Before igniting make sure that:
a) Connections with the fuel line, thermostats or pressure switches are carried out exactly as illustrated in the control

box wiring diagram.

b) There is fuel in the tank and water in the boiler.
c) That all the sluice valves on the fuel oil suction and return piping are open as is every other part through which the

fuel flows.

d) Combustion fumes discharge occurs freely (boiler flue gates and chimney open).
e) Make sure the burner head penetrates the combustion chamber in accordance with the boiler manufacturer’s

specifications.  To  ensure  this  is  so  the  burner  is  equipped  with  a  boiler  attachment  flange  which  slides  with
respect to the combustion head.

f)

The burner nozzles are compatible with boiler output; if necessary, replace them.
The  quantity  of  fuel  being  delivered  must  never  be  greater  than  the  maximum  boiler-requested  quantities  or
maximum admissible burner quantities. Bear in mind that the combustion head has been designed for use with
nozzles having a 45° spray angle.
Note: To ensure good ignition and combustion with the first stage only, fuel delivery must not be notably lower than

the minimum flow-rate for the employed burner (see identification plate).

FOR IGNITION PROCEED AS FOLLOWS:

Note: The burner is equipped with a manual switch to change from the 1st to the 2nd stage.
1) Switch on the 1st and 2nd stage switch to prevent ignition of the 2nd flame.
2) Slightly open the air gate to obtain the air-flow thought necessary for burner operation with the 1st stage by acting

on the cam which limits the servomotor stroke for the 1st stage (see BT 8653/1 or BT 8711/1). Adjust the air
adjustment device on the combustion head to an intermediate position (see, further on, “Air regulation on the
combustion head”).

3) Turn on the main switch and the ON/OFF burner switch.

This switches on all the fuel oil heating elements and simultaneously causes the yellow warning light on the burner
to come on.

4) The minimum thermostat comes on when the fuel contained in the preheater reaches  the set  temperature.

When the minimum thermostat switches off the control box (if the other boiler thermostats are off) is switched on;
the control box then switches on the devices making up the burner as per the pre-set program.
The unit ignites as illustrated in “Description of Operation”.

5) When the burner is operating with the 1st stage adjust, as described in point 2, the air quantity so that good

combustion is ensured. It is better to have a slightly poor 1st stage air-flow in order t ensure perfect ignition even
under the most demanding conditions.

6) After regulating the 1st stage air-flow stop the burner by cutting power at the main switch. Connect the terminals

of the 2nd stage thermostat terminal block together and position the1st-2nd stage switch to 2nd stage.

7) Act on the cam which limits the 2nd stage air gate servomotor stroke; adjust to the quantity thought necessary

for the fuel to be burnt (see BT 8653/1 or BT 8711/1).

8) Switch the unit back on; it will now pass automatically to the second stage according to the set program.
9) With the unit now operating with the 2nd stage, adjust (by operating on the cam described in point 7) the air-flow

to  the  quantity  needed  to  ensure  good  combustion.  Combustion  checks  should  be  carried  out  with  special
instruments. If suitable instruments are unavailable observe the colour of the flame. We recommend that  you adjust
to obtain a soft, light orange flame: avoid a red flame that gives off smoke or a white flame with  excess air.
The air regulator must be in a position which gives a percentage of carbon dioxide (CO

2

) in the fumes that varies

from a minimum of 10% to a maximum of 13% with a smoke rating that does not exceed standard limits (Bacharach
scale). We recommend that you adjust to obtain a soft, light orange flame: avoid a red flame that gives off smoke
or a white flam with excess air (see also “Air adjustment on the combustion head”.

10) Adjustment of the preheater thermostats, minimum thermostat and regulation thermostat (max) is effected by the

manufacturer and set at values which may, however, be unacceptable in certain individual cases. It is therefore
necessary, during final testing, to check that these values do not cause problems (poor combustion, smoke,
formation of gas in the preheater, etc.). Where necessary, increase or decrease the settings; bear in mind that the
regulation  thermostat  must  nevertheless  be  at  a  temperature  approximately  15°  higher  than  the  minimum
thermostat setting. The minimum thermostat must close at the minimum temperature needed to ensure that fuel
arrives at the nozzle with viscosity below 2° E. This condition is indispensable for proper atomization.
(As a rough guide see the viscosity-temperature diagram regarding the employed oil type).

IGNITION AND ADJUSTMENT

(see BT 8608/1. drawing n° 0002900445, BT 8711/1 and drawing n° 0002900564)

Содержание BT 75 DSN-4T

Страница 1: ...D BT 75 DSN 4T D BT 100 DSN 4T D BT 120 DSN 4T D BT 180 DSN 4T D BT 250 DSN 4T D BT 300 DSN 4T D BT 350 DSN 4T D it sp Prima di iniziare a usare il bruciatore leggere attentamente quanto esposto nel...

