LTF Time Of Flight Laser Distance Sensor Instruction Manual
34
•
•
Timer
The Timer option sets the delays and timers. On/Off Delays and On/Off One-Shot timers can be programmed between 1 to
9999 ms (a value of 0 disables the delay/timer). The following figure defines how the delays/timers affect the output behavior.
Navigate:
MENU
›
D_OUT
›
Timer
Remote Input
: not available
Default
: 0 ms for all timers
Delays/Timers
Output
OFF Delay
ON Delay
Time
OFF 1-Shot
ON 1-Shot
ON
OFF
D
D
D
D
D
D
D
D
(D = 1 - 9999 ms)
Some combinations of delays/timers are not allowed. The programming menu automatically disables invalid combinations of delays/timers. The following ta-
ble shows the allowable combinations of delays/timers.
Off Delay
Off One-Shot Timer
On Delay
On One-Shot Timer
Off Delay
(OffDly)
OK
OK
OK
N/A
Off One-Shot Timer
(Off1Sho)
OK
OK
N/A
N/A
On Delay
(OnDly)
OK
N/A
OK
OK
On One-Shot Timer
(On1Sho)
N/A
N/A
OK
OK
Polarity
The Polarity option sets the discrete output polarity to either PNP (current sourcing) or NPN (current sinking). The physical
wiring of the sensor and the sensor polarity setting must match.
Navigate
:
MENU
›
D_OUT
›
Polarity
Remote Input
: Not available
Default
: PNP
Input Menu (INPUT)
Use this menu to view or change the:
Multi-function input type
Active state of the remote input