icon stays filled or solid when the relay is closed and hollow when the relay is open For Option 10 the BAPI Man Icon is disabled but the ON or OFF Dot on the display is controlled by the EXT OVR terminal When there is a ground signal at the EXT OVR terminal the ON dot is lit Otherwise the OFF and hollow ...

Страница 7: ...ly Check that the resistance across the override output is less than 5Ω when the override is pushed Fan Mode not correct Make sure that the fan mode output is correct Remove the fan mode output wire and check the output for the correct resistance See the product label for your specific range and compare it to the resistance chart at the bottom of page 3 Don t forget to reconnect the wire When the ...

Страница 8: ...uts Dry contact 24V 1mA Occupied EXT OVR Grounded Unoccupied EXT OVR Open to Ground Display LCD Overall 2 W x 1 1 H Temp Setpoint Occupied LCD 3 5 Digits 0 6 H Occ Unocc BAPI Man Icon Filled in man is occupied Display Limits 1 0º 0 5 and 0 1 F C increments Setpoints in 1º steps Range 40 to 185 F 40 to 85 C Display Setup Temp Setpoint Temp only or Setpoint only ºF or ºC Optional Fan Speed System Mo...