AIR REGULATION ON THE COMBUSTION HEAD
The combustion head is equipped with a regulation device that makes
it possible to open or close the air passage between the disk and the
head.
It may be necessary to have high air pressure upstream of the disc,
so as to prevent flame pulses. This condition is indispensable when
the burner operates on pressurised combustion chamber and/or with
high heating load.
When the
maximum required supply
is reached, correct
the position of the device closing the air on the combustion head
by moving it forwards or backwards so as to have a suitable air
flow for the supply,
with suction air adjustment damper
considerably open.
0002936150
16
11
10
15
X
X = Head-disk distance; adjust distance X following the instructions:
•
loosen the screws (10),
•
turn screw (11) to position the combustion head (16) referring to
index (15).
•
adjust the distance X between the minimum and maximum value,
according to what is indicated in the table.
Model
X
Index value (15)
TBG 35 / 35P
3 ÷ 31
0 ÷ 6
CAUTION / WARNINGS
The above adjustments are only indicative; position the
combustion head according to the characteristics of the
furnace.
11
0002932162_02
MANUAL AIR REGULATION ON THE COMBUSTION HEAD
To adjust the opening angle of the air damper, loosen the screw (8)
and turn the hand wheel (1) to bring the index to the desired position.
Subsequently tighten the screw to lock the damper.
Position 0: damper completely closed
Position 9: damper completely open
1
8
0002932162_01
18 / 30
0006081424_202211
ENGLISH
Содержание TBG 35
Страница 2: ......
Страница 32: ...SCHEMI ELETTRICI 30 30 0006081424_202211 ITALIANO...
Страница 62: ...WIRING DIAGRAMS 30 30 0006081424_202211 ENGLISH...
Страница 63: ......