Page 20
IBVR20 software 8.43.doc
Issue 1
HOW TO VIEW OR CHANGE SERIAL PORT ADDRESS, BVRM ZONE POSITION, FIRE
PANEL INTERFACE SELECTION AND MESSAGE CONFIGURATION.
1. Insert the key and rotate clockwise.
The display will show the software version, in this example 08.41.
------------------------------------------
| BVR 20 VOICE ALARM Version 08.41 06.19 |
| BALDWIN BOXALL COMMUNICATIONS |
------------------------------------------
2. Press the Page down key.
The display invites you to enter your 4 digit access code to enable adjustments.
There are 4 access levels,
Level 1 allows input and output EQUALIZER, volume, limiter/compressor and chime
volume adjustments only.
Level 2 allows level 1 together with amplifier/loudspeaker line surveillance and ambient
noise adjustments.
Level 3 allows level 2 and all other settings except access level codes.
Level 4 allows level 3 and access level codes.
------------------------------------------
| *****************WARNING**************** |
| ENTER CODE TO ENABLE ADJUSTMENTS ???? |
------------------------------------------
3. Enter your 4 digit access code, the factory set default for all levels is 0000, but may be
changed via level 4.
Press the Page down key again.
The display invites you to enter an output channel number 1-20 that you wish to set up.
------------------------------------------
| OUT 00 VOLUME & EQUALIZER SETTINGS |
| Enter output no required Press page down |
------------------------------------------
4. Press the Page down key again.
The display invites you to enter an input channel number 1-20 that you wish to set up.
------------------------------------------
| IN 00 VOLUME & EQUALIZER SETTINGS |
| Enter input no required Press page down |
------------------------------------------
5. Press
2.
------------------------------------------
| IN 20 VOLUME & EQUALIZER SETTINGS |
| Enter input no required Press page down |
------------------------------------------