- 2 -

Issue 1

BVR20 Microdrive

Ambient Noise Supplement.

This addendum to the BVR20 Microdrive manual assumes that the user is familiar with the
operation of the BVR20 Microdrive

General Description

The Baldwin Boxall Ambient Noise System is based around the 

BVR20

 Microdrive.

BVRAMB 

ambient noise sensors are connected to the BVR20 via 

BVRCI

 interface cards.

The BVRCI cards connect via ribbon cable assemblies to

 BVRIO40

 cards located in the

BVR20.
The BVR20 will accommodate sixteen ambient noise circuits with a maximum of two
BVRAMB ambient noise sensors on each circuit.
Each BVRAMB circuit is terminated to a BVRCI card.  Of the three available BVRCI cards
only cards two and three have the ambient noise function.  The terminations of these cards
and their associated zones are shown in the following table.

BVRCI card 2

terminal number

BVR20 Output

number

BVRCI card 3

terminal number

BVR20 Output

number

1

1

1

9

2

2

2

10

3

3

3

11

4

4

4

12

5

5

5

13

6

6

6

14

7

7

7

15

8

8

8

16

Note: Important.

The BVRCI cards nominated for use with BVRAMB noise sensors must have their jumper
link LK1 in the ‘0V’ position.

Содержание VIGIL BVR20

Страница 1: ...oad Crowborough East Sussex TN6 2JR Telephone 01892 664422 Fax 01892 663146 Website www baldwinboxall co uk Email mail baldwinboxall co uk C O M M U N I C A T I O N S IBVR20 08 08 2003 ECR 1500 VIGIL...

Страница 2: ...ATORS 6 MAINTENANCE OF THE BVR20 7 FAULT REPORTING AND STATUS PAGES 8 HOW TO MONITOR EITHER AN INPUT OR OUTPUT CHANNEL SIGNAL 11 HOW TO VIEW OR CHANGE AN OUTPUT CHANNEL SETTING 12 HOW TO VIEW OR CHANG...

Страница 3: ...he BVR20 provides all of the monitoring functions and displays the system status using a 40 x 2 character LCD display and 5 front panel mounted LEDs The unit can be operated in two separate modes depe...

Страница 4: ...1KHz 2 5KHz 200Hz 12dB Octave high pass filter Aural and visual monitor 20 sounder circuit opto coupled inputs OPT402 CH1 OPT402 CH2 OPT402 CH3 OPT402 CH4 MESSAGE 1 MESSAGE 2 3 MESSAGE 4 5 MESSAGE 6 7...

Страница 5: ...L CONTROLS AND INDICATORS COMPLIES COMMON SYSTEM HEALTHY FAULT FAULT ACCEPT FAULT RESTART CPU CPU 1 2 4 5 3 6 7 8 9 0 BS5839 WITH PART 8 LAMP TEST SERIAL INTERFACE PAGE PAGE UP DOWN SYSTEM CONFIGURATI...

Страница 6: ...nals G Buzzer Sounds when a fault is detected see C for more details H Fault Accept Button Press to accept a fault once detected see C for more details I Lamp Test Button Press to check front panel LE...

Страница 7: ...s Again the signal from each message is presented to the audio bus at 0dBm The system monitors the audio output presented to the first output module and the DC bias present at the output of the digita...

Страница 8: ...ult output produced by the relay contacts to external equipment i e Fire detection panel The various status pages are scrolled up and down with the Page Up and Page Down keys Faults are shown by XX in...

Страница 9: ...1 OK ACCESS 1 OK NO FAULTS 2 OK 3 OK 4 OK 2 OK 3 OK 4 OK Emergency microphones FIRE MICS AUDIO 1 OK ACCESS 1 OK FAULTS 2 XX 3 OK 4 OK 2 OK 3 OK 4 OK XX indicates that Mic 2 has an audio fault Page7 M...

Страница 10: ...AULTS 6 OK 7 OK 8 OK 6 OK 7 OK 8 OK Page microphones PAGE MICS AUDIO 5 OK ACCESS 5 OK FAULTS 6 OK 7 OK 8 OK 6 OK 7 XX 8 OK XX indicates that Mic7 has a access fault Page13 Noise sensing microphones 1...

Страница 11: ...wn keys to select the page shown below L S OUTPUT ZONE INPUT SOURCE VOLUME MONITOR 00 00 Press the or cursor keys and move along to the INPUT SOURCE or OUTPUT ZONE window Using the or keys enter the N...

Страница 12: ...vel codes Level 4 allows level 3 and access level codes WARNING ENTER CODE TO ENABLE ADJUSTMENTS 3 Enter your 4 digit access code the factory set default for all levels is 0000 but may be changed via...

Страница 13: ...fore please refer to 6 8 Press the Page down key again The display will step to the 3rd page current equalizer settings of output channel 1 OUT 01 frequency 315 500 1K0 2K0 3K1 6K3 equalizer dB 12 12...

Страница 14: ...d frequency and mode Note for normal surveillance operation only use 30Hz or 20KHz Example 1 Frequency 30Hz loudspeaker line A monitored only OUT 01 CHIME SURV A 00 B 00 ANS 00 00 Out 09 30Hz A Sens 0...

Страница 15: ...the ambient noise In theory if the ambient noise is at its loudest the announcements should remain around 10dB above the ambient level The sensitivity is adjustable from 01 and 15 Once set the loudsp...

Страница 16: ...ess level codes Level 4 allows level 3 and access level codes WARNING ENTER CODE TO ENABLE ADJUSTMENTS 3 Enter your 4 digit access code the factory set default for all levels is 0000 but may be change...

Страница 17: ...value to 0 flat simply press the 0 key note the cursor automatically steps to the next window Or using the or keys will lift or cut the value between 14 and 14 Input surveillance and busy relay outpu...

