IO-Link-Smart Sensor Profile (BML SL1-ALZ0-U1ZZ-…) (continued)
There are three ways to move the zero point:
–
Preferred method
: Writing the parameter
Preset
sets
the current position to the value
Preset
. The value
range of the parameter
Preset
is −8.19 m…+8.19 m.
The
Preset
parameter changes the
Offset
parameter.
–
Alternative 1:
By directly configuring the offset
parameter the parameter
Offset
is calculated as
following: Offset = new position (target value) – current
position.
The value range of the parameter
Offset
is
−8.19 m…+8.19 m.
–
Alternative 2:
Using the system command
Teach In
Zero Point
the current position is defined as 0.
The Preset value affects the parameter
Minimal
Negative Position
. When writing the parameter
Preset
a check is made to see whether the
value
Preset
lies within the set measuring range.
If the value
Preset
does not lie in the measuring
range, the measuring range is automatically
adjusted.
The offset and preset can be reset either by using the
system command
Reset Offset
or by writing a 0 to the
parameter
Offset
.
Minimal Negative Position
In the standard configuration the measuring range of the
sensor head is 0 to 8.19 m. If negative values also need to
be output, the measuring range must be adjusted. If the
measuring range is extended in the negative direction, the
measuring range is shortened in the positive direction by
the same amount. the entire measuring length (negative
measuring range limit to positive measuring range limit)
always adds up to 8.19 m. The minimal position value can
be set in two different ways:
– The negative limit of the measuring range can be
directly entered using the parameter
Minimal Negative
Position
. The setting takes effect as soon as the
parameter is written.
– The sensor is moved to the position which represents
the measuring range limit in the negative direction.
There the system command
Teach In Minimal Negative
Position
is carried out. The current position immediately
represents the negative measuring range limit. The
sensor can be moved 8.19 m in the positive direction
without experiencing an overrun.
Fig. 6-2:
8.19 m
8.19 m
Overflow
Position value
Position value
Path
Lower measuring limit
Path
Example for a measuring range adjustment by setting a
minimal negative position
To disable the output of negative positions,
Minimal
Negative Position
must be set to 0.
BML SL1-ALZ _-_ _ ZZ- _ _ _ _ - _ _ _ _
Absolute Magnetically Coded Position Measuring System
english
Содержание BML SL1-ALZ-ZZ Series
Страница 2: ...www balluff com...
Страница 3: ...deutsch Betriebsanleitung BML SL1 ALZ_ _ _ZZ _ _ _ _ _ _ _ _...
Страница 4: ...www balluff com...
Страница 53: ...english User s Guide BML SL1 ALZ_ _ _ZZ _ _ _ _ _ _ _ _...
Страница 54: ...www balluff com...
Страница 103: ...fran ais Notice d utilisation BML SL1 ALZ_ _ _ZZ _ _ _ _ _ _ _ _...
Страница 104: ...www balluff com...
Страница 153: ...italiano Manuale d uso BML SL1 ALZ_ _ _ZZ _ _ _ _ _ _ _ _...
Страница 154: ...www balluff com...
Страница 203: ...espa ol Manual de instrucciones BML SL1 ALZ_ _ _ZZ _ _ _ _ _ _ _ _...
Страница 204: ...www balluff com...
Страница 253: ......