Using the Keypad 6-1
MN762
Chapter 6
Using the Keypad
6.1 Keypad Components
This chapter provides an overview of the integrated keypad and how to use it to program the VS1MX drive. The controls are
shown in Table 6-1.
Table 6-1 Operator Interface Description
Key
Name
Description
Display
6 Digit seven segment display. Display of parameter
numbers, values, error messages and other information.
Start
Starts motor if Direction command and Speed reference
are set. Only active if P07 is set to allow keypad control and
when P28 is not set to 2 or 3. Programmable to change the
motor direction if pressed while running.
Stop / Reset
Stops the drive when in Keypad mode only. Active when
P-07 = 1 or 2 and when P28 is not set to 2 or 3. Resets any
active faults, if fault condition has been cleared.
Enter / Program
Momentarily press to view available displays. Pressing and
holding the ENT Key for approximately 2 Seconds or more
will enter the programming mode or escape back out of the
programming mode.
Increase
During operation increases the speed reference. (Active in
keypad mode). Pressing for a period of time will increase
the reference value rate of change. In edit mode, navigates
between parameters and increments parameter values.
Decrease
During operation decreases the speed reference. (Active in
keypad mode). Pressing for a period of time will increase
the reference value rate of change. In edit mode, navigates
between parameters and decrements parameter values.
Speed Reference
(Disconnect models only)
Adjusts the motor speed when Analog In1 is set as the
Speed Reference Source.
Direction Command
(Disconnect models only)
Sets the direction of motor rotation and issues a run
command, 0 (OFF), FWD (run forward) or REV (Run reverse).
At 0 position, the motor output is disabled but power is
applied to the control circuits.
On/Off Power Switch
(Disconnect models only)
OFF removes power from internal circuits. On powers up
the control for operation.
Note: In OFF, AC power is still present at the L1, L2, L3
terminals. Separate disconnect required to remove AC
power from drive terminals.
NEMA12 only
(Disconnect models only)
On/Off Power Switch (with Lockout). Allows the On/Off
Power Switch to be locked in the OFF position using a
20mm standard shackle pad lock (not provided). This
ensures no one will accidentally turn power on.