background image

Cyclic Data about the Chain

Short Name

Data Format

Description

Order mismatch

1/0

The order of devices in the chain does not match the configuration

No ISD data detected

1/0

No (or corrupted) ISD data being transmitted (being received by diagnostic device)

Incompatible device

1/0

The chain or a unit in the chain has data but not ISD data

ISD detected not configured

1/0

ISD data detected on inputs that are not configured as ISD input

Terminator missing

1/0

Terminator plug not present (or inputs to first device low)

Actuator not taught

1/0

Not applicable

Wrong actuator detected

1/0

Not applicable

Internal unit error

1/0

A unit in the chain has an internal error

Output fault detected

1/0

A unit in the chain has an output fault and will turn off after the switch off delay period

Individual Unit Data - Flags

Short Name

Data Format

Description

Actuator detected

1/0

Not applicable

Wrong actuator detected/Button
armed

1/0

E-stop button is in the run state

Sensor not paired

1/0

Not applicable

Output 1

1/0

Output 1 is on

Output 2

1/0

Output 2 is on

Marginal range/Button armed

1/0

E-stop button is in the run state

Input 1

1/0

ISD device input 1 is on

Input 2

1/0

ISD device input 2 is on

Local reset expected

1/0

An ISD device with the latch feature requires a reset

Operating voltage warning

1/0

Voltage to the ISD device is at the limit of specifications

ISD data error

1/0

ISD error bit, corrupted data was received from the SI-RF ISD chain of switches.

Safety input fault

1/0

The system detected a fault on a safety input of an ISD device, power cycle required

Output error

1/0

ISD Device detects an output short to voltage or ground. This starts the "switch-off timer"
counter.

Operating voltage error

1/0

Voltage to the ISD Device is above (over 30 V DC) or below (less than 19.2 V DC) limit of range.

Power cycle required

1/0

ISD Device detects a fault, a power cycled required.

Individual Unit Data - Configuration

Short Name

Data Format

Description

Local reset unit

1/0

The ISD Device includes the latch feature

High coding level

1/0

Not applicable

Cascadable

1/0

The ISD Device includes the cascade feature Note: This will always be true for Emergency Stop
models with ISD.

Fault tolerant outputs

1/0

Indicates that the ISD Device includes the fault tolerant output feature where output faults cause a
20 minute off delay/fault delay. Note: This will always be true for Emergency Stop models with
ISD.

 

 

SSA-EB1PLx-0Dx Series Lighted Emergency Stop Button with ISD

 

www.bannerengineering.com - Tel: + 1 888 373 6767

19

Содержание SSA-EB1PL 0D Series

Страница 1: ...SSA EB1PLx 0Dx Series Lighted Emergency Stop Button with ISD Instruction Manual Original Instructions 215157 Rev A 3 August 2020 Banner Engineering Corp All rights reserved 215157...

Страница 2: ...Using the Quick Disconnect QD 8 2 5 Checkout 10 2 6 Resetting the Inputs 10 2 7 In Series Diagnostic ISD Information 11 2 8 Installing the Silicone Cover 11 3 Specifications 12 3 1 Dimensions 12 4 Ac...

Страница 3: ...SSA EB1PLXR 0DECQ8 None SSA EB1PLGR 0DECQ8 Green SSA EB1PLYR 0DECQ8R Yes Yellow SSA EB1PLXR 0DECQ8R None SSA EB1PLGR 0DECQ8R Green SSA EB1PLYR 0DED1Q8 Flush No Yellow SSA EB1PLXR 0DED1Q8 None SSA EB1P...

Страница 4: ...more devices to the same safety module controller in series Connecting devices in parallel defeats the switch contact monitoring ability of the module and creates an unsafe condition that could resul...

Страница 5: ...s The device is intended for indoor use only and must not be affected by environmental conditions Install the device so that operation is not impeded but protected against inadvertent operation for ex...

Страница 6: ...master stop control element it switches such that a failure causes a loss of the safety stop command or the failure allows the safety function to be suspended overridden or defeated Connect both OSSD...

Страница 7: ...ro The SSA EB1PLx 0Dx Series Lighted Emergency Stop Button with ISD can be connected in series or individually to a compatible Banner XS26 2 or SC10 2ro Safety Controller See the XS26 2 SC10 Safety Co...

Страница 8: ...Connect the female 4 pin M12 Euro style cable to the male 4 pin M12 Euro style of the series connection t adapter SI RFA TS 2 If a manual reset model emergency stop device is used connect the female 8...

Страница 9: ...ay be needed refer to Figure 11 on p 10 For using ISD information to monitor the individual device voltages see In Series Diagnostic ISD Information on p 11 There are two options to connect an additio...

Страница 10: ...e contamination Replace the switch and or appropriate components when any parts or assemblies are damaged broken deformed or badly worn or if the electrical mechanical specifications for the environme...

Страница 11: ...ce information to be loaded into the machine control system To interpret this information Banner diagnostic modules are available including the SI RF DM1 Diagnostic Module and the SC10 2roe Safety Con...

Страница 12: ...of following ISD devices Housing Button Flush mount models Polycarbonate Polyamide 10 or M5 M5 hardware included Max tightening torque 0 56 N m 5 in lbf Housing Button 30 mm models Polycarbonate Poly...

Страница 13: ...wn silicone cover SSA EB1P ECWC DTM1 102 1 4 02 109 5 4 31 65 2 56 65 2 56 33 1 30 14 7 0 58 80 3 3 16 80 8 3 18 4X 5 5 0 22 10 2 0 40 Figure 14 Flush mount models SSA EB1PLx 0Dx Series Lighted Emerge...

Страница 14: ...lack 5 Gray MQDC1 506 2 m 6 5 ft MQDC1 515 5 m 16 4 ft MQDC1 530 9 m 29 5 ft MQDC1 506RA 2 m 6 5 ft Right Angle 32 Typ 1 26 30 Typ 1 18 14 5 0 57 M12 x 1 MQDC1 515RA 5 m 16 4 ft MQDC1 530RA 9 m 29 5 f...

Страница 15: ...ft MQDEC 420RS 6 10 m 20 ft MQDEC 430RS 9 14 m 30 2 ft MQDEC 450RS 15 2 m 49 9 ft 8 Pin Threaded M12 Euro Style Cordsets Double Ended Model 8 pin 8 pin 4 Length Style Dimensions Pinout DEE2R 81D 0 3 m...

Страница 16: ...SI RFA DM1 SI RF Diagnostic Module with 8 digital outputs and 1 diagnostic circuit Interfaces IO Link USB 2 0 SSA EB1P ECWC FDA grade silicone cover 4 4 Safety Controllers Safety Controllers provide a...

Страница 17: ...r external device monitoring is required in the application See datasheet p n 141249 for more information Model Description UM FA 9A 3 normally open N O redundant output 6 amp contacts UM FA 11A 2 nor...

Страница 18: ...l X Double flash red OFF Faults that do not immediately compromise the safe operation of the emergency stop device for example safety output to external potential crosswire short safety output result...

Страница 19: ...Input 2 1 0 ISD device input 2 is on Local reset expected 1 0 An ISD device with the latch feature requires a reset Operating voltage warning 1 0 Voltage to the ISD device is at the limit of specific...

Страница 20: ...the Banner product THIS LIMITED WARRANTY IS EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES WHETHER EXPRESS OR IMPLIED INCLUDING WITHOUT LIMITATION ANY WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PART...

Отзывы: