IGNITION AND ADJUSTMENT WITH LIQUID
FUEL
CAUTION / WARNING
To obtain a proper ignition and combustion using the first flame
alone, the fuel supply should not be considerably lower than
the minimum capacity indicated on the identification plate of
the burner.
Before starting up, make sure that:
•
The correct type of fuel has been selected.
•
Check that thee voltage on the mains meets the manufacturer
requirements and that all electrical connections made at the
installation site are performed properly as illustrated in our wiring
diagram.
•
Check that the discharge of combustion products through the boiler
gate and flue gate take places freely.
•
Check that there is water in the boiler and that the gate valves of
the system are open.
Check that all the gate valves fitted on the fuel suction and return
pipes are open; the same applies to any other fuel shut-off devices.
•
Check if there is fuel in the tank and water in the boiler.
•
Check that combustion head penetrates the combustion chamber
by the measure requested by the manufacturer of the boiler.
Check that the air closure device on the combustion head is in the
right position to guarantee a correct combustion, the air passage
between disk and head must be slightly reduced if a relatively small
amount of fuel is supplied. When the fuel supply is abundant the air
passage must be increased, see chapter "COMBUSTION HEAD
ADJUSTMENT”.
•
Check that the nozzles fitted on the burner are suitable for the
boiler capacity. If necessary, replace them with suitable ones. In
no case should the quantity of fuel delivered exceed the maximum
amount required by the boiler and the maximum amount allowed
for the burner.
CAUTION / WARNING
For burner adjustment see the quick guide supplied.
• Turn on the main switch and the one on the control panel.
•
The programmer is activated and it starts carrying out the
predefined program activating the burner devices.The equipment
will start operation as described in the Chapter “DESCRIPTION
OF OPERATION”.
DANGER / CAUTION
The burner must not operate below the specified minimum flow
rate to prevent damage to the components of the combustion
head.
THERMAL RELAY CALIBRATION
The thermal relay prevents the motor from being damaged due to a
sudden increase in power consumption, or in the event that a phase
is missing.
To calibrate it, refer to the value of the nominal current of the motor.
To reset the burner if the thermal relay has been triggered, press the
(RESET) button.
DANGER / CAUTION
If present, the automatic reset can be dangerous, so do not set
this function on the thermal relay.
Содержание TBML 120 ME
Страница 2: ......
Страница 4: ...ITALIANO 2 60 0006160032_201711 ITALIANO Schemi elettrici 48 ...
Страница 50: ...ITALIANO 48 60 0006160032_201711 SCHEMI ELETTRICI ...
Страница 51: ...ITALIANO 49 60 0006160032_201711 ...
Страница 52: ...ITALIANO 50 60 0006160032_201711 ...
Страница 53: ...ITALIANO 51 60 0006160032_201711 ...
Страница 54: ...ITALIANO 52 60 0006160032_201711 BT1 BA BP I1 I2 I3 I4 ...
Страница 56: ...ITALIANO 54 60 0006160032_201711 ...
Страница 57: ...ITALIANO 55 60 0006160032_201711 ...
Страница 58: ...ITALIANO 56 60 0006160032_201711 ...
Страница 59: ...ITALIANO 57 60 0006160032_201711 ...
Страница 60: ...ITALIANO 58 60 0006160032_201711 BT1 BA BP I1 I2 I3 I4 ...
Страница 62: ......
Страница 64: ...ENGLISH 2 60 0006160032_201711 ENGLISH Wiring diagrams 48 ...
Страница 110: ...ENGLISH 48 60 0006160032_201711 WIRING DIAGRAMS ...
Страница 111: ...ENGLISH 49 60 0006160032_201711 ...
Страница 112: ...ENGLISH 50 60 0006160032_201711 ...
Страница 113: ...ENGLISH 51 60 0006160032_201711 ...
Страница 114: ...ENGLISH 52 60 0006160032_201711 BT1 BA BP I1 I2 I3 I4 ...
Страница 116: ...ENGLISH 54 60 0006160032_201711 ...
Страница 117: ...ENGLISH 55 60 0006160032_201711 ...
Страница 118: ...ENGLISH 56 60 0006160032_201711 ...
Страница 119: ...ENGLISH 57 60 0006160032_201711 ...
Страница 120: ...ENGLISH 58 60 0006160032_201711 BT1 BA BP I1 I2 I3 I4 ...
Страница 122: ......
Страница 123: ......