Diagnostics 

8.1.

 

Diagnostics 
message 

  The diagnostics message that is generated by the module in the event of an error is usually 

read out by the PLC and processed. It is also possible to read out the diagnosis from the 
module by means of function modules and evaluate it. 
 
The diagnostics message is 34 bytes long and divided into 3 blocks: 
Block Header, Alarm Specifier, Channel Properties 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Byte 

Value 

Meaning 

Block 

00 

Block Type 

Block Header 

02 

00 

Block Length  

1E 

01 

Block Version High 

00 

Block Version Low 

00 

Alarm type 

01 

00 

API 

00 

10 

00 

11 

00 

12 

00 

Slot number 

13 

01 

14 

00 

Subslot number 

15 

01 

16 

00 

Module ID 

17 

00 

18 

00 

19 

17 

20 

00 

Submodule ID 

21 

00 

22 

00 

23 

01 

24 

A8 

AlarmSpecifier 

AlarmSpecifier 

25 

36 

26 

80 

User Structure ID 

27 

00 

28 

00 

Channel number 

29 

08 

30 

08 

ChannelProperties 

ChannelProperties 

31 

00 

32 

00 

ChannelErrorType 

33 

1 A 

 

Содержание BNI PNT-508-105-Z031-002

Страница 1: ...BNI PNT 508 105 Z031 BNI PNT 508 105 Z031 002 BNI PNT 508 105 Z031 004 IP67 Module User s Guide...

Страница 2: ...NT 508 105 Z031 002 and BNI PNT 508 105 Z031 004 8 I O port 9 IO Link port 9 Port 9 4 Technical data 10 4 1 Dimensions BNI PNT 508 105 Z031 10 4 2 Mechanical data 10 4 3 Operating conditions 10 4 4 El...

Страница 3: ...ctions 24 Cycle settings 24 Data selection 24 Validation 24 Parameter server 25 6 Display 26 6 1 General 26 6 2 Controls and visualization 26 6 3 Display information 26 6 4 Design and symbols 27 6 5 S...

Страница 4: ...Channel Properties 40 Type 40 Accumulative 40 Maintenance 40 Specifier 40 Direction 40 8 6 Channel Error Type 41 9 Configuration of IO Link devices 42 General 42 Function block 42 Reading 42 Writing 4...

Страница 5: ...y an arrow Action instruction 1 Result of action Action instruction 2 Actions can also be indicated as numbers in parentheses 1 Step 1 2 Step 2 Syntax Numbers Decimal numbers are shown without additio...

Страница 6: ...void by Unauthorized tampering Improper use Use installation or handling contrary to the instructions provided in this operating manual Obligations of the Operating Company The device is a piece of e...

Страница 7: ...xxx 1 Ground connection 2 Display 3 Status LED 4 Port 0 5 Pin port LED signal status 6 Port 2 7 Port 4 8 Schilder 9 Port 6 10 Mounting hole 11 PROFINET port 1 12 PROFINET port 2 13 Port 1 14 Power IN...

Страница 8: ...odule sensor power supply max 16A 2 0 V GND Module sensor power supply 3 24 V Actuator power supply max 16A 4 0 V GND actuator power supply 5 FE Function ground Note Provide sensor bus power and actua...

Страница 9: ...n c 8 n c PROFINET Interface BNI PNT 508 105 Z031 002 and BNI PNT 508 105 Z031 004 Pin Function Description 1 TX 2 RX Note The FO port does not support the measurement of the optical power level Thus...

Страница 10: ...pe 2 Note Each output receives a maximum current of 2 0 A The total current of the module must not exceed 16 A Note Unused I O ports must be provided with cover caps in order to ensure enclosure ratin...

Страница 11: ...ap installation M4 Weight Approx 950 gr 4 3 Operating conditions Operating temperature Ta Storage temperature 5 C 55 C 25 C 70 C EMC Immunit t Immunity Emission Emission EMC directive 2004 108 EEC EN...

Страница 12: ...nstallation with 2 securing holes Ground strap installation M4 Weight Approx 950 gr 4 8 Operating conditions Operating temperature Ta Storage temperature 5 C 55 C 25 C 70 C EMC Immunit t Immunity Emis...

Страница 13: ...oles Ground strap installation M4 Weight Approx 950 gr 4 13 Operating conditions Operating temperature Ta Storage temperature 5 C 55 C 25 C 70 C EMC Immunit t Immunity Emission Emission EMC directive...

Страница 14: ...ection Port Standard port Status Function off Status of input or output pin is 0 Yellow Status of input or output pin is 1 Both LEDs flashing red Short circuit at sensor supply between pin 1 and pin 3...

Страница 15: ...modules the corresponding data modules are assigned to a slot Integration of the module The device can be found by searching in the catalog and inserted in the Profinet section by drag drop In the BN...

Страница 16: ...ab to open a menu selection for defining the port functions and diagnostic functions Note IO Link configuration If the connected IO Link device needs additional power over pin 2 pin 2 must be configur...

Страница 17: ...ble IO Link module that corresponds to the process data length of the IO Link device must be selected in the catalog and dragged to the appropriate slot by means of drag drop The process data length r...

Страница 18: ...com 17 5 Integration IO Link configuration Double click on the IO Link module to change the IO Link parameters of the respective port pins A description of the individual modules is beginning in secti...

Страница 19: ...com 18 5 Integration Device name Profinet address Double click on the module in the Profinet line to view the communication parameters of the module The device name and the Profinet address IP are con...

Страница 20: ...start the tool for assigning the module a device name Assigning device name Select the desired name and use Assign name to assign the marked device that you found The device name must be the same as t...

Страница 21: ...Validation failed If the module still reports a bus error there could be a problem in one of the following areas Device relationship not established Scan the network via Target system Ethernet Ethern...

Страница 22: ...ppressed to the output of the module Optical diagnostics and diagnostics in configured diagnostics modules are not affected This function is valid only for channels pins that are configured as outputs...

Страница 23: ...wn pin 4 pin 2 Depicts a short circuit between a set output to ground at the respective port pin Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 Port 7 Port 6 Port 5 Port 4 Port 3 Port 2 Port 1 Port 0...

Страница 24: ...rt 1 Port 0 Peripheral error socket Feedback indicating the port at which an error occurred Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 Port 7 Port 6 Port 5 Port 4 Port 3 Port 2 Port 1 Port 0 Shor...

Страница 25: ...ta The visible data window for the input data can now be adjusted via an IO Link module with appropriate process data length Validation No validation Validation deactivated every device will be accept...

Страница 26: ...nload is started if activated if there are different parameter sets since no upload may be performed Enable download Select whether or not a download of parameter data to the IO Link device is to be p...

Страница 27: ...Display 2 Arrow Key 3 Octett Cursor 4 Address type cursor 5 Set Key 6 LEDs Arrow Key This button is used to go through the entries of a menu and is a short time keypress The display shows the default...

Страница 28: ...rt time keypress on Set Key Step in a menu with short time keypress on Arrow Key Actual state Change over S Condition short time keypress on Set Key S Condition long time keypress on Set Key min 3 sec...

Страница 29: ...confirmed the device performes a restart Note A factory reset can be performed only after a power reset without an attached network cable 6 8 Module Info Go through the Module Info menu with short tim...

Страница 30: ...or configuration of the module and the connected IO Link devices First ensure that integration in your network has been carried out correctly For connection setup with the web server enter the IP addr...

Страница 31: ...you can read about the configuration and network activity of the module The navigation line appears in the upper area of the window making it possible to switch between the different web pages A clic...

Страница 32: ...Link device is connected to one of the IO Link ports some of the device data is displayed in addition to the module data This text or module port can be used as a link to the device properties by mea...

Страница 33: ...that can be read or written are defined by the connected IO Link device Refer to the manual of the IO Link device for more information on this Note Process data and parameterization data of the IO Lin...

Страница 34: ...this screen The IO Link device parameters can be read and written under Parameter data The parameter indices and subindicies are described in the operating instructions of the IO Link device The event...

Страница 35: ...www balluff com 34 7 Webserver 7 5 Diagnostics module The current status of the module and network as shown on the module appears on this page...

Страница 36: ...7 Webserver 7 6 Configurations You can edit the module description and module position This function can only be used following input of a user name and password User name Balluff Password BNIPNT 7 7...

Страница 37: ...ed into 3 blocks Block Header Alarm Specifier Channel Properties Byte Value Meaning Block 0 00 Block Type Block Header 1 02 2 00 Block Length 3 1E 4 01 Block Version High 5 00 Block Version Low 6 00 A...

Страница 38: ...arm Type 2 bytes the information on the type of alarm is provided here Possible values Meaning 0x0001 Diagnostics API 4 bytes default is 0 Possible values Meaning 0x00000000 Default value Slot 2 bytes...

Страница 39: ...es Meaning 0x00 No diagnosis related to manufacturer is pending 0x01 Diagnosis related to channel is pending Submodules Diagnostic State Bit 13 Possible values Meaning 0x00 No further diagnosis of sub...

Страница 40: ...pin 4 0x05 Port 5 pin 4 0x06 Port 6 pin 4 0x07 Port 7 pin 4 0x08 Port 0 pin 2 0x09 Port 1 pin 2 0x0A Port 2 pin 2 0x0B Port 3 pin 2 0x0C Port 4 pin 2 0x0D Port 5 pin 2 0x0E Port 6 pin 2 0x0F Port 7 pi...

Страница 41: ...6 32 bit 0x07 64 bit 0x08 0xFF Reserved Accumulative Bit 8 not used always 0 Maintenance Bit 9 10 Possible values Meaning Bit 9 Bit 10 0x00 0x00 Diagnostics Specifier Bit 11 12 Possible values Meaning...

Страница 42: ...oltage 0x0004 Overload 0x0005 Temperature limit exceeded 0x0006 Cable break 0x0007 Upper threshold exceeded 0x0008 Lower threshold undershot 0x0009 Error 0x001A External error 0x001B Sensor has incorr...

Страница 43: ...r Port number Reserved 2 65098 FI_Index IO Link header is following IO Link header 1 0 255 Task 2 write 3 read 2 0 3276 7 65535 IO Link index Port function 1 0 255 IO Link subindex Data range 232 Rang...

Страница 44: ...tions 508 IP 67 IO Link master module 8 IO Link ports Versions 105 Display version 2 port switch Mechanical version Z031 Die cast zinc housing Data transmission Push Pull connection Power connection P...

Страница 45: ...f com 44 www balluff com Balluff GmbH Schurwaldstrasse 9 73765 Neuhausen a d F Germany Tel 49 7158 173 0 Fax 49 7158 5010 balluff balluff de No 898239 E Edition F15 Replaces Edition E15 Subject to mod...

Отзывы: