background image

 

6

 

STARTUP

 

 

40

 

www. matrix-vision.com 

BVS SC-_1280Z00-30-0-0 
SMART

CAMERA

 Fieldbus

 

www.balluff.com 

Data modules for IO-Link inputs and outputs 

Data module 

Data width 

Input

 

Output

 

IOL_I/O_1/_1byte 

1 byte 

1 byte 

IOL_I/O_2/_2byte 

2 bytes 

2 bytes 

IOL_I/O_2/_2byte 

2 bytes 

2 bytes 

IOL_I/O_4/_4byte 

4 bytes 

4 bytes 

IOL_I/O_4/_2byte 

4 bytes 

2 bytes 

IOL_I/O_2/_8byte 

2 bytes 

8 bytes 

IOL_I/O_4/_8byte 

4 bytes 

8 bytes 

IOL_I/O_8/_2byte 

8 bytes 

2 bytes 

IOL_I/O_8/_4byte 

8 bytes 

4 bytes 

IOL_I/O_8/_8byte 

8 bytes 

8 bytes 

IOL_I/O_10/_10byte 

10 bytes 

10 bytes 

IOL_I/O_4/_32byte 

4 bytes 

32 bytes 

IOL_I/O_32/_4byte 

32 bytes 

4 bytes 

IOL_I/O_16/_16byte 

16 bytes 

16 bytes 

IOL_I/O_24/_24byte 

24 bytes 

24 bytes 

IOL_I/O_32/_32byte 

32 bytes 

32 bytes 

 

Additional modules (slot 3 to 9) 

Slot 

Subslot 

Input 

Output 

Contents 

1 byte 

IO-Link station diagnostics 

1 byte 

IO-Link extended diagnostics 

1 byte 

Input pin 4 

1 byte 

Output pin 4 

1 byte 

Restart pin 4* 

1 byte 

Input Pin 2 

1 byte 

Output pin 2 

1 byte 

Restart pin 2* 

 

NOTE

 

 

Project planning software of various providers mostly offers graph-
ical assistance during configuration; the configuration string is au-
tomatically created.

 

Содержание SMARTCAMERA

Страница 1: ...BVS SC _1280Z00 30 0 0 SMARTCAMERA Fieldbus User s manual ...

Страница 2: ...www balluff com ...

Страница 3: ... 4 1 Product variants 9 4 2 Scope of delivery 10 4 2 1 Assembly 11 4 3 Product specification 13 4 3 1 Image sensor 13 4 3 2 Mechanical data 13 4 3 3 Electrical data 13 4 3 4 Operating conditions 14 4 4 Connections and pin assignment 15 4 4 1 Fieldbus versions 15 4 4 2 Power 18 4 4 3 LAN 19 4 4 4 Fieldbus 20 4 4 5 IO Link 20 4 5 Display elements 21 4 5 1 Displays on the front at the plug connectors...

Страница 4: ...ters in BVS Cockpit 35 6 7 2 Configuration 37 6 7 3 Coding IO Link data modules slot 2 38 6 7 4 Data modules for IO Link inputs 39 6 7 5 Parameter configuration 42 6 7 6 Integration into project planning software 45 6 7 7 Process data structure 50 6 7 8 Configuration via explicit messages 53 6 7 9 SMARTCAMERA integration in Rockwell Studio 5000 55 6 8 IO Link interface 58 6 8 1 PLC gateway mode 58...

Страница 5: ...vice Simple camera access from the network Simple and user friendly settings control of camera without additional software Simple user supporting operation Direct connection to industrial networks fieldbuses Support of Industry 4 0 through IO Link Separate data channel for larger data volumes Integrated flexible displays of process statistics These characteristics make it possible to easily create...

Страница 6: ...hown with a period e g 0 123 Hexadecimal numbers are shown with the additional indicator hex e g 00hex Parameters are shown in italics e g CRC_16 Path information for saving data is shown with fixed font width e g Projekt Data Types Benutzerdefiniert Characters transmitted in ASCII code are set in apostrophes e g L NOTE A note indicates important information that helps you optimize us age of the p...

Страница 7: ...e ROM EMC Electromagnetic compatibility EtherNet IP Ethernet Industrial Protocol FCC Federal Communications Commission FE Function ground GND Ground GSD General Station Description GSDML GSD Markup Language I O port Digital input output port ID Identification IO Input Output IP Internet Protocol IRT Isochronous Real time LAN Local Area Network LPS Limited Power Source MAC Media Access Control n c ...

Страница 8: ...e conditions in these operating instructions as well as the regulations of the Balluff Enduser Licensing Agreement You may use the software only in compliance with these provisions If they should not yet be available Balluff GmbH will gladly provide the cur rent GTC upon request The SMARTCAMERA uses an embedded Linux GNU as the operating system Also used are a variety of freely available tools whi...

Страница 9: ...duct specification This product was developed and manufactured in accordance with all applicable European Directives CE conformity has been verified This product is approved by UL PROCESS CONTROL EQUIPMENT File No E227256 All approvals and certifications are no longer valid in the following cases Components are used that are not part of the SMARTCAMERA BVS SC Components are used that have not been...

Страница 10: ... Before maintenance disconnect the device from the power supply NOTE In the interests of product improvement Balluff GmbH reserves the right to change the technical data of the product and the con tent of this manual at any time without notice 3 3 Disposal Observe the national regulations for disposal ...

Страница 11: ...quirements in the environment of Industry 4 0 Since the complete software is located on the SMARTCAMERA itself no external soft ware is required for the configuration and monitor display Using standardized web browsers such as Google Chrome Mozilla Firefox or Internet Explorer the user can easily connect with the SMARTCAMERA and work in the Balluff BVS Cockpit interface developed specifically for ...

Страница 12: ...ROFINET EtherNet IP configura ble yes 2 81 BVS0033 BVS SC M1280Z00 30 020 Mono chrome All tools plus HDevelopinter face yes PROFINET EtherNet IP configura ble yes 2 81 1 depending on the configuration of the IO Link port 4 2 Scope of delivery Included in the scope of delivery SMARTCAMERA BVS SC Filter mounted o with monochrome sensor protection glass o with color sensor IR Cut 2 cap M12 Safety Pre...

Страница 13: ...S 004 C2 3 xx14 2 Screw on filter BAM OF VS 002 xx yy Lights BAE LX Touchpanel PC BAE PD VS 011 01 Mounting accessories Connection cable Power supply units NOTE Visit www balluff com for more information on available software and accessories The camera features 12 internal threads for installation at the location of use Four threads each at the rear the left and the right This ensures secure and r...

Страница 14: ...t the rear plate have M4 threads The maximum engagement length is 5 mm The maximum tightening torque is 2 Nm The lateral screw connections have an M5 thread The maximum engagement length is 5 mm The maximum tightening torque is 2 6 Nm WARNING The SMARTCAMERA and accessories must be firmly attached Use only installation materials which are sufficiently dimensioned and ensure secure attachment ...

Страница 15: ...terial Painted aluminum die cast box Degree of protection IP67 with connectors and protection tube 2 Weight approx 360 g Dimensions L W H without connector without lens 110 62 55 mm 2 The enclosure rating has not been UL certified Supply voltage 24V 20 Residual ripple 5 Rated current consumption without external load 300mA Max current consumption 4A Protective circuit Reverse polarity protection 4...

Страница 16: ... 61000 6 3 EN 55011 Vibration shock for opera tion inside EN 60068 Part 2 6 27 Operation Internally Height up to 2000 m Relative humidity maximum 80 for temperatures up to 31 C decreasing linearly to 50 at 40 C Pollution degree Pollution degree 2 Vibration shock was verified for the SMARTCAMERA the C mount lens used and its adjustment rings must be secured accordingly for operation 4 3 4 Operating...

Страница 17: ...CAMERA with an IO Link device or e g an external lighting LAN Integrates the SMARTCAMERA in a local network PROFINET Ether Net IP Connects the SMARTCAMERA with the fieldbus network PROFINET EtherNet IP WARNING The SMARTCAMERA and accessories shall be supplied by limited energy in accordance to UL 61010 1 Third Edition Sub Clauses 9 4 or LPS in accordance to UL 60950 1 or Class 2 in accordance to U...

Страница 18: ...s EN 61131 2 Type 3 The maximum load on any output is 100 mA The total current of the module must not exceed 4 A per pin The load or supply must be limited accordingly IO Link 5 pin M12 female A coded Pin Description Function 1 L Supply voltage 2 I Q IO 6 Input output 3 L Ground 4 C Q IO 7 IO Link Input output 5 Not used None Pin may not be used NOTE The maximum load on the supply voltage output i...

Страница 19: ...idirectional data Pair D 6 BI_DD Bidirectional data Pair D 7 BI_DC Bidirectional data Pair C 8 BI_DC Bidirectional data Pair C Fieldbus Female M12 4 pin D coded Pin Description Function 1 Tx Transmit data 2 Rx Receive data 3 Tx Transmit data 4 Rx Receive data NOTE The cable must correspond at least to category 5 in accordance with EIA TIA 568 NOTE The cable must correspond at least to category 5e ...

Страница 20: ...nal 1 11 30 V 2 5 mA Delay 160 μs Operation as output Voltage Signal 0 0 V VD 100 mA max Signal 1 24 V VDC VD 100 mA max Voltage drop VD 2 V Delay 10 μs See also the guideline on digital inputs EN 61131 2 Type 3 Below are examples how inputs and outputs must be connected to obtain input and output function Input connection If I O 0 is configured as input it is sinking and can be connected directly...

Страница 21: ... is predominantly used in Europe The output is sourcing so that the load between I O and GND must be switched accordingly The load is connected with supply voltage if 1 is being output Figure 5 PNP output connection NPN Ausgangsbeschaltung NPN logic is predominantly used in Asia The output is sinking so that the load between I O and supply voltage must be switched accordingly The load is set to GN...

Страница 22: ...ignals in addition to the binary process signals over the IO Link interface The IO Link interface is suitable for connecting external lighting e g a ring light Compatibility with standard I O IO Link sensors actuators can be connected to existing I O modules Sensors actuators that are not IO Link capable can be connected to an IO Link module Standard sensor actuator cables can be used Key technica...

Страница 23: ...f No supply voltage Green on Inspection is running or waiting for a trigger Green flashing Inspection stopped or in configuration mode Red on Fault Red flashing Firmware update active Signal LED Off Signal 0 Yellow on Signal 1 The signal LED indicates the status of the I O cable null Fieldbus LED Indicator Function Fieldbus Link Off No fieldbus connection Green on Fieldbus connection established F...

Страница 24: ... IO not ready Fieldbus 1 and Fieldbus 2 Both LEDs flashing red DCP signal service enabled EtherNet IP LED Indicator Function Fieldbus 1 NS Network Status Off No voltage or no IP address Green Connection made Green flashing No connection made Red Duplicate IP address Red flashing Connection timeout Red Green flashing Self test after switch on Fieldbus 2 MS Module Status Off No voltage Green Device ...

Страница 25: ...uration of the IO Link data length self test after switch on Rot on IO Link short circuit sensor supply short circuit firm ware update IO Link Pin 2 Off Status of input or output pin is 0 Yellow on Status of input or output pin is 1 Red on Short circuit at output LAN LED Indicator Function LAN Link Off No LAN connection Green on LAN connection established LAN Act Off No data transfer Yellow flashi...

Страница 26: ... are possible Structure Consequences SMARTCAMERA and PC are connected directly via a LAN cable IP addresses are set automatically SMARTCAMERA and PC are in the same subnet of a local net work and a DHCP server is available for automatic IP as signment IP addresses are set automatically SMARTCAMERA and PC are in the same subnet of a local net work and no DHCP server is available for automatic IP as...

Страница 27: ...e NOTE JavaScript must be enabled in the web browser 1 Record the serial number of the SMARTCAMERA The serial number is located on the nameplate on the SMARTCAMERA If the nameplate is not visible you can also locate the SMARTCAMERA in the net work via Windows Explorer e g sc 150800015de 2 To do so select the network folder to display all the network devices It also lists the connected SMARTCAMERA ...

Страница 28: ...5 FIRST STEPS 26 www matrix vision com BVS SC _1280Z00 30 0 0 SMARTCAMERA Fieldbus www balluff com Figure 8 Display of all SMARTCAMERAs in the network ...

Страница 29: ...ter 2 Unzip the downloaded file It contains a A PDF document that describes the new functions fixed errors and the up date procedure b The file BVS_Cockpit_X X X sh This contains the new software and must be loaded into the SMARTCAMERA X X X indicates the software version 3 If an inspection program is running please stop it and make sure that the camera is not acquiring new images 4 Press the Wind...

Страница 30: ... the network environment The different options are described in the following examples This covers a large part of the application cases To operate the SMARTCAMERA requires that the supply voltage is provided via the power connection in any case In the fieldbus 1 topology both network connections of the SMARTCAMERA are being used The LAN connection is used for the configuration and if necessary th...

Страница 31: ...TCAM ERA are shown The IO Link port allows expanding the SMARTCAMERA by additional I O signals The example shows a Balluff SMARTLIGHT for indicating the system status Figure 10 Fieldbus 3 topology IO Link can also be combined with the fieldbus 2 topology Figure 11 Fieldbus 2 topology in combination with IO Link The following sections describe the configuration of the individual interfaces in detai...

Страница 32: ...lecting the communication interface for the process data The exchange of the process data results of image analysis control of image acquisi tion can be performed either via fieldbus or LAN interface The operating principle and communication protocol of the fieldbuses are described in the separate software manual BVS Cockpit Manual under Connection to the custom er control system Communication via...

Страница 33: ... explicitly created to be able to subdivide computers in different networks and to structure it in this way Since the different subnets on the other hand are con nected via switches the communication with the SMARTCAMERA is still possible In most networks it is only necessary to enter the URL http sc 150800015de with the matching serial number in the address field of the browser The connection is ...

Страница 34: ...nterface is used permanently for monitoring the image analysis The fieldbus interface features a transfer rate of only 100 Mbit s and the real time data have priority over the non time critical data of the web interface This may lead to problems such as delayed response of the web interface particularly during the transfer of the live image The network configuration is done in the System settings ...

Страница 35: ...vated the state of the in output is shown with the camera LED only supported on smart cameras Duration Defines the pulse duration of an output in milliseconds The default value of 0 means that the output is active until another value is set manually using the Set outputs tool Choosing pulse durations larger than zero the out put is active for the defined time span and retransferred into its inacti...

Страница 36: ... configuration Signal I O 0 I O 1 I O 2 I O 3 I O 4 I O 5 I O 6 I O 7 Power Pin 2 Pin 4 I O Link camera mode Depends on the device configuration see IO Link inter face I O Link I O mode Pin 2 Pin 4 I O Link PLC gateway mode N C signals depending on the configuration via fieldbus Figure 13 Control plan The same applies here again when operating the I O as output signals of the same name are switche...

Страница 37: ...g between PROFINET and Ethernet IP NOTE After switching the fieldbus and after setting a few fieldbus param eters the fieldbus module of the SMARTCAMERA must be re started Only then does the change take effect In this case the button will appear for initiating the re start Click on the button when you are finished making your set tings The fieldbus module then restarts After a few seconds the dial...

Страница 38: ...ask Fieldbus subnet mask assigned by the PLC IO Link mode Defines how the IO Link master port is used The communication between the SMARTCAMERA and the host system is done via PROFINET IO The system PROFINET IO consists of the following components IO controller e g PLC IO device here the SMARTCAMERA In a PROFINET network IO controllers and IO devices are connected to each other using all common ne...

Страница 39: ...MERA is delivered without a device name The GSDML file has the prepared device name BVS SC In configuring PROFINET devices a device is mapped as a modular system that con sists of a BVS SC head module and multiple data modules GSDML file The device data required for configuring is stored in a GSDML file General Station De scription The data module of the SMARTCAMERA the IO Link port and any additi...

Страница 40: ...dules of various data widths or configurable as a standard I O port IO Link parameterization 3 IO Link station diagnostics or IO Link extended diagnostics Slots for optional IO Link additional modules 4 Input pin 4 5 Output pin 4 6 Restart pin 4 7 Input pin 2 8 Output pin 2 9 Restart pin 2 Data modules for standard I O ports Data module Data width Standard I O 0 byte see Additional modules slot 3 ...

Страница 41: ...ytes IOL_I_8byte 8 bytes IOL_I_10byte 10 bytes IOL_I_16byte 16 bytes IOL_I_24byte 24 bytes IOL_I_32byte 32 bytes Data modules for IO Link outputs Data module Data width IOL_O_1byte 1 byte IOL_O_2byte 2 bytes IOL_O_4byte 4 bytes IOL_O_6byte 6 bytes IOL_O_8byte 8 bytes IOL_O_10byte 10 bytes IOL_O_16byte 16 bytes IOL_O_24byte 24 bytes IOL_O_32byte 32 bytes 6 7 4 Data modules for IO Link inputs ...

Страница 42: ...te 8 bytes 8 bytes IOL_I O_10 _10byte 10 bytes 10 bytes IOL_I O_4 _32byte 4 bytes 32 bytes IOL_I O_32 _4byte 32 bytes 4 bytes IOL_I O_16 _16byte 16 bytes 16 bytes IOL_I O_24 _24byte 24 bytes 24 bytes IOL_I O_32 _32byte 32 bytes 32 bytes Additional modules slot 3 to 9 Slot Subslot Input Output Contents 3 1 1 byte IO Link station diagnostics 3 1 1 byte IO Link extended diagnostics 4 1 1 byte Input p...

Страница 43: ...e short circuit pin 3 IO Link mode 5 Overload warning pin 2 or pin 4 6 Actuator warning pin 2 or pin 4 7 Supply voltage short circuit pin 3 IO mode IO Link extended diagnostics Bit Meaning 0 IO Link device connected 1 2 3 Supply voltage short circuit pin 3 4 Overload warning pin 4 5 Overload warning pin 2 6 Actuator warning pin 4 7 Actuator warning pin 2 Modules for use as digital I O port All of ...

Страница 44: ...ault 1 0 0 6 bits Cycle time 0 63 0 0 6 2 bits Cycle time base 0 1 2 0 2 0 0 1 byte Data window offset 0 31 0 1 0 1 byte Max data input length 0 32 0 3 0 0 2 bits Validation type 0 255 0 1 0 1 byte Vendor ID byte0 0 255 0 2 0 1 byte Vendor ID byte 1 0 255 0 3 0 1 byte Vendor ID byte 2 0 255 0 4 0 1 byte Device ID byte 0 0 255 0 5 0 1 byte Device ID byte 1 0 255 0 6 0 16 bytes Serial number String ...

Страница 45: ...efined Normally open Input as normally open contact Normally closed Input as normally closed contact Output Output function Diagnostics input Cable break detection IO Link safe state pin 4 2 This function is an extension of the IO Link port starting configuration A safe state that the port is to take on in the case of a loss of bus communication can be predefined for the respective port Cycle time...

Страница 46: ...e plate Parameter server optional Automatic upload IO Link slave IO Link master or download IO Link master IO Link slave can be switched on using this parameter For automatic upload the parameter configuration is read when an IO Link device is plugged in For automatic download the parameter configuration is transmitted to the device when an IO Link device is plugged in Background The automatic upl...

Страница 47: ...irectory and GSDML file The Install button becomes active only if a GSDML file is selected 5 Click on Install The GSDML file is being installed A message appears once the process has finished 6 Confirm the message and close the window 7 Select Tools Update catalog The devices are displayed in the product tree Figure 15 Installing the GSDML file Adding a PROFINET device The devices are located in t...

Страница 48: ...x vision com BVS SC _1280Z00 30 0 0 SMARTCAMERA Fieldbus www balluff com Figure 16 Adding a PROFINET device Determining the station name 1 Define the PROFINET station name of the device Figure 17 Determining the station name ...

Страница 49: ...ss Configuring SMARTCAMERA data The number of process data buffer size of the SMARTCAMERA can be selected by deleting or inserting a corresponding module min 16 bytes max 1280 bytes When a module is not plugged in no process data are configured The optimal size depends on the size of the results container used and the input data Figure 19 Configuring SMARTCAMERA data ...

Страница 50: ... sary to delete the default IO module first 1 Drag the selected module to slot 2 slots 3 9 are reserved for optional additional modules for IO Link Figure 20 Configuring the IO Link module 2 If the IO Link port is to be used with standard I O slot 2 must host the Standard I O module and slots 3 to 9 must host the corresponding modules input or output pin 4 and pin 2 Figure 21 Using IO Link port wi...

Страница 51: ...ses only MAC address Basic MAC address of the fieldbus Handshake timeout This setting activates a 500 ms timeout for the handshake of the process data IP mode IP address subnet mask and gateway can either be manually set static or automatically using DHCP protocol or BOOTP IP address Fieldbus IP Address Subnet mase Fieldbus subnet mask Gateway Fieldbus default gateway IO Link mode Defines how the ...

Страница 52: ...t Manual under Appendix Con trol commands Communication via fieldbus 128 1 Digital inputs Bit 0 Pin 4 input data Bit 1 Pin 2 input data 129 1 IO Link Device Status Bit 0 Port in IO Link mode Bit 1 Device is connected Bit 2 Validierung failed Bit 3 Short circuit between pins 1 and 3 Bit 4 Pin 4 overload Bit 5 Pin 2 overload 130 32 IO Link process data 162 2 IO Link vendor ID 164 3 IO Link device ID...

Страница 53: ... a pin is an input or output A digital I O pin is always both If a pin is to be used as an input the output must output a zero byte 128 in the output assembly The output stage is a highside switch and if it outputs a zero the pin is highimpedence and can be used as an input The input data byte 128 in the input assembly always represent the logical value of the corresponding pin even if it is con t...

Страница 54: ...ement functions disabled stored parameter data and identifi cation data of the IO Link device remain stored Enable upload If only the upload is enabled the master always starts an upload of the parameter data In this case the upload is independent of the upload flag of the IO Link device If there are no data stored in the master port an upload also takes place e g after deleting the data or before...

Страница 55: ...onnection is lost This always affects pin 2 It affects pin 4 if it is configured as a digital I O line Standard services 14 Get Attribute Single and 16 Set Attribute Single are used for the fault state Values can be read Get Attribute Single and written Set Attribute Single Attribute 6 enables or disables the Fault State function Class Instance Attribute Value 9 1 6 0 Fault State disabled 1 Fault ...

Страница 56: ... parameter Service Class Instance Attribute Value 50 150 1 3 Read Parameter Byte Meaning 0 Index lowest byte 1 Index highest byte 2 Subindex The response contains the addressed data There must be sufficient storage space on the host system Writing a parameter Service Class Instance Attribute Value 50 150 1 2 Write Parameter Byte Meaning 0 Index lowest byte 1 Index highest byte 2 Subindex 3 n Data ...

Страница 57: ...onnected to a CompactLogix or Con trolLogix PLC 1 Start EDS Hardware Installation Tool in the Logix Designer and register EDS file Figure 23 Register EDS File 2 Right click Ethernet on the corresponding scanner card Select a new module Note The function is not available in online mode 6 7 9 SMARTCAME RA integration in Rockwell Studio 5000 ...

Страница 58: ...ARTUP 56 www matrix vision com BVS SC _1280Z00 30 0 0 SMARTCAMERA Fieldbus www balluff com Figure 24 Add module 3 Select SMARTCAMERA Module BVS_SC 1280 and apply to the configuration Figure 25 Select camera ...

Страница 59: ...us www balluff com 4 The input output and configuration tags are automatically created in the controller tags Figure 26 Camera controller tags 5 Set the desired IP address and connection parameters for the SMARTCAM ERA under Module Properties Figure 27 Set connection parameters ...

Страница 60: ...ation tab in the System Settings In this mode the interface is controlled by the controller e g PLC The parameterization is done via the fieldbus diagnostics are forwarded via the fieldbus to the controller Figure 28 PLC gateway mode This mode allows controlling some special IO Link devices by the SMARTCAMERA In this case the control is done via the 8 IO channels of the camera IO Link parameters o...

Страница 61: ...Port 7 4 BNI004L BNI IOL 310 000 K025 IO1 IO2 IO3 IO4 IO5 IO6 IO7 IO8 BNI004K BNI IOL 309 000 K024 IO1 IO2 IO3 IO4 IO5 IO6 IO7 IO8 BNI005M BNI IOL 771 000 K027 IO1 IO2 IO3 IO4 IO5 IO6 IO7 IO8 BNI003A BNI IOL 302 S01 Z013 Port 0 4 Port 1 4 Port 2 4 Port 3 4 Port 4 4 Port 5 4 Port 6 4 Port 7 4 1 The representation 0 4 means port 0 pin 4 Some of these I O modules require a voltage supply for actuator...

