Integration
Concluding the
configuration
Download the configuration into HW config.
At this point, the bus error on the module should disappear.
There could still be an active system error, particularly if an IO-Link is used.
Possible causes:
-
Line break (no IO-Link device connected)
-
IO-Link device fault (e.g., external voltage supply not connected)
-
Validation failed
If the module still reports a bus error, there could be a problem in one of the following areas:
-
Device relationship not established.
Scan the network and check whether the device is signaling under the correct
device name and correct IP address.
Adapt the Ethernet address or device name if necessary,
assign the device name to the device once again and download the configuration.