Termination and Troubleshooting

Water Leak Detector (BA/LDT) 5 Amp Relays

Building Automation Products, Inc., 750 North Royal Avenue, Gays Mills, WI  54631 USA

Tel:+1-608-735-4800 • Fax+1-608-735-4804 • E-mail:[email protected] • Web:www.bapihvac.com

rev. 09/01/21

26268_ins_LDT

2 of 6

Mounting

ATTACHED SENSOR

1. Set the sensor in a location where a water leak is likely 

to occur.

2. Use the 4 screw holes on the feet of the bracket to 

secure the sensor.

3. Adjust the depth screw with the wing nut to set the 

alarm depth for detecting leaks as shown in Fig. 5.

4. Terminate the unit as described in the Termination 

section.

REMOTE SPOT SENSOR

1. The sensor can be secured to a flat surface using the 

adhesive mounting strips (Fig. 7) or a screw (Fig. 8). 

It can also be mounted to a drip pan rim using the 

provided 7/64” hex set screws as shown in Fig. 6. If 

using the adhesive mounting strip, clean the surface 

before adhering.

2. Adjust the depth screw with the wing nut to set the 

alarm depth for detecting leaks as shown in Fig. 9.

3. Mount the BAPI-Box with the transmitter in a visible 

location within cable length of the Remote Spot 

Sensor.

4. Terminate the unit as described in the Termination 

section.

ROPE SENSOR

1. The sensor can be laid on the floor or around pipes as 

shown in Figs. 10, 11, 12, & 13.

2. Secure the sensor by using cable clamps.
3. Mount the BAPI-Box with the transmitter in a visible 

location within cable length of the Rope Sensor.

4. Terminate the unit as described in the Termination 

section.

Fig. 5: 

Leak Detector with Attached Sensor

(Attached sensor can also be mounted to a drip 

pan rim using the provided 7/64” hex set screws 

as shown above.)

Fig. 8:

 Remote 

Sensor Floor 

Mount

Installer-provided 

mounting screws

Fig. 6:

 Remote Spot Sensor Pan Rim Mounting

Detection depth 

adjust screw

Pan edge 

mounting screws 

(7/64” hex)

Firmly push down 

on clean surface

Fig. 7:

 Remote Spot Sensor Tape Mount

Detection depth 

adjust screw

Reference probe

Up

Down

Fig. 9:

 Remote 

Spot Sensor 

Depth Adjust

Detection depth 

adjust from 1/16” 

to 1/2” depth

1.  Loosen wing nut.

2.  Set the required depth of the 

sensor probe screw using a #2 

Phillips screwdriver.

3.  Hold the sensor probe screw 

stationary with the screwdriver.

4.  Turn the wing nut down the probe 

screw until it engages the plastic.

5.  Tighten the wing nut 1/4 turn into 

the plastic.

Sensor Probe

Screw

Mounting

Nut