Balluff Network Interface Profibus
www.balluff.com
26
8
Diagnostics
8.1.
Function
indicators
The status of the supply voltages is indicated by the status LED´s 1 to 5.
LED indicators
Status LEDs
LED
Indicator
Function
US
Green
US power supply sensor ok
UA
Green
UA power supply actuator ok
US
Red
US power supply sensor under voltage
UA
Red
UA power supply actuator under voltage
BUS
Green
Grün, blinking
BUS data transmission Profibus ok
BUS data transmission Profibus inactive
IO-Link Port
LEDs
Each IO-Link-port is assigned two LEDs which indicate the operating states.
LED “0” - PIN 4, LED “1” - PIN 2
Indicator
Function
IO-Link
Output
Input
Diagnostic-Input
Off
-
Signal = 0
Signal = 0
Diagnostics = 0
Yellow
-
Signal = 1
Signal = 1
Red
SC >Imax
I Output > Imax
SC*
Diagnostics = 1 or SC*
Green
IO-Link Commu-
nication active
-
-
-
Green
blinking
No IO-Link
Communication
-
-
-
* SC = Short circuit detection on Pin 1. In this case both LEDs are red.
Diagnostics input
Pin 2 of the I/O port can be configured as a diagnostics channel It behaves like an inverted
input. The 0 V signal is interpreted as 1, the corresponding port LED comes n red and a
diagnostics message is sent over DP-diagnostics.
The optical indicator on the corresponding I/O port allows defective sensors/actuators to be
more easily and quickly localized.