background image

Termination and Troubleshooting

Water Leak Detector (BA/LDT) 5 Amp Relays

Building Automation Products, Inc., 750 North Royal Avenue, Gays Mills, WI  54631 USA

Tel:+1-608-735-4800 • Fax+1-608-735-4804 • E-mail:[email protected] • Web:www.bapihvac.com

rev. 09/01/21

26268_ins_LDT

5 of 6

INDICATION/CONTROLS   DESCRIPTION

Red LED

 ......................................LED illuminates when water is detected

Green LED ..................................LED illuminates when normal power is applied

Reset Button (SW1)

.....................

Resets manual alarm contact (only if water is no longer present)

FIELD CONFIGURABLE JUMPER (J1) SET UP

The jumpers on J1 are used to set whether the relays 

are “Latching” or “Non-Latching”, and whether they are 

“Supervised” or “Unsupervised”. These setting are described 

in the Operation Sequence section below.

OPERATION SEQUENCE

When power is applied, the green LED will illuminate and 

the unit will start to detect for water at the sensor probe. 

When there is no detection of water (normal condition), the 

relays are not in an alarm state and the red LED remains 

off. For units in the “Unsupervised” relay mode, the relays are de-energized. For units in the “Supervised” relay 

mode (default), the relays will be energized. (Note: When there is a loss of power, a supervised relay will drop out 

indicating a water detection alarm.) 
Within 5 seconds of water detection, the relays go into an alarm state and the red LED illuminates. For units in the 

“Unsupervised” relay mode, the relays are energized.  For units in the “Supervised” relay mode (default), the relays 

are de-energized.
If the unit is in “Non-latching” or auto-reset (default) operation, then the alarm state will automatically reset when the 

water has dried up. If the unit is in “Latching” or manual-reset operation, then the unit will stay in an alarm state until 

the reset button is pressed or power is cycled. If there is still water detected during a reset button push, the unit will 

not reset.  If there is still water detected after a power interrupt, the unit will initiate another alarm within 5 seconds.

COMMISSIONING

1.  After the unit is installed and wired, turn on the power. (24VAC +/- 10%)
2.  Check that the green LED is “on”. If it is not “on”, check the power source.
3.  Dampen a cloth or sponge and touch both the sensor probe tip and the sensor base. An alarm should occur 

within 5 seconds. 

4.  The red LED should illuminate and the relay(s) should de-energize, or energize if set up as unsupervised. (To 

check relay status, measure the resistance at the relay contacts or monitor the status from the BAS screen.)

5.  Remove the dampened rag or sponge to clear the alarm. If the unit is set up for a non-latching relay (J1 jumper 

across the “N” pins), the red LED and relay(s) will energize, or de-energize if set up as a unsupervised relay. If 

the unit is set up for a latching relay (J1 jumper across the “L” pins), the operator must push the reset switch on 

the detector board or interrupt power to clear the alarm.

6.  Check the depth screw (see Mounting Section) to be sure it’s at the appropriate water depth for alarm.

Set Up and Commissioning

Detectable Liquids

The sensors are designed to detect the presence of water and other conductive fluids. BAPI has performed tests on 

multiple liquid types to see which are detectable and which are not. Before leaving the installation, always check the 

sensor with the liquid you are trying to detect as every environment and application may be different.

DETECTABLE: 

Water, De-ionized water, Distilled Water, Reverse Osmosis (RO) Water

NOT DETECTABLE:

 Oil, Diesel Fuel, Unleaded Fuel

Fig. 16:

Reset Button

Fig. 17:

 Jumper J1 Settings

Non-Latching

Unsupervised

Latching

Unsupervised

Non-Latching

Supervised

Latching

Supervised

Отзывы: