![Banner Sure Cross DXM1000-B Series Скачать руководство пользователя страница 31](http://html1.mh-extra.com/html/banner/sure-cross-dxm1000-b-series/sure-cross-dxm1000-b-series_instruction-manual_471855031.webp)
4.8 Outputs
The base board is a Modbus slave device (Slave ID 203) that communicates to the processor using Modbus commands. Use
the DXM Configuration Software to create write maps that will access outputs on the board.
Communication with the board runs at a maximum rate of 10 ms per transaction. The parameter setting for the bus with the
board and the processor board are fixed. External Modbus communication runs at a maximum rate of 50 ms per transaction.
The parameter settings for the external RS-485 buses are controlled by the DXM Configuration Software.
Refer to the Modbus Registers section for more descriptions of each Modbus register on the DXM700-Bx Wireless Controller.
4.8.1 Modbus I/O Registers for the Base Board
Modbus Registers for the Base Board Outputs (Modbus Slave ID 203)
Modbus Register
Range
Description
2101
0–1
PNP Output 1
2102
0–1
PNP Output 2
2103
0–1
PNP Output 3
2104
0–1
PNP Output 4
Sure Cross
®
DXM700-Bx Wireless Controller
www.bannerengineering.com - Tel: + 1 888 373 6767