background image

Installation & Operating Instructions

BAPI-Stat 4 Sensor, w/Display, Button Setpoint, Fan or System Mode Control

BA/BS4M  Temperature Sensor

Specifications subject to change without notice.

rev. 01/18/16

25188_ins_BS4M

4 of 8

FRONT PANEL BUTTONS

SETPOINT:

 

When pressed, the setpoint will display for three to four seconds. When pressed again, the setpoint will change 

in one degree increments. It will only change within the setpoint range that was ordered.

OVERRIDE:

 

When the override button is pressed, the BAPI-Man will be displayed as “Solid” for 3-5 seconds and the override 

output will shunt or short for 3 seconds depending on the override option selected.  (-N Option = Momentary 

Temperature Sensor Shunt to <15Ω, -P Option = Momentary Setpoint Shunt to <15Ω, -J Option = Momentary Override as 

a Separate Shorting Contact Output, -L# Option = Override as a Latching Switch, See “Latching Override Operation” on 

pg. 5.)  If the occupied input (EXT OVR) terminal is grounded, then the BAPI-Man will stay filled in, indicating an occupied 

state. If the input is open, then the BAPI-Man will revert to hollow, indicating unoccupied (or the icon will disappear 

completely if there has never been a ground on the EXT OVR terminal).

MODE:

Cycles through ‘HEAT’, ‘OFF’ and ‘COOL’.

FAN:

Cycles through ‘AUTO’, ‘ON’ and Fan Speed (see Fig. 12).

A display is standard for all BA/BS4M 

units. It is available with an optional 

override button, setpoint buttons, fan 

control or system control buttons or any 

option combination. Fig. 10 shows a fully 

featured sensor.

NUMERICAL DISPLAY:

The default display shows current 

temperature.  When the up/down buttons 

are pushed, then the display will show 

and adjust the current setpoint and hold 

the display for 3 to 4 seconds. The unit 

can also be set up to display setpoint 

only or for setpoint lockout. See “Optional 

Technicians Adjustments” section.

BAPI-MAN ICON:

 

The BAPI-Man Icon shows the status of 

the room – Solid for Occupied, Hollow for 

“Unoccupied” (Fig. 11). 

Note:

 The unit must receive a 

confirmation (ground) signal on the “EXT OVR” 

terminal for the BAPI-Man to remain visible on the 

screen. Pressing the Override button will light the 

BAPI-Man icon; however, if no confirmation signal is 

received, then the BAPI-Man will go blank (disappear) 

after 5 seconds. 
Upon receiving a first confirmation (ground) signal 

on the “EXT OVR” terminal, the BAPI-Man will show 

occupied (Solid). The BAPI-Man will then show 

unoccupied (Hollow) whenever the confirmation signal 

is removed and occupied when the signal is returned. 

The only way to blank the BAPI-Man from the display 

at this point is to cycle power.

Front Panel & Control Descriptions

Fig. 10:

  BAPI-Stat 4M unit with Override, Setpoint, Fan 

& System Buttons.

Note: 

 BAPI-Stat 4M shown with five buttons. Two, 

three or five buttons may be present.

 

Occupied or Unoccupied Icon

Fan and Speed Indicator

Heat Mode

Cool Mode

Automatic System Mode

System Mode Button

Override Button

Fan Speed Button

Engineering Units

Temperature Display 

in .5 Increments

Override On

Override Off

Setpoint Up/Down 

Buttons

Fig. 12:

 Fan Speed 

Indicator

Fan Speed 

Low

Fan Speed 

Medium

Fan Speed 

High

 Hollow 

equals 

“Unoccupied”

Fig. 11: 

BAPI-Man Icon

 Solid 

equals 

“Occupied”

Содержание BAPI-Stat 4M

Страница 1: ... lock down screws using a 1 16 Allen wrench until they are flush with the bottom of the cover DRYWALL MOUNTING 1 Place the base plate against the wall where you want to mount the sensor 2 Using a pencil mark out the two mounting holes and the area where the wires will come through the wall 3 Drill two 3 16 holes in the center of each marked mounting hole Insert a drywall anchor into each hole 4 Dr...

Страница 2: ...der voltage SET1 is SET2 is If the unit is a common ground configuration CG see Grounding Note below OVR1 OVR2 Override output Dry contact The contact can be ordered as a momentary shunt across the sensor N or as a momentary shunt across the setpoint P or as a separate momentary contact J or as a separate latching contact L If the unit is a common ground configuration CG see Grounding Note below R...

Страница 3: ...hermistor 7 32KΩ 43 7 F 3 65Ω 105 2 F Test and Balance Switch S1 NORM Sensor operates normally LOW Sets the sensor value low HIGH Sets the sensor value high On the Test and Balance Switch the NORM position allows the real sensor to be monitored The HIGH position forces the output to a very hot reading and the LOW position forces a very cold reading see Table below Optional Fan Speed and System Mod...

Страница 4: ...shows a fully featured sensor NUMERICAL DISPLAY The default display shows current temperature When the up down buttons are pushed then the display will show and adjust the current setpoint and hold the display for 3 to 4 seconds The unit can also be set up to display setpoint only or for setpoint lockout See Optional Technicians Adjustments section BAPI MAN ICON The BAPI Man Icon shows the status ...

Страница 5: ... Override S5 Up Adjust and S6 Down Adjust See Fig 14 After adjustment place the board back into the cover and insert the center mounting screw Do not over tighten MODE MENUS The setup mode consists of menu pages P1 through P6 for configuring the sensor The following adjustments can be done with the program jumper J16 installed P1 Temperature offset Adjust Up or Down 5 to 5 in 0 1 increments P2 Set...

Страница 6: ...d when there is a ground signal to the EXT OVR terminal of the unit For Option 9 the BAPI Man Icon stays filled or solid when the relay is closed and hollow when the relay is open For Option 10 the BAPI Man Icon is disabled but the ON or OFF Dot on the display is controlled by the EXT OVR terminal When there is a ground signal at the EXT OVR terminal the ON dot is lit Otherwise the OFF and hollow ...

Страница 7: ...ly Check that the resistance across the override output is less than 5Ω when the override is pushed Fan Mode not correct Make sure that the fan mode output is correct Remove the fan mode output wire and check the output for the correct resistance See the product label for your specific range and compare it to the resistance chart at the bottom of page 3 Don t forget to reconnect the wire When the ...

Страница 8: ...uts Dry contact 24V 1mA Occupied EXT OVR Grounded Unoccupied EXT OVR Open to Ground Display LCD Overall 2 W x 1 1 H Temp Setpoint Occupied LCD 3 5 Digits 0 6 H Occ Unocc BAPI Man Icon Filled in man is occupied Display Limits 1 0º 0 5 and 0 1 F C increments Setpoints in 1º steps Range 40 to 185 F 40 to 85 C Display Setup Temp Setpoint Temp only or Setpoint only ºF or ºC Optional Fan Speed System Mo...

Отзывы: