![B&R X20SA4430 Скачать руководство пользователя страница 23](http://html2.mh-extra.com/html/bandr/x20sa4430/x20sa4430_manual_4786905023.webp)
X20(c)SA4430
Data sheet V1.141 X20(c)SA4430 Translation of the original documentation
23
Danger!
With "Disable_Shunttest = Yes-ATTENTION", the module has reduced error detection capabilities and
no longer meets the requirements of Cat. 4 per EN ISO 13849-1:2015.
As a result, the module meets the requirements up to max. Cat. 3 per EN ISO 13849-1:2015.