Страница 2: ...la BALTUR misma y con los accesorios de linea gas certificados CE suministrables a pedido NOTA la presente declaraci n no tiene validez respecto a la Norma CE o UNI para los quemadores de gas y para...

Страница 3: ...tion gead Adjusting distance diffuser disc and the nozzle 39 Checks Using the burner Maintenance Two stage burners description of operation 40 Irregularity cause remedy 42 Hydraulic circuit principle...

Страница 4: ...pericolose come la formazione di miscele tossiche ed esplosive Per chiarire meglio la situazione facciamo un esempio Per bruciare correttamente una quantit di combustibile corrispondente alla modesta...

Страница 5: ...l gas Far verificare da personale professionalmente qualificato a che la linea di adduzione e la rampa siano conformi alle norme e prescrizioni vigenti DPR del 12 4 96 G U n 103 del 4 5 96 b che tutte...

Страница 6: ...0mA TRANSFORMER TRANSFORMADOR TENSIONE TRIFASE 220 380V 220 380V 220 380V 220 380V 220 380V VOLTAGE THREE PHASE 50 Hz 50 Hz 50 Hz 50 Hz 50 Hz TENS ON TRIF SICA RESISTENZA PRERISCALDATORE PRE HEATER RE...

Страница 7: ...r acoplamiento el stico N 1 N 1 N 1 N 1 N 1 N 2 PRIGIONIERI STUD BOLTS Pernos sin cabeza N 4 M16 N 4 M16 N 3 M20 N 3 M20 DADI ESAGONALI HEXAGONAL NUTS Tuercas hexagonales N 8 M16 N 8 M16 N 3 M20 N 3 M...

Страница 8: ...TI 1 Fotoresistenza 2 Trasformatore d accensione 3 Testa di combustione 4 Guarnizione isolante 5 Flange attacco bruciatore 6 Vite regolazione aria alla testa di combustione 7 Elettrovalvola 2a fiamma...

Страница 9: ...9 CAMPO DI LAVORO WORKING FIELD RANGO DE TRABAJO N 0002921701 REV 05 02 2003 CAMPO DI LAVORO WORKING FIELD RANGO DE TRABAJO N 0002921710 Olio C...

Страница 10: ...locking system is highly efficient do not tighten the nuts too much During this operation tightening of the flange locking nuts keep the body of the burner lifted so that the combustion head is kept...

Страница 11: ...with welded couplings to eliminate the need for threaded joints which often bleed in air and consequently compromise performance of the pump and therefore the burner too Where detachable couplings are...

Страница 12: ...ns regarding apparatus required in the pipeline system H Total length meters meters 1 1 31 2 35 2 5 35 3 35 H Total length meters meters 1 1 31 2 35 2 5 35 3 35 Maximum intake and return pressure 1 ba...

Страница 13: ...on P 3 5 m max H Height difference between minimum fuel tank level and pump axis L Total length of pipeline including vertical lenght Subtract 0 25 mt for every elbow or gate valve N B Comply with exi...

Страница 14: ...ght difference between minimum fuel tank level and pump axis L Total length of pipeline including vertical lenght Subtract 0 25 mt for every elbow or gate valve N B Comply with existing regulations re...

Страница 15: ...max H Height difference between minimum fuel tank level and pump axis L Total length of pipeline including vertical lenght Subtract 0 25 mt for every elbow or gate valve N B Comply with existing regu...

Страница 16: ...ed when the burner stops Carry out auxiliary pump electrical connections by connecting the coil 230 V which controls the pump relay switch to the N terminals control box input terminal block and L1 te...

Страница 17: ...OT WATER TO HEAT THE OIL 15 HEAVY OIL HEATING COIL STEAM OR HOT WATER 16 HUB DIAMETER 100MM HEIGHT 300MM HEATING ELECTRICAL LEAD IF NECESSARY N B The thank for recovery of hot oil diameter 150 mm heig...

Страница 18: ...dense version burners are equipped with an auxiliary element for the pump the atomization unit and for the two solenoid valves In addition the line filter is preheated By closing the switch on the bu...

Страница 19: ...ct to a pressure of 25 bars From the moment in which the flame appears in the combustion chamber the burner is controlled by the photoresistance and the thermostats When the temperature or pressure re...

Страница 20: ...he burner is operating with the 1st stage adjust as described in point 2 the air quantity so that good combustion is ensured It is better to have a slightly poor 1st stage air flow in order t ensure p...

Страница 21: ...uldsuchasituationoccurshifttheregulatorbackalittleatatimeuntilitisinapositionthatgivesregularignition and take this as the definitive setting It should be pointed out once again that for the 1st stage...

Страница 22: ...t settings The control device trips and extinguishes the second stage fuel and air when its setting levels are reached The burner then continues to operate with the first stage only The first stage is...

Страница 23: ...t flash in these fields 2 Scale of absolute values for setting the time in side the selected field 3 Status display LED U T Electrical supply tension LED on time passed or stopped LED flashing time de...

Страница 24: ...the programmer 11 Preheater tank filter clogged 12 Broken solenoid valve 13 Atomizing group valve does not open 14 Voltage too low 1 Fuel oil in the tank too viscous 2 Pipeline diameters too small 3 A...

Страница 25: ...3 Fume temperature too low below 180 C 1 Fumes cool down too much below 180 C before reaching the stop due to an insufficiently insulated exterior chimney or to infiltration of cold air REMEDY 1 Spea...

Страница 26: ...device 4 1 st stage nozzle closing device pressure selling 16 bar 4 1 2 nd stage nozzle closing device pressure selling 16 bar 5 80 W heating element only for D version for high fuel viscosity 6 closi...

Страница 27: ...selling 16 bar 4 1 2 nd stage nozzle closing device pressure selling 16 bar 5 80 W heating element only for D version 6 closing device adjusting screw 7 1 st stage normally open valve 8 2 nd stage nor...

Страница 28: ...Fuel outlet to the atomising unit 1 Conexi n man metro Rp 1 2 2 Junta t rica OR 3 Muelle de cierre v lvula p 2 3 bares 4 Tap n purga aire 5 Filtro de red 6 Obturador v lvula antig s 7 Salida del combu...

Страница 29: ...65 POMPA BALTUR MOD BT BALTUR PUMP MOD BT BOMBA BALTUR MOD BT N 0002900580...

Страница 30: ...50 31 2 32 7 34 2 36 9 38 2 39 5 40 7 41 9 43 0 44 1 45 2 46 3 47 3 48 4 49 4 50 3 51 3 52 2 53 2 54 1 7 50 8 30 34 5 36 2 37 8 40 9 42 3 43 7 45 0 46 4 47 6 48 9 50 1 51 2 52 4 53 5 54 6 55 7 56 8 57...

Страница 31: ...SK ADJUSTMENT DIAGRAM ESQUEMA INDICATIVO DISPOSICI N BOQUILLA ELECTRODOS DISCO DEFLECTOR N 0002933870 Gruppo a 3 Ugelli 3 nozzles atomizing group Grupo a 3 boquillas Gruppo a 2 Ugelli 2 nozzles atomiz...

Страница 32: ...CORRETTA CORRECT REGULATION REGULACI N CORRECTA Ingresso aria di combustione con serranda sensibilmente aperta Combustion air inlet with air shutter sensibly open Entrada de aire de combusti n con cie...

Страница 33: ...y la rueda se desplazar respecto a la escala de referencia El ndice de la rueda roja indica el ngulo de rotaci n establecido para cada leva en la correspondiente escala de referencia 1 CAMMA inserzion...

Страница 34: ...lama Perno di esclusione accoppiamento motore ambero cammes Premendo si ottiene la disinserzione del collegamento motore albero Motor cam sheft coupling exclusion pin Push it to disconnect motor from...

Страница 35: ...FERENCE INDEX INDICE DE REFERENCIAINDICE CAMME REGOLABILI ADJUSTABLE CAMS LEVAS REGULABLES I CAMMA REGOLAZIONE ARIA 2 FIAMMA 60 III CAMMA NON UTILIZZATA II CAMMA REGOLAZIONE ARIA 1 FIAMMA 20 IV CAMMA...

Страница 36: ......

Страница 37: ......

Страница 38: ...74 SCHEMA ELETTRICO ELECTRIC DIAGRAM DIAGRAMA DE CONEXION BT 17 35 SPN BT 40 100 DSN 4T N 0002310290 n 1 di 2...

Страница 39: ...75 SCHEMA ELETTRICO ELECTRIC DIAGRAM DIAGRAMA DE CONEXION BT 17 35 SPN BT 40 100 DSN 4T N 0002310290 n 2 di 2...

Страница 40: ......

Страница 41: ......

Страница 42: ......

Страница 43: ......

Страница 44: ......

Страница 45: ......

Страница 46: ...ltur it Il presente catalogo riveste carattere puramente indicativo La casa pertanto si riserva ogni possibilit di modifica dei dati tecnici e quant altro in esso riportato Technical data in this broc...

Отзывы: