Balluff Network Interface
ProfiNet™
www.balluff.com
9
3
Getting Started
I/O port
M12, A-coded, female
Pin
Function
1
+24 V, 200 mA
2
Input/output 2A
3
GND
4
Input/output 2A
5
FE
Note
For the digital sensor inputs, refer to guideline on inputs EN 61131-2, Type 2.
Note
Each output receives a maximum current of 2.0 A.The total current of the
module must not exceed 16 A.
Note
Unused I/O ports must be provided with cover caps in order to ensure enclosure
rating IP67.
IO-Link port
M12, A-coded, female
Pin
Function
1
+24 V, 1.6 A
2
Input/output 2A
3
GND
4
IO-Link / input / output 2A
5
n.a.
Port
Port
0-7
BNI PNT-508-105-Z031
IN / OUT / IO-Link
BNI PNT-508-105-Z031-002
IN / OUT / IO-Link
BNI PNT-508-105-Z031-004
IN / OUT / IO-Link