Banner ES-GA-5A Скачать руководство пользователя страница 8

E-Stop Safety Module 

– Models ES-GA-5A and ES-HA-5A

Connection of Reset Switch

The Reset Circuit switch can be any mechanical switch such as a normally open
momentary switch, or a two-position key switch. The Reset switch must be capable of
reliably switching 12 to 18V dc at 40 to 100 milliamps. As shown in Figure 2, the Reset
switch connects between terminals S33 and S34 of the Safety Module. In addition,
connect a jumper wire between terminals S32 and S33.

The Reset switch must be located outside of – and not be accessible from – the
area of dangerous motion, and must be positioned so that any area of dangerous
motion may be observed by the switch operator during the Reset procedure.

Automatic Reset Mode

Model ES-..A-5A may be used also with automatic reset. This requires a jumper
between S32-S33 and S32-S35. The E-Stop Safety Module will reset (and the outputs
energize) as soon as the E-stop switch returns to its closed-contact position.  

The automatic reset mode is useful for some automated processes. 

However, if

automatic reset is used, it is necessary to provide an alternate means of preventing
resumption of hazardous machine motion, until an alternate reset procedure is
performed.

The alternate procedure must include a Reset switch, located outside the

area of dangerous motion, which is positioned so that any area of dangerous motion
may be observed by the switch operator during the reset procedure.

NOTE:

The minimum amount of time required for the ES-..A-5A Module to be in a

STOP or OFF condition is 500 ms. This “recovery time” (OFF-state) is required for the
internal circuitry of the Safety Module to normalize, allowing a reliable reset to occur. A
lockout will occur if the Module is cycled too quickly. To clear the lockout, the Module
must be re-cycled, meeting the minimum OFF time requirement.

Auxiliary Monitor Contact/Solid-State Monitor Outputs Connection

The action of the auxiliary monitor contact, K3, inversely “follows” the action of the
output relays, K1 and K2 when power is applied to the E-stop safety module. The
contact of K3 is open when the output contacts of K1 and K2 are closed, and vice
versa. The K3 auxiliary monitor contact is a light-duty contact to be used only for
control functions that are NOT safety-related. A typical use is to communicate the
status of the safety module output to a programmable logic controller (PLC). The
switching capacity of the K3 auxiliary monitor contact is 125V ac or V dc maximum at
500 mA maximum (resistive load). Connection to the auxiliary monitor contact is made
at terminals 51 and 52 (see Figure 2).

There are two solid-state monitor outputs, each capable of switching up to 20
milliamps at 24V dc. One output at terminal Y32 follows the action of the output
circuits (K1 and K2); the other output at terminal Y35 opens (low signal) when there is
an internal power supply fault. See Figure 2 for hookup information.

WARNING . . . 

Multiple E-Stop Switches

•  Whenever two or more E-stop switches

are connected to the same E-Stop Safety
Module, the contacts of both switches
must be connected together in series.
This series combination is then wired to
the respective Safety Module input.

Never connect the contacts of multiple
E-stop switches in parallel to the
E-Stop Safety Module inputs; this
defeats the switch contact monitoring
ability of the Safety Module, and
creates an unsafe condition which
could result in serious injury or death. 

•  

Also, when two or more E-stop
switches are used, each switch must
be individually actuated (engaged),
then re-armed and the E-stop Safety
Module reset

(if using manual reset

mode).  This allows the monitoring
circuits to check each switch and its
wiring to detect faults. 

Failure to test

each switch individually in this manner
could result in undetected faults and
create an unsafe condition which could
result in serious injury or death.

!

WARNING . . .

Reset

Routine Required

ANSI B11 and NFPA 79
standards require that a reset

routine be performed after returning the 
E-stop switch to its closed-contact
position (when arming the E-stop switch).
When automatic reset is used, an alternate
means must be established to require a
reset routine, after the E-stop switch is
armed. 

Allowing the machine to restart

as soon as the E-stop switch is armed
creates an unsafe condition which could
result in serious injury or death.

!

Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: [email protected]

Содержание ES-GA-5A

Страница 1: ... injury or death Monitors one dual channel normally closed emergency stop switch circuit for a contact failure or wiring fault Input monitoring circuit uses a diverse redundant design Four output switching channels for connection to control reliable power interrupt circuits Auto reset or monitored manual reset Auxiliary non safety outputs for status monitoring by process controller one electromech...

Страница 2: ...le in any particular application are satisfied Extreme care is urged that all legal requirements have been met and that all installation and maintenance instructions contained in this manual are followed U S Standards Applicable to Use of Emergency Stop Safety Modules ANSI B11 Standards for Machine Tools Safety Requirements for the Construction Care and Use Available from Safety Director AMT The A...

Страница 3: ...omes an input to the E Stop Safety Module The Safety Module monitors the condition of both contacts of the E stop switch Use of a 1 channel E stop switch provides no input redundancy and no ability for the Safety Module to monitor for input short circuits One channel E stop switches used with this Safety Module are generally suitable only for Safety Category 2 applications per EN 954 see page 6 NF...

Страница 4: ... are closed when the switch is in the armed position Once activated the E stop switch must open its contacts and be returned to the closed contact position only by a deliberate action such as twisting pulling or unlocking The switch should be a positive opening type as described by IEC947 5 1 A mechanical force applied to such a button or switch is transmitted directly to the contacts forcing them...

Страница 5: ...d then both be closed to reset the output contacts If not the unit will go into a lockout condition that results in the outputs opening and requiring a reset after the fault has been corrected Mechanical Installation The E Stop Safety Module must be installed inside an enclosure It is not designed for exposed wiring It is the user s responsibility to house the Safety Module in an enclosure with NE...

Страница 6: ... and 2 Channel E Stop Applications WARNING If arc suppressors are used they MUST be installed as shown across the actuator coil of the Master Stop Control Elements MSC1 to MSC4 NEVER install suppressors directly across the output contacts of the E Stop Safety Module It is possible for suppressors to fail as a short circuit If installed directly across the output contacts of the Safety Module a sho...

Страница 7: ...ither master stop control element fails in the shorted condition the associated monitor contact will remain open Therefore it will not be possible to reset the E Stop Safety Module If no MSC monitor contacts are monitored a jumper must be installed between terminals S31 and S32 see Figure 2 It is the responsibility of the user to ensure that any single failure will not result in a hazardous condit...

Страница 8: ...K1 and K2 are closed and vice versa The K3 auxiliary monitor contact is a light duty contact to be used only for control functions that are NOT safety related A typical use is to communicate the status of the safety module output to a programmable logic controller PLC The switching capacity of the K3 auxiliary monitor contact is 125V ac or V dc maximum at 500 mA maximum resistive load Connection t...

Страница 9: ...pply power to the Machine Control Elements and perform the Periodic Checkout Procedure NOTE If more than one E stop switch is series connected to one E Stop Safety Module the above checkout procedure must be run individually for EACH switch Periodic Checkout Procedure The functioning of the E stop system must be verified on a regular periodic basis to ensure proper operation see also the machine m...

Страница 10: ...internal power supply is ok Output circuits require application of 24V dc 15 at terminal Y31 dc common at Y30 Maximum switching current 20 mA at 24V dc Both outputs are protected against short circuits Output Response Time 2 Channel applications 30 milliseconds maximum 1 Channel applications 70 milliseconds maximum Status Indicators 3 green LED indicators Power ON K1 energized K2 energized 1 red L...

Страница 11: ... safety function can not be guaranteed Repairs NOTE Do not attempt any repairs to the ES A 5A Emergency Stop Safety Module It contains no field replaceable components Return the Safety Module to the factory for warranty repair or replacement If it ever becomes necessary to return an E Stop Safety Module to the factory please do the following 1 Contact the Banner Factory Application Engineering Gro...

Страница 12: ...connector and wire termination is properly seated Ensure both input channels are open a minimum of 0 5 seconds Power LED ON Fault LED OFF Ch 1 LED ON Ch 2 LED OFF S11 S12 closed S21 S22 open Check wiring Check switch Ensure connector and wire termination is properly seated Ensure both input channels are open a minimum of 0 5 seconds Power LED OFF Fault LED ON Ch 1 LED OFF Ch 2 LED OFF Constant sho...

Отзывы: