Page 35
IBVR20 software 8.43.doc
Issue 1
45. Press the Page down key until the display steps to the 1
st
page of auxiliary inputs 1-4
remote volume control access selection for outputs 01-10.
------------------------------------------
| AUX1-4 out|01|02|03|04|05|06|07|08|09|10 |
| volume in|18|18|00|00|00|00|00|00|00|00 |
------------------------------------------
The volume of AUX 1-4 (music) inputs can be adjusted to any output or group outputs
from a remote volume control. In the example above a 5k Ohm linear variable resistor
connected between access input 18 and 0V would adjust the volume of outputs 1 and 2,
minimum resistance equals maximum volume which can not exceed the set preset level.
If remote volume control is not required on an output set the value to 00.
To change the access input, move the cursor along until it flashes beneath the required
output 1-10 window.
If the access input required is between 0-9, enter it directly using the numbered keys, or
using the + or – keys step to the number required between 00 and 54.
46. Press the Page down key again.
The display steps to the 2
nd
page of auxiliary inputs 1-4 remote volume control access
selection for outputs 11-20.
------------------------------------------
| AUX1-4 out|11|12|13|14|15|16|17|18|19|20 |
| volume in|00|00|00|00|00|00|00|00|00|00 |
------------------------------------------
To change the access input, move the cursor along until it flashes beneath the required
output 11-20 window.
If the access input required is between 0-9, enter it directly using the numbered keys, or
using the + or – keys step to the number required between 00 and 54.
47. Press the Page down key again.
The display steps to the level access codes.
------------------------------------------
| ACCESS CODE level| 01 | 02 | 03 | 04 |
| PASSWORD |0000|0000|0000|0000 |
------------------------------------------
The codes will only be displayed and changed if level 4 code has been entered following
rotation of key, see step 2.
To change an access code, move the cursor along until it flashes beneath the required
access code, enter the new code using the numbered keys.
Pressing Page up key enables you to step to the previous page.
Note:
Once settings have been adjusted, always return the key to the anti clockwise position to
prevent accidental adjustment.