8.1.3 Industrial Ethernet Reading Phase Acquisition Control
To acquire individual images using an Industrial Protocol Input Bit, use the following instructions:
1. Go to Reading Phase > Phase Mode > Acquisition Trigger and select Trigger Type as External.
The External Trigger Source list displays.
2. Select an Industrial Protocol Input Bit.
In this example, select Bit 6.
Because the selected bit polarity is set to Leading, the ABR will take an image each time the input bit goes high.
Industrial Ethernet Bits
Figure 74. Industrial Ethernet Strings and Bits
8.1.4 Industrial Ethernet Digital Output Control
The Industrial Ethernet host controller can also drive the ABR reader’s physical discrete outputs by assigning individual
communication bits to the Digital Output Activation and Deactivation parameters. These bits are received by the ABR as
Input Bits.
1. Go to Output Setup > Output.
2. Under Activation, select an input bit, leaving the polarity setting as Leading.
In this example, select Input Bit 0.
ABR 7000 Series Barcode Reader
www.bannerengineering.com - Tel: + 1 888 373 6767
61