INSTRUCTIONS FOR DETERMINING THE CAUSE LEADING TO IRREGULARITIES IN THE
OPERATION AND THEIR ELIMINATION
IRREGULARITY
The equipment locks out with the flame
on (red lamp on). The fault is in the flame
control device.
The equipment goes into lock-out spraying
liquid fuel but the flame does not ignite (red
light on).
The equipment goes to lock-out without
spraying fuel.
The burner does not start.(The equipment
does not perform the start up program).
POSSIBLE CAUSE
1 Flame sensor off or soiled with smoke
2 Insufficient draught.
3 Flame sensor circuit interrupted in the
equipment.
4 Dirty flame disk and diffuser.
1 Ignition circuit severed.
2 The ignition transformer cables are
discharging to ground.
3 The ignition transformer leads are not
properly connected.
4 Ignition transformer is faulty.
5 The electrode faces are not at the right
distance.
6 Electrodes discharge to earth because
they are dirty or their insulation is
cracked: check also the porcelain
insulator terminals.
1 Pump pressure is not regular.
2 Water in the fuel.
3 Too much combustion air.
4 Air passage between flame disk and
diffuser excessively closed.
5 Nozzle worn out or dirty.
1 Thermostats (boiler or room) or
pressure switches are open.
2 Flame sensor short circuit.
3 Absence of line voltage, main switch
open, meter switch tripped or absence
of line voltage.
4 Thermostat line not wired according to
diagram or open thermostats.
5 Equipment internal fault.
REMEDY
1 Clean or replace.
2 Check all the smoke ducts in the boiler
and in the chimney.
3 Replace the equipment.
4 Clean.
1 Check the entire circuit.
2 Replace.
3 Restore the connection.
4 Replace.
5 Return to the required position.
6 Clean and if necessary replace them.
1 Adjust.
2 Drain water from the tank using a
suitable pump. Never use the burner
pump for this purpose.
3 Reduce combustion air.
4 Correct the position of the combustion
head adjusting device.
5 Clean or replace.
1 Raise the thermostats settings, or
wait that the contacts close for natural
decrease of temperature or pressure.
2 Replace it.
3 Activate switches or wait for power to
return.
4 Check the connections and
thermostats.
5 Replace it.
33 / 40
0006160435_202112
ENGLISH
Содержание 35575410
Страница 2: ......
Страница 38: ...SCHEMI ELETTRICI TBL 18P TBL 26P 36 40 0006160435_202112 ITALIANO ...
Страница 39: ...TBL 35P DACA 37 40 0006160435_202112 ITALIANO ...
Страница 40: ...TBL 35P TBL 45P 38 40 0006160435_202112 ITALIANO ...
Страница 42: ...40 40 0006160435_202112 ITALIANO ...
Страница 78: ...WIRING DIAGRAMS TBL 18P TBL 26P 36 40 0006160435_202112 ENGLISH ...
Страница 79: ...TBL 35P DACA 37 40 0006160435_202112 ENGLISH ...
Страница 80: ...TBL 35P TBL 45P 38 40 0006160435_202112 ENGLISH ...
Страница 82: ...40 40 0006160435_202112 ENGLISH ...
Страница 83: ......