BIS M-62_ MANUAL
102
6
Page will be reset to zero (0x00), indicating that the host has received and processed its
pending data.
6.3.1 Modbus TCP - Host/BIS M-626_ Handshaking
When the host issues a command, it must first write the entire command to the Node Input
Page, leaving the Overall Length value to be written last.
For example, for the host to issue the 6-
word command “
Read Data
,” it must first write the
last five words of the command to Node Input Page 01, beginning at register 40002. After
which, the host will fill in the first word (at holding register 40001) with the Overall Length of
the command packet.
Last Five Words of a Read Data Command
Word
MSB
LSB
Description
02
0xAA
0x05
Command ID:
Read Data
03
0x00
0x01
Node ID:
0x01
04
0x03
0xE8
Timeout Value:
1 second
05
0x00
0x20
Read Start Address
: 0x0020
06
0x00
0x04
Block Size
: 4 Bytes
After writing the last five words of the command, the host will write the Overall Length value
to holding register 40001 of Node Input Page 01.
First Word of a Read Data Command
Word
MSB
LSB
Description
01
0x00
0x06
Overall Length
(
in words
)
The moment the Overall Length value (at holding register 40001) of Node Input Page 01
changes from 0x0000 to a “non-zero” value, the BIS M-626_ will recognize the waiting data
and will execute the command.
6.3.2 Modbus TCP - Handshaking Example
1. The host or PLC issues an RFID command to the BIS M-626_, writing the command
string to the holding registers for Device ID 01 (Node Input Page 01). An Overall
Length value of 0x0006 is written last to holding register 40001.
2. The BIS M-626_ recognizes that the Overall Length value at holding register 40001
has changed for Device ID 01 (Node Input Page 01), indicating that a command is
waiting to be executed.
3. The BIS M-626_ executes the command and then clears the Overall Length holding
register of Device ID 01 (Node Input Page 01), setting it back the default value of zero
(0x0000).
Содержание BIS M-62 Series
Страница 1: ......
Страница 2: ......
Страница 3: ......
Страница 7: ......
Страница 16: ...9 BIS M 371 000 A01 BIS M 372 000 A01 BIS M 373 000 A01 BIS M 370 000 A02 Figure G...
Страница 17: ...10...
Страница 21: ...BIS M 62_ MANUAL 14 1...
Страница 60: ...INSTALLATION 53 2...
Страница 77: ...BIS M 62_ MANUAL 70 4...
Страница 101: ...BIS M 62_ MANUAL 94 5...
Страница 103: ...BIS M 62_ MANUAL 96 6 The HTTP Server Main Page will be displayed...
Страница 126: ...DEVICENET INTERFACE 119 8...
Страница 185: ...BIS M 62_ MANUAL 178 10...
Страница 188: ...RFID OPERATING PRINCIPLES 181 11...
Страница 198: ...RFID OPERATING PRINCIPLES 12 No 896 712 726 EN Edition A17 Subject to modification Replaces edition L14...