www.balluff.com
13
7
Startup
7.1.
Profibus-Address
The Profibus address is set directly on the BNI PBS-... using two BCD-switches.
Adressing
Permissible address range 0...99.
Each Profibus node must have a unique address assigned to it.
The address is read once after power is turned on.
Any change to the address does not become effective until power is reset on the
modules.
A DP Master is generally assigned addresses 0 bis 2. For the PBS modules we recommend
using addresses 3 and higher.
7.2.
Configuration
When project planning Profibus Devices, a Device is mapped as a modular system which
consists of a header module and multiple data modules
GSD file
The Device data required for project planning are stored in GSD files (Generic Station
Description). The GSD files are available in 2 languages for downloading over the Internet
(www.balluff.com).
The data modules of an IO-Link module are represented in the project planning software by
slot. The GSD file provides the possible data modules (inputs or outputs of various data
width). To configure the IO-Link module the appropriate data modules are assigned to a
particular slot.
Slot
Module
Function
1
Header module
Identification/parameter setting special
indentifier format, 1 data bytes
2
Port 0 Pin 4 (1. IO-Link port)
IO-Link data modules of various data
width or configurable as standard I/O
port
3
Port 1 Pin 4 (2. IO-Link port)
4
Port 2 Pin 4 (3. IO-Link port)
5
Port 3 Pin 4 (4. IO-Link port)
6
Slots for optional additional moduls:
Communication state
IO-Link diagnosis enable
Stations diagnostic
Peripherie fault
Sensor short circuit
Actuator shut down / warning Pin 4
Actuator shut down / warning Pin 2
Restart Pin 4
Restart Pin 2
7
8
9
10
11
12
13
14
15
16