2 Installation Instructions

2.1 Mechanical Installation

The SSA-EB1PLx-0Dx Series Lighted Emergency Stop Button with ISD is supplied with all necessary mounting hardware.

Important: Install the emergency stop in a manner that discourages tampering or defeat. Mount

emergency stops to prevent bypassing at the terminal chamber or quick disconnect (QD) connection.

The hardware supplied with the 30 mm mount SSA-EB1PLx-0Dx..ECQ.. series includes a jam nut, lock washer, lock ring,

and seal washer. Use the lock ring to prevent rotation if a 5 mm keyway is provided in the 30 mm mounting hole. The

threaded base contains external M30 threads for the supplied jam nut, as well as internal ½-14 NPSM threads for an

alternate mounting option.
The hardware supplied with the flush mount SSA-EB1PLx-0Dx..ED1Q.. series includes four M5 screws and nuts.

M30 jam nut 
Torque to 4.5 N-m 
(40 in-lbf)

Lock Ring 
To be used in place of lock 
washer when mounted 
through a keyed hole

Figure 3. Mounting the ..ECQ (30 mm) models

4X M5 hardware 
Torque to 0.56 N-m 
(5 in-lbf)

Figure 4. Mounting the ..ED1Q (flush mount) model

2.2 Installation Requirements

The device is intended for indoor use only and must not be affected by environmental conditions. Install the device so that

operation is not impeded, but protected against inadvertent operation (for example, accidental actuation by being bumped

or leaned against). Do not operate the switch using a tool. Do not expose the switch to excessive shocks and vibrations,

otherwise the switch may be deformed or damaged, causing malfunction or operation failure.
Electrical installation must be made by qualified personnel

1

 and must comply with NEC (National Electrical Code), ANSI/

NFPA 79 or IEC/EN 60204-1, and all applicable local standards. It is not possible to give exact wiring instructions for a

device that interfaces to a multitude of machine control configurations. The following is general in nature; it is recommended

to perform a risk assessment to ensure appropriate application, interfacing/connection, and risk reduction (see ISO 12100

or ANSI B11.0).

1

A person who, by possession of a recognized degree or certificate of professional training, or who, by extensive knowledge, training and
experience, has successfully demonstrated the ability to solve problems relating to the subject matter and work.

 

 

SSA-EB1PLx-0Dx Series Lighted Emergency Stop Button with ISD

 

www.bannerengineering.com - Tel: + 1 888 373 6767

5

Содержание SSA-EB1PL 0D Series

Страница 1: ...SSA EB1PLx 0Dx Series Lighted Emergency Stop Button with ISD Instruction Manual Original Instructions 215157 Rev A 3 August 2020 Banner Engineering Corp All rights reserved 215157...

Страница 2: ...Using the Quick Disconnect QD 8 2 5 Checkout 10 2 6 Resetting the Inputs 10 2 7 In Series Diagnostic ISD Information 11 2 8 Installing the Silicone Cover 11 3 Specifications 12 3 1 Dimensions 12 4 Ac...

Страница 3: ...SSA EB1PLXR 0DECQ8 None SSA EB1PLGR 0DECQ8 Green SSA EB1PLYR 0DECQ8R Yes Yellow SSA EB1PLXR 0DECQ8R None SSA EB1PLGR 0DECQ8R Green SSA EB1PLYR 0DED1Q8 Flush No Yellow SSA EB1PLXR 0DED1Q8 None SSA EB1P...

Страница 4: ...more devices to the same safety module controller in series Connecting devices in parallel defeats the switch contact monitoring ability of the module and creates an unsafe condition that could resul...

Страница 5: ...s The device is intended for indoor use only and must not be affected by environmental conditions Install the device so that operation is not impeded but protected against inadvertent operation for ex...

Страница 6: ...master stop control element it switches such that a failure causes a loss of the safety stop command or the failure allows the safety function to be suspended overridden or defeated Connect both OSSD...

Страница 7: ...ro The SSA EB1PLx 0Dx Series Lighted Emergency Stop Button with ISD can be connected in series or individually to a compatible Banner XS26 2 or SC10 2ro Safety Controller See the XS26 2 SC10 Safety Co...

Страница 8: ...Connect the female 4 pin M12 Euro style cable to the male 4 pin M12 Euro style of the series connection t adapter SI RFA TS 2 If a manual reset model emergency stop device is used connect the female 8...

Страница 9: ...ay be needed refer to Figure 11 on p 10 For using ISD information to monitor the individual device voltages see In Series Diagnostic ISD Information on p 11 There are two options to connect an additio...

Страница 10: ...e contamination Replace the switch and or appropriate components when any parts or assemblies are damaged broken deformed or badly worn or if the electrical mechanical specifications for the environme...

Страница 11: ...ce information to be loaded into the machine control system To interpret this information Banner diagnostic modules are available including the SI RF DM1 Diagnostic Module and the SC10 2roe Safety Con...

Страница 12: ...of following ISD devices Housing Button Flush mount models Polycarbonate Polyamide 10 or M5 M5 hardware included Max tightening torque 0 56 N m 5 in lbf Housing Button 30 mm models Polycarbonate Poly...

Страница 13: ...wn silicone cover SSA EB1P ECWC DTM1 102 1 4 02 109 5 4 31 65 2 56 65 2 56 33 1 30 14 7 0 58 80 3 3 16 80 8 3 18 4X 5 5 0 22 10 2 0 40 Figure 14 Flush mount models SSA EB1PLx 0Dx Series Lighted Emerge...

Страница 14: ...lack 5 Gray MQDC1 506 2 m 6 5 ft MQDC1 515 5 m 16 4 ft MQDC1 530 9 m 29 5 ft MQDC1 506RA 2 m 6 5 ft Right Angle 32 Typ 1 26 30 Typ 1 18 14 5 0 57 M12 x 1 MQDC1 515RA 5 m 16 4 ft MQDC1 530RA 9 m 29 5 f...

Страница 15: ...ft MQDEC 420RS 6 10 m 20 ft MQDEC 430RS 9 14 m 30 2 ft MQDEC 450RS 15 2 m 49 9 ft 8 Pin Threaded M12 Euro Style Cordsets Double Ended Model 8 pin 8 pin 4 Length Style Dimensions Pinout DEE2R 81D 0 3 m...

Страница 16: ...SI RFA DM1 SI RF Diagnostic Module with 8 digital outputs and 1 diagnostic circuit Interfaces IO Link USB 2 0 SSA EB1P ECWC FDA grade silicone cover 4 4 Safety Controllers Safety Controllers provide a...

Страница 17: ...r external device monitoring is required in the application See datasheet p n 141249 for more information Model Description UM FA 9A 3 normally open N O redundant output 6 amp contacts UM FA 11A 2 nor...

Страница 18: ...l X Double flash red OFF Faults that do not immediately compromise the safe operation of the emergency stop device for example safety output to external potential crosswire short safety output result...

Страница 19: ...Input 2 1 0 ISD device input 2 is on Local reset expected 1 0 An ISD device with the latch feature requires a reset Operating voltage warning 1 0 Voltage to the ISD device is at the limit of specific...

Страница 20: ...the Banner product THIS LIMITED WARRANTY IS EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES WHETHER EXPRESS OR IMPLIED INCLUDING WITHOUT LIMITATION ANY WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PART...

Отзывы: