Installation and Operations Manual
— VP Gate Operator
15
B&B ARMR
A Division of B&B Roadway and Security Solutions VP Revision B1
6.2 Final Adjustments
With the gate opening and closing properly and the installed safety devices have been tested, you
can make adjustment to the operation of the system.
1.
Adjusting MaxRun Time. Max run time is the time from which the operator has been given
a command to open or close and when the appropriate limit switch is made or a safety is
encountered.
1.
Open or Close the gate and time how long it takes to perform the successful operation.
2.
Adjust the MaxRun Time in the Set Parm (section 5). It is recommended that round up in
increments of 5 seconds to the next time. Ie. Measured time is 16 seconds, set max run
to 20 seconds.
2.
Adjust AutoClose time. If you are utilizing adjust the autoclose time to the desired time
(section 5)
3.
Adjust the Inherent Pressure (section 5)
4.
Verify a positive gate stop (the yoke) is installed. It should be located 1 to 2 inches from the
end of the gate panel
5.
Warning signs should be mounted in a visible location per applicable safety codes
instructing personnel and traffic to maintain a safe distance clear of gate path
6.
Record the names and phone numbers of the dealer, installer and other important contact is
the manual for future reference.
7.
Leave the manual along with all supplements with the owner. Have them keep them in a
place that is readily available if needed.