8-2 Customizing Your Application
MN762
8.2 Analog and Digital Input Configurations
Parameters P-07 and P-08 can be set to allow various operating modes. Following are settings for these parameters.
8.2.1 Terminal Strip Mode (P-07 = 0)
Table 8-1 Parameter P-08 Control of Digital Inputs when P-07=0
P-08
Digital In 1 (Term. 2)
Digital In 2 (Term. 3)
Digital In 3 (Term. 4)
Analog Input 1 (Term. 6)
0
Open
Stop
Open
FWD Run
Open
Analog Input 1
SPD Ref
Closed
Run
Closed
REV Run
Closed
Preset Speed1
1
Open
Stop
Open
Analog SPD Ref
Open
Preset Speed1
SPD Ref
Closed
Run
Closed
Preset Speed
1/2
Closed
Preset Speed2
2*
Open
Stop
Digital In 2
Digital In 3
Speed Select
Digital In 4*
Preset Speed 1-4
(Term 3)
(Term 4)
(Term 6)
0
0
Preset Speed 1
Open*
1
0
Preset Speed 2
Closed
Run
0
1
Preset Speed 3
Closed *
Max Speed (P-06)
1
1
Preset Speed 4
3*
Open
Stop
Open
Analog SPD Ref
Open
Trip (Ext Trip)
SPD Ref
Closed
Run
Closed
Preset Speed1
Closed
Run
4
Open
Stop
Open
Analog Input 1
Analog Input 2
SPD Ref
Closed
Run
Closed
Analog Input 2
5*
Open
FWD Stop
Open
REV Stop
Open
Analog SPD Ref
SPD Ref
Closed
FWD Run
Closed
REV Run
Closed
Preset Speed1
6*
Open
Stop
Open
FWD Run
Open
Trip (Ext Trip)
SPD Ref
Closed
Run
Closed
REV Run
Closed
Run
7*
Open
FWD Stop
Open
REV Stop
Open
Trip (Ext Trip)
SPD Ref
Closed
FWD Run
Closed
REV Run
Closed
Run
8
Open
Stop
Open
FWD Run
Digital In 3
Digital In 4*
Speed Select
(Term 4)
(Term 6)
Closed
Run
Closed
REV Run
0
0
Preset Speed 1
9*
Open
FWD Stop
Open
REV Stop
1
0
Preset Speed 2
Closed
FWD Run
Closed
REV Run
0
1
Preset Speed 3
1
1
Preset Speed 4
10
3Wire Control
Momentary Close = RUN
3Wire Control
Open = STOP
Open
Analog SPD Ref
SPD Ref
Closed
Preset Speed 1
11*
3Wire Control
Momentary Close = RUN
3Wire Control
Open = STOP
3Wire Control
Momentary Closed = REV
SPD Ref
12
Open
Stop
Open
Fast Stop (P33)
Open
Analog SPD Ref
SPD Ref
Closed RUN (ENABLE)
Closed
RUN (ENABLE)
Closed
Preset Speed1
*Table 8-1 notes:
P-08 = 2, 8 or 9 Note: Analog Input 1 becomes Digital Input 4
Closed: 8V< Analog Input1 < 30V
Open: Analog Input1 < 2V
P-08 = 5, 7 or 9 Note: Closing both Digital Input 1 and 2 = Fast Stop (P33).
P-08 = 3 or 6 Note: Connect external PTC Motor Thermistor or similar user contact to Digital Input 3.
P-08 = 11 Note: Closing both Digital Input 1 and Digital Input 3 = Fast Stop (P33).