Страница 62: ...36 3 stage Then IO channels I O 5 I O 6 and I O 7 are used to control the segments of the SMARTLIGHT I O 5 I O 6 I O 7 Description 0 0 0 Off 1 0 0 Red off off 0 1 0 Off yellow off 1 1 0 Off off green 0 0 1 Flashing red off off 1 0 1 Off flashing yellow off 0 1 1 Off off flashing green 1 1 1 Red yellow green NOTE The IO channels I O 5 I O 6 and I O 7 must have been configured as output in the BVS C...

Страница 63: ...ARTCAMERA Pin 2 and pin 4 can each be configured as an input or output I O 6 of ther SMARTCAMERAis linked with pin 2 and I O 7 with pin 4 An external lighting can be controlled here for example IO Link parameters of the controller are not taken into account no data or diagnostics are exchanged with the controller Figure 30 IO mode 6 8 3 IO mode ...

Страница 64: ...at your PC retrieves it s IP address automatically DHCP 1 Open the settings of your network adapter and there the settings of the internet protocoll TCP version 4 2 Set the IP address to automatically 3 Inside the tab alternative configuration also set the IP address to autmatically 4 Close the windows and restart the PC 5 Retry the previously described way No con nection to the cam era pos sible ...

Страница 65: ...able Name Type Host Address Life sec SC NNNNNNNNNDE 20 UNIQUE 169 254 4 9 540 SC NNNNNNNNNDE 00 UNIQUE 169 254 4 9 549 You can also reach the camera with the IP address directly in this sample 169 254 4 9 Connec tion to the camera possible however a dialog appears that the connec tion to the camera was lost Firewall ac tive Please add http gemini as trusted web addresses to your firewall settings ...

Страница 66: ...ng credentials Login expert Password expert If Windows does not prompt for the login and password please use this command in a ter minal window replacing the host name with the correct value for your camera cmdkey exe add gemini 000110 U expert P expert 7 2 Type code 1 2 3 4 5 6 7 8 9 1 0 1 1 1 2 1 3 1 4 1 5 1 6 1 7 1 8 1 9 2 0 2 1 2 2 B V S S C 1 2 8 0 Z 0 0 1 3 BVS Balluff Vision Solutions 5 6 S...

Страница 67: ...C2 3 1614 2 C mount lens 16 mm focal length BAM02FF BAM LS VS 004 C2 3 2514 2 C mount lens 25 mm focal length BAM02FH BAM LS VS 004 C2 3 3514 2 C mount lens 35 mm focal length BAM02FJ BAM LS VS 004 C2 3 5014 2 C mount lens 50 mm focal length BAM02Y3 BAM LS VS 004 C2 3 7532 2 C mount lens 75 mm focal length Filters BAM02FK BAM OF VS 002 PL 27 Lens filter 27 mm polarized BAM02FL BAM OF VS 002 UV 27 ...

Страница 68: ...bracket SMARTCAMERA Connection cable BCC0HZK BCC M418 E818 8X0 723 PS58N9 020 GigE cable RJ45 M12 2 m BCC06K7 BCC M418 0000 2A 044 VX8825 020 IO interface M12 open 2 m BCC0JF0 BCC M414 E834 8G 668 PS54N2 020 PROFINET M12 M12 2 m BCC0E90 BCC M414 E894 8G 672 ES64N9 020 EtherNet IP M12 M12 2 m BCC032F BCC M415 0000 1A 003 PX0434 020 Power M12 open 2 m BCC031N BCC M414 0000 2A 003 PX0434 020 IO Link ...

Страница 69: ...f GmbH Schurwaldstraße 9 73765 Neuhausen a d F Germany Tel 49 7158 173 0 Fax 49 7158 5010 balluff balluff de www balluff com www balluff com No 928009 726 EN 09 130077 G20 Subject to modification Replaces K19 ...

Отзывы: