DP0003c

CONTROLS: ROTARY/PUSHBUTTON SELECTOR

Turn

In menu level 0 the selected limit value is displayed and can be changed.
In menu level 1 reset hysteresis (HY), delay time (TD) or temperature monitoring (TP) can be selected.
In menu level 2 desired values for reset hysteresis and delay time (0.1 to 9.9 seconds) can be selected.

Anticlockwise rotation: -
Clockwise rotation: +

Press

Press to select submenus.

Pressing the button in submenu 2 returns the display to menu 1.

Note:

Changed settings are saved immediately!
If the rotary/pushbutton selector is not operated for more than 7 seconds, the display returns automatically to menu level 0.

Menu structure

Turn switch

Press switch

LED Off

LED On

Threshold value display low

Threshold value display med

Threshold value display high

0-100

0-100

Hysteresis selection

Time delay selection

Temperature monitoring

Hysteresis 1...25%

Time 0.1...9.9s

on / off

back to
level 1

back to
level 1

back to
level 1

1

2

SETTING THE THRESHOLD, LIMIT VALUE AND COMMISSIONING

Adjustment takes place after installation and electrical connection.
If problems arise, see “Troubleshooting”.

All steps must be carried out in chronological order!

Detecting the transition from the clear phase to sludge:

1. Turn the rotary/pushbutton selector on the evaluation unit clockwise as far as it will go until the display indicates 100% in the HIGH range.

3 LEDs light up yellow.

2. Fill the measuring cell with the clear phase or immerse the probe into the clear phase (blue LED is off).
3. Turn the rotary switch anticlockwise (-) until the blue LED lights up.
4. Slowly turn clockwise (+) until the blue LED goes out.

The device now reacts as soon as the medium becomes slightly more turbid.

5. To prevent the TURBISWITCH GS5 from reacting to extremely slight deviations, adjust the switching point a bit further in the clockwise

direction (+) (approx. 5 to 20 %).

TUR

19-08-2021

M-410.03-EN-AA

410-03

/7

Turbidity Limit Value

Evaluation Unit

TURBISWITCH GS5

22, Rue de la Voie des Bans · Z.I. de la gare · 95100 ARGENTEUIL

Tel

Fax

+33 (0)1 30 25 83 20

+33 (0)1 34 10 16 05

Web

E-mail

www.bamo.eu

[email protected]

INTERNATIONAL

Содержание TURBISWITCH GS5

Страница 1: ...OMAT series TT GS TR GS and CP1 at the evaluation unit TURBISWITCH GS5 is not possible TECHNICAL DATA Supply power 100 240V AC 50 60Hz TURBISWITCH GS5 G or 10 30V DC and 12 24V AC TURBISWITCH GS5 D Po...

Страница 2: ...shed by simply turning the rotary pushbutton selector The selected hysteresis value is automatically skipped in this case 100 in the LOW range is followed by 0 in the MEDIUM range 100 in the MEDIUM ra...

Страница 3: ...iefly displayed The display is then limit value display INSTALLING A MEASURING CELL IN A PIPING SYSTEM IN LINE Installation of in line measuring cell The Measuring cells TURBISWITCH GA1 GA5 GA11 can b...

Страница 4: ...TURBISWITCH CP2 and CP5 transducers are designed as hanging probes or for use with an extension tube It can be installed in slurry tanks basins or open wells The probe should be installed so that it c...

Страница 5: ...eiver TT HDR and TR HDR or TT HDR5 and TR HDR5 Emitter Receiver IR Light TT HDR Emitter TURBISWITCH GS5 TR HDR Receiver 10 to 30 V DC 100 to 240 V AC L N Fuse 16 14 8 2 6 1 3 4 OC V RX V Limit value L...

Страница 6: ...13 15 Switching logic with increased reliability The contacts open when one of the following events occur Contact 9 11 opens when the limit value is exceeded Contact 9 12 opens when measurements are b...

Страница 7: ...NG THE THRESHOLD LIMIT VALUE AND COMMISSIONING Adjustment takes place after installation and electrical connection If problems arise see Troubleshooting All steps must be carried out in chronological...

Страница 8: ...is so high that no light is reaching the receiver HDR5 emitter blinks red Defective emitter Replace the emitter TR appears on the display The receiver has malfunctioned or it is not connected Check t...

Страница 9: ...mescale remover The side of the glass disc marked with a dot must be installed that it faces the medium Check the seals O rings for damage and replace them if necessary before start up The frequency o...

Отзывы: