12
deutsch
IOLink Interface
Parameterdaten
Index
hex
S
ubindex
hex
Object name
Access
Length
Value Range
Gradi
ent
Unit
Default
0x3C
0x01
SetPoint 1 = SP1
R/W
2 Byte
Process Data
100%
0x3C
0x02
SetPoint 2 = rP1
R/W
2 Byte
Process Data
0%
0x3E
0x01
SetPoint 1 = SP2
R/W
2 Byte
Process Data
100%
0x3E
0x02
SetPoint 2 = rP2
R/W
2 Byte
Process Data
0%
0x60
0x00
Password
W
4 Byte
0000..9999
0
0xD0
0x00
Delay Switching Time 1
R/W
2 Byte
0..500
0.1
sec
0
0xD1
0x00
Delay Back Switching Time 1
R/W
2 Byte
0..500
0.1
sec
0
0xD2
0x00
Delay Switching Time 2
R/W
2 Byte
0..500
0.1
sec
0
0xD3
0x00
Delay Back Switching Time 2
R/W
2 Byte
0..500
0.1
sec
0
0xD5
0x00
Min Pressure Value
R
2 Byte
Process Data
0xD6
0x00
Max Pressure Value
R
2 Byte
Process Data
0xD7
0x00
Measure damping
R/W
2 Byte
0…1000
in 10 ms steps
1
ms
0
Drucksensoren mit IO-Link
BSP-B... /-V...