Technical data
28
Panel PC 2100 user's manual V1.17
AP1000 panels with clamping blocks - Installation diagrams
Z
Y
X
Figure 7: Panel PC 2100 with AP1000 panels with clamping blocks (example figure) - Installation diagram
All dimensions are specified in mm.
The cutout tolerances are +0 mm / -0.5 mm.
Display type
Model number
X
Y
Z min. Z max. Number of clamping blocks
10.4" single-touch with keys
5AP1181.1043-000
303
341
2
10
10
10.4" single-touch with keys
5AP1182.1043-000
403
271
2
10
8
12.1" single-touch
5AP1120.1214-000
342
267
2
10
8
15.0" single-touch
5AP1120.1505-000
415
313
2
10
8
15.0" single-touch with keys
5AP1180.1505-000
415
313
2
10
8
15.0" single-touch with keys
5AP1181.1505-000
415
413
2
10
10
19.0" single-touch
5AP1120.1906-000
510
404
2
10
12
Table 14: AP1000 panels with clamping blocks - Installation diagrams
Dimension "Z" describes the thickness of the wall or control cabinet panel.
A 3 mm hex screwdriver is needed to tighten and remove the screw on the clamping blocks. The maximum tight-
ening torque of the clamping blocks is 0.5 Nm.