DESCRIPTION OF OPERATION WITH LIQUID
FUEL
FURTHER INSTRUCTIONS TO START A MIXED BURNER
It is not advisable to have too large a burner for the boiler for heating
and for hot water as the burner may work for long periods with a
single flame, making the boiler work at lower than required output; as
a result of this the combustion products (fumes) emerge at too low a
temperature (at about 180°C in the case of heavy oil and 130°C with
diesel fuel), causing soot to build up at the chimney outlet.
IMPORTANT
When the boiler is working at a lower output than that indicated
by the technicians, it is likely that acidic condensate and soot
will form in the boiler with the result that it will quickly corrode
and get clogged up.
When the two-flame burner is installed on a water boiler for heating
use, it must be connected so that it works normally with both flames,
completely stopping without passing to the first flame when the preset
temperature is reached.
To obtain this operating condition, do not install the second flame
thermostat and make a direct connection (bridge) between the
respective four pole plug terminals.
In this way only the burner’s capacity to switch on at low rate is used
for a gentle ignition, which is essential for boilers with a pressurised
combustion chamber and also very useful for normal boilers with
depression combustion chamber. The burner (start/stop) command is
subject to the usual operating or safety thermostats.
With main switch -1 in the "on" position, close the switch -2 if the
thermostats are closed, the command and control equipment starts
its operation.
The motor turns the fan that carries out an air wash of the combustion
chamber and, at the same time, the fuel pump that causes circulation
in the ducts, expelling any gas bubbles through the return valve. This
pre-washing phase ends with the opening of the operating solenoid
valves that makes it possible for the fuel to reach the nozzle and enter
the combustion chamber finely atomised.
As soon as the atomized fuel exits the nozzle, it is set on fire by the
spark present between the electrodes since the start of the motor.
During first stage ignition, the air gate is held in the adjusted position
on the special air adjustment servomotor cam.
If the flame appears regularly, after the safety time foreseen by the
device, it starts the air regulation servomotor that moves to the second
stage position. During the transition from the first to the second stage,
the equipment activates the solenoid valve (normally closed) of the
second stage.
If the flame appears regularly, after the safety time foreseen by the
device, it starts the air regulation servomotor that moves to the second
stage position. During the transition from the first to the second stage,
the equipment activates the solenoid valve (normally closed) of the
second stage.
The opening of the second stage valve allows the diesel to reach the
second nozzle and the burner to operate at full capacity.
Once the flame appears in the combustion chamber, the burner is
controlled and commanded by the flame control equipment and by
the thermostats.
The control equipment follows the program and switches the ignition
transformer off. When the temperature or the pressure in the boiler
reaches that set by the thermostat or pressure switch, the latter stops
the burner.
Subsequently, if the temperature of pressure decreases below the
lower thermostat or pressure switch threshold value, the burner will
switch on again.
If, for any reason, the flame fails during operation, after just one
second the flame control device cuts off the power supply to the relay,
causing the deactivation of the solenoid valves which intercept the
fuel flow to the nozzles.
The equipment will shut-down automatically.
Содержание TBML 120 ME
Страница 2: ......
Страница 4: ...ITALIANO 2 60 0006160032_201711 ITALIANO Schemi elettrici 48 ...
Страница 50: ...ITALIANO 48 60 0006160032_201711 SCHEMI ELETTRICI ...
Страница 51: ...ITALIANO 49 60 0006160032_201711 ...
Страница 52: ...ITALIANO 50 60 0006160032_201711 ...
Страница 53: ...ITALIANO 51 60 0006160032_201711 ...
Страница 54: ...ITALIANO 52 60 0006160032_201711 BT1 BA BP I1 I2 I3 I4 ...
Страница 56: ...ITALIANO 54 60 0006160032_201711 ...
Страница 57: ...ITALIANO 55 60 0006160032_201711 ...
Страница 58: ...ITALIANO 56 60 0006160032_201711 ...
Страница 59: ...ITALIANO 57 60 0006160032_201711 ...
Страница 60: ...ITALIANO 58 60 0006160032_201711 BT1 BA BP I1 I2 I3 I4 ...
Страница 62: ......
Страница 64: ...ENGLISH 2 60 0006160032_201711 ENGLISH Wiring diagrams 48 ...
Страница 110: ...ENGLISH 48 60 0006160032_201711 WIRING DIAGRAMS ...
Страница 111: ...ENGLISH 49 60 0006160032_201711 ...
Страница 112: ...ENGLISH 50 60 0006160032_201711 ...
Страница 113: ...ENGLISH 51 60 0006160032_201711 ...
Страница 114: ...ENGLISH 52 60 0006160032_201711 BT1 BA BP I1 I2 I3 I4 ...
Страница 116: ...ENGLISH 54 60 0006160032_201711 ...
Страница 117: ...ENGLISH 55 60 0006160032_201711 ...
Страница 118: ...ENGLISH 56 60 0006160032_201711 ...
Страница 119: ...ENGLISH 57 60 0006160032_201711 ...
Страница 120: ...ENGLISH 58 60 0006160032_201711 BT1 BA BP I1 I2 I3 I4 ...
Страница 122: ......
Страница 123: ......