IGNITION AND ADJUSTMENT WITH LIQUID
FUEL
CAUTION / WARNINGS
To obtain a proper ignition and combustion using the first flame
alone, fuel supply should not be lower than the minimum capaci
-
ty indicated on the burner identification plate.
Before starting up, make sure that:
•
The right type of fuel has been selected.
• Make sure that the mains voltage corresponds to the manufacturer's
requirements and that all electrical connections made at the instal
-
lation site are effected properly as illustrated in our wiring diagram.
•
Make sure that the combustion products may be freely vented throu
-
gh the boiler and flue dampers.
•
Check that there is water in the boiler and that the gate valves of the
system are open.
•
Check that all the gate valves fitted on the fuel suction and return
pipes are open; the same applies to any other fuel shut-off devices.
•
There is fuel oil in the tank and water in the boiler.
•
Make sure that the combustion head penetrates into the furnace to
the extent requested by the boiler manufacturer. Check that the air
closure device on the combustion head is in the right position to
guarantee a correct combustion, the air passage between disk and
head must be slightly reduced if a relatively small amount of fuel is
supplied. When the fuel supply is abundant the air passage must
be increased, see chapter "COMBUSTION HEAD ADJUSTMENT”.
•
Check that the nozzles fitted on the burner are suitable for the boiler
capacity. If necessary, replace them with suitable ones.
CAUTION / WARNINGS
For burner adjustment see the quick guide supplied.
• Turn on the main switch and the one on the control panel.
•
The programmer is activated and it starts carrying out the predefi
-
ned program activating the burner devices.The equipment will start
operation as described in the Chapter “DESCRIPTION OF OPERA
-
TION”.
THERMAL RELAY CALIBRATION
The thermal relay prevents motor failure due to a large increase in
electric absorption, or the lack of single-stage.
For calibrating, please refer to the nominal value of the motor current.
To reset the burner, if the thermal relay trips, press the reset button
(RESET).
DANGER / ATTENTION
The automatic reset may be dangerous thus, when possible, do
not set this function on the thermal relay.
ENGLISH
22 / 54
0006160337_202006
Содержание 56570010
Страница 2: ......
Страница 44: ...SCHEMI ELETTRICI TBML 80 120 160 ITALIANO 42 54 0006160337_202006...
Страница 45: ...ITALIANO 43 54 0006160337_202006...
Страница 46: ...ITALIANO 44 54 0006160337_202006...
Страница 47: ...ITALIANO 45 54 0006160337_202006...
Страница 48: ...BT1 BA BP I1 I2 I3 I4 ITALIANO 46 54 0006160337_202006...
Страница 50: ...TBML 210 310 ITALIANO 48 54 0006160337_202006...
Страница 51: ...ITALIANO 49 54 0006160337_202006...
Страница 52: ...ITALIANO 50 54 0006160337_202006...
Страница 53: ...ITALIANO 51 54 0006160337_202006...
Страница 54: ...BT1 BA BP I1 I2 I3 I4 ITALIANO 52 54 0006160337_202006...
Страница 56: ...ITALIANO 54 54 0006160337_202006...
Страница 98: ...WIRING DIAGRAMS TBML 80 120 160 ENGLISH 42 54 0006160337_202006...
Страница 99: ...ENGLISH 43 54 0006160337_202006...
Страница 100: ...ENGLISH 44 54 0006160337_202006...
Страница 101: ...ENGLISH 45 54 0006160337_202006...
Страница 102: ...BT1 BA BP I1 I2 I3 I4 ENGLISH 46 54 0006160337_202006...
Страница 104: ...TBML 210 310 ENGLISH 48 54 0006160337_202006...
Страница 105: ...ENGLISH 49 54 0006160337_202006...
Страница 106: ...ENGLISH 50 54 0006160337_202006...
Страница 107: ...ENGLISH 51 54 0006160337_202006...
Страница 108: ...BT1 BA BP I1 I2 I3 I4 ENGLISH 52 54 0006160337_202006...
Страница 110: ...ENGLISH 54 54 0006160337_202006...
Страница 111: ......