Страница 18: ...utput volume if several operators use a microphone or music with wide ranging levels IN 08 ATTENUATOR COMPRESSOR CHIME 00 00 Off Off To select either a limiter or compressor move the cursor along unti...

Страница 19: ...ess 2 for 2 notes Press 3 for 3notes IN 08 ATTENUATOR COMPRESSOR CHIME 00 00 Limiter 06 Fast 3note Pressing Page up key enables you to step to the previous page Pressing Page down key steps to the nex...

Страница 20: ...amplifier loudspeaker line surveillance and ambient noise adjustments Level 3 allows level 2 and all other settings except access level codes Level 4 allows level 3 and access level codes WARNING ENTE...

Страница 21: ...the BVR20 to be processed thus identifying an individual BVR20 when several maximum 11 are connected to a BVRM control microphone If only 1 BVR20 is connected to a BVRM the address both TX and RX is s...

Страница 22: ...all unselected zones to message 4 12 Both Select Cancel have all call select Unselected zones will not automatically alert 13 As above Message 1 will select all unselected zones to message 2 14 As ab...

Страница 23: ...example zone outputs 02 03 10 11 12 would be barred on Port1 10 Press the Page down key again The display steps to the 1st page of BVRM zone positions 01 10 PORT 1 out 01 02 03 04 05 06 07 08 09 10 a...

Страница 24: ...een 00 and 63 13 Press the Page down key again The display steps to the 4th page of BVRM zone positions PORT 1 out 11 12 13 14 15 16 17 18 19 20 group mode 11 12 13 14 15 16 17 18 19 20 In group mode...

Страница 25: ...below to enter correct code for output operation in 2nd and 4th page of BVRM zone positions 00 0 08 d 01 a 09 a d 02 b 10 b d 03 a b 11 a b d 04 c 12 c d 05 a c 13 a c d 06 b c 14 b c d 07 a b c 15 a...

Страница 26: ...Note the cursor automatically steps to the next message Or using the or keys will increase or decrease the value between 00 and 63 seconds When several BVR20 are used on 1 site it may be desirable to...

Страница 27: ...non latching input Mode 02 Normally closed energized fail safe latching input Mode 03 Normally closed energized fail safe non latching input To change the mode move the cursor along until it flashes...

Страница 28: ...ion system the message broadcast may be delayed to any output from 0 to 31 5 minutes providing phased evacuation a requirement for high rise buildings In the example above outputs 1 and 2 would be eva...

Страница 29: ...2 02 02 02 02 00 00 00 00 Repeat 19 onwards for all 20 fire panel inputs 25 Press the Page down key again The display steps to the 1st page of message 01 monitored access selection for outputs 01 10 M...

Страница 30: ...he cursor along until it flashes beneath the required output 1 10 window If the access input required is between 0 9 enter it directly using the numbered keys or using the or keys step to the number r...

Страница 31: ...nes 1 8 press to speak access Inputs 1 8 19 26 on the 2nd BVRCI are used for ambient noise sensors outputs 1 8 and inputs 1 8 37 44 on the 3rd BVRCI are used for ambient noise sensors outputs 9 16 If...

Страница 32: ...any of the 20 outputs when the control input is closed or via a 1k2 resistor to 0V In the example above if input access 10 were closed to 0V page microphone 01 would be broadcast to outputs 01 05 and...

Страница 33: ...d access selection for outputs 11 20 P M 01 out 11 12 13 14 15 16 17 18 19 20 group mode 00 00 00 00 00 00 00 00 00 00 For group mode settings refer to sections 13 15 above 39 Press the Page down key...

Страница 34: ...ode 00 00 00 00 00 00 00 00 00 00 42 Press the Page down key again The display steps to the 3rd page of auxiliary input 01 unmonitored access selection for outputs 11 20 AUX 01 out 11 12 13 14 15 16 1...

Страница 35: ...number required between 00 and 54 46 Press the Page down key again The display steps to the 2nd page of auxiliary inputs 1 4 remote volume control access selection for outputs 11 20 AUX1 4 out 11 12...

Страница 36: ...t 14 Priority 21 1 0 0 1 1 10 0 1 0 1 PM7 Input 11 Priority 18 Input 15 Priority 22 0 1 0 1 1 11 1 1 0 1 PM8 Input 12 Priority 19 Input 16 Priority 23 1 1 0 1 1 12 0 0 1 1 AUX1 Input 13 Priority 20 In...

Страница 37: ...tate Farningham Road Crowborough East Sussex TN6 2JR Telephone 01892 664422 Fax 01892 663146 Website www baldwinboxall co uk Email mail baldwinboxall co uk C O M M U N I C A T I O N S IBVR20AMB Issue...

Страница 38: ...VR20 will accommodate sixteen ambient noise circuits with a maximum of two BVRAMB ambient noise sensors on each circuit Each BVRAMB circuit is terminated to a BVRCI card Of the three available BVRCI c...

Страница 39: ...ngle of the loudspeakers or close to a permanent noise source air conditioning fruit machines etc In high ceiling rooms position the sensor so that it closer to the floor than the ceiling Cables shoul...

Страница 40: ...is important to establish two points 1 Set the maximum output volume required in the ANS zone that is the volume demanded to meet a fully populated area or with maximum ambient noise i e a train waiti...

Страница 41: ...to the ANS it is important that the Surveillance Monitored is switched off otherwise the ANS will detect this as a signal and freeze the output Simply reduce SURV Out to read 00 fig 6 Fig 6 OUT 01 CHI...

Страница 42: ...he installer to select the freeze condition when the output has been selected i e the busy state As message 1 input 5 does not have the facility to select a chime this is now used to select the ANS mo...

Отзывы: