40
TWO STAGE PROGRESSIVE NATURAL GAS BURNERS
OPERATING ANOMALY
DETAILS OF PROBLEM
The apparatus goes into “lock-
out” with the flame (red light
on). Fault restricted to flame
control device.
The apparatus goes into “lock-
out”, gas flows out, but there is
no flame (red light on).
Fault restricted to ignition
circuit.
The apparatus goes into “lock-
out”, gas flows out, but there is
no flame (red light on).
POSSIBLE CAUSE
1) Disturbance to ionization
current from ignition
transformer.
2) Flame sensor (ionization probe
or UV cell) inefficient.
3) Flame sensor (ionization probe
or UV cell) position incorrect.
4) Ionization probe or relative
earth cable.
5) Electrical connection cut-off by
flame sensor.
6) Inefficient draught or fumes
passage blocked.
7) Flame disk or combustion
heads dirty or worn.
8) UV cell dirty or greasy.
9) Equipment fault.
10) No ionization.
1) Fault in ignition circuit.
2) Ignition transformer cable
discharges to earth.
3) Ignition transformer cable
disconnected.
4) Ignition transformer faulty.
5) The distance between
electrode and earth is incorrect.
6) Isolator dirty, so electrode
discharges to earth.
1) air/gas ratio incorrect.
2) Gas pipe has not been properly
bled of air (in the case of first
ignition).
3) The gas pressure is insufficient
or excessive.
4) Air flow between disk and head
too narrow.
SOLUTION
1) Invert the ignition transformer
power supply (230V side) and
check using an analog micro-
ammeter.
2) Replace flame sensor.
3) Correct the position of the flame
sensor, and then check its
efficiency by inserting the analog
micro-ammeter.
4) Check visually and using the
instrument.
5) Restore the connection.
6) Ensure that the boiler fumes
passage and chimney connection
are free.
7) Visually check and replace, if
necessary.
8) Clean
carefully
.
9) Replace.
10)
If the “earth” of the apparatus
is not efficient, do not check the
ionization current. Check the
efficiency of the “earth” at the
terminal concerned of the
apparatus and at the “earth”
connection of the electric system.
1) Check the ignition transformer
power supply (230V) and high
voltage circuit (electrode to earth
or isolator broken under locking
terminal).
2) Replace.
3) Connect.
4) Replace.
5) Position at the correct distance.
6) Clean or replace isolator and
electrode.
1) Correct the air/gas ratio (there is
probably too much air or very little
gas).
2) Bleed the gas pipe again, taking
great care.
3) Check the maximum gas
pressure value
at the time of
ignition
(use a water pressure
gauge, if possible).
4) Adjust the disk/head opening.
Содержание BTG 20 LX
Страница 35: ...35 TWO STAGE PROGRESSIVE NATURAL GAS BURNERS LMG 2 CONTROL BOX SPECIFICATIONS...
Страница 36: ...36 TWO STAGE PROGRESSIVE NATURAL GAS BURNERS LMG 2 CONTROL BOX SPECIFICATIONS...
Страница 37: ...37 TWO STAGE PROGRESSIVE NATURAL GAS BURNERS LMG 2 CONTROL BOX SPECIFICATIONS...
Страница 49: ...QUEMADORES DE GAS NATURAL DE DOS ETAPAS PROGRESIVO 49...
Страница 50: ...QUEMADORES DE GAS NATURAL DE DOS ETAPAS PROGRESIVO 50...
Страница 51: ...QUEMADORES DE GAS NATURAL DE DOS ETAPAS PROGRESIVO 51...
Страница 52: ...QUEMADORES DE GAS NATURAL DE DOS ETAPAS PROGRESIVO 52...
Страница 65: ...65 BR LEUR GAZ NATUREL DEUX ALLURES PROGRESSIVES...
Страница 66: ...66 BR LEUR GAZ NATUREL DEUX ALLURES PROGRESSIVES...
Страница 67: ...67 BR LEUR GAZ NATUREL DEUX ALLURES PROGRESSIVES...
Страница 80: ...ZWEISTUFIG GLEITEND BEI ERDGAS BRENNER 80...
Страница 81: ...ZWEISTUFIG GLEITEND BEI ERDGAS BRENNER 81...
Страница 82: ...ZWEISTUFIG GLEITEND BEI ERDGAS BRENNER 82...
Страница 95: ......