X20(c)SA4430
Data sheet V1.141 X20(c)SA4430 Translation of the original documentation
1
X20(c)SA4430
Information:
B&R makes every effort to keep data sheets as current as possible. From a safety point of view, how-
ever, the current version of the data sheet must always be used.
The certified, currently valid data sheet can be downloaded from the B&R website
Organization of notices
Safety notices
Contain
only
information that warns of dangerous functions or situations.
Signal word
Description
Danger!
Failure to observe these safety guidelines and notices will result in death, severe injury or substantial damage to property.
Warning!
Failure to observe these safety guidelines and notices can result in death, severe injury or substantial damage to property.
Caution!
Failure to observe these safety guidelines and notices can result in minor injury or damage to property.
Notice!
Failure to observe these safety guidelines and notices can result in damage to property.
Table 1: Organization of safety notices
General notices
Contain
useful
information for users and instructions for avoiding malfunctions.
Signal word
Description
Information:
Useful information, application tips and instructions for avoiding malfunctions.
Table 2: Organization of general notices
1 General information
The modules are equipped with 2 safe analog input pairs for current measurement. Each input pair has its own
sensor power supply. The channels with their respective sensor supplies are galvanically isolated from each other.
It is possible to acquire current signals in the range of 0.5 to 25 mA.
The safe analog input modules are suitable for safely acquiring current signals for safety-related applications up
to PL e or SIL 3.
These modules are designed for X20 16-pin terminal blocks.
•
2 safe analog input pairs for current measurement 0.5 to 25 mA
•
24-bit digital converter resolution
•
Channels individually galvanically isolated
•
Sensor power supplies galvanically isolated
•
Input filter configurable