background image

4-2 Troubleshooting and Maintenance

MN1269

Fault

Symptom

Corrective Action

No torque in one direction.

Check left or right limit switch wires to ensure that they are not tied to

common.

Verify that the proper limit switches are used.
Verify P1 position

N/A

No output in either direction.

Check interlock and reset wires to ensure that they are not tied to common.
Perform set–up procedure and verify all connections.  Observe if all 4

green LED’s are lit on logic supply.

If all 4 LED’s are not lit, perform start–up procedure in Section 3 and

recheck all steps.

If only (bus) LED is lit, check AC logic fuse on top of unit to verify it is good

and set in the holder.

Verify P1 jumper is not missing.

N/A

Motor runs at uncontrolled
speeds

Verify that the servo control is not set for current mode.
Verify P6 position.
Verify that (T) pot is not set full CCW.  Reverse tach leads and verify that

tach voltage is present at signal input connector when motor is running.

Oscillation in motor seen as
instability or rocking of motor
shaft.  Motor may have
growling sound.

Refer to Start-up and Adjustment
Procedures for proper setting of (R) and (T) pots.

Motor exhibits a “dead zone“
when responding to a signal
input.

Verify that the bus voltage is sufficient for the motor.
Verify that inductance is not overly high (see specifications in Section 1

).  Refer to Start-up procedures for proper setting of (R) pot.

Low output voltage from logic
power supply.

Check incoming power to logic power supply and verify that it is in specified

range.   If in range, disconnect any external load on logic power and
reset servo control.

VE

Bus Voltage too high.

Check fuse on shunt regulator.
Recheck voltage and if problem still exists, disconnect power to each servo

control individually and isolate which servo control is drawing excess
current.

Check to ensure (T) pot is turned too far CCW.

RMS current output is
exceeded.

Check axis for instability (oscillation). Correct by turning (R) pot CCW.

EC

Overtemperature on servo
control.

If not instability, look for high tach noise (over 5% p–p) by using an

oscilloscope. If noise is present, check tach shielding.

If overloading is suspected, a larger servo control may be required.

Contact your supplier for alternatives.

Verify that air circulation is present.  Check for overload using oscilloscope

on the DCS line to determine current to motor.   1V is approximately 1/10
of the peak rated output current.  If not overloaded, unit should be
returned for repair.

GF

Current flow is detected at
ground potential

Can be caused by a short to ground. Remove armature connections and

check for short to ground. If none exists, remove servo control and reset
unit. If problem is resolved, servo control should be returned for repair.

SC

Rated peak current has been
exceeded.

Verify that motor has sufficient inductance (see Section 1.5.2). Reset servo

control and see if  problem immediately reappears. If so, check for short
in motor. If motor is not shorted, unit has an internal short and should be
returned for repair.

If upon resetting servo control, the unit does not fault, cycle equipment

while watching for a fault during acceleration. If fault occurs, increase the
acceleration time, reset and cycle until problem is eliminated.

Servo Systems Co. • 115 Main Road • P.O. Box 97 • Montville, NJ, 07045-0097 

(973) 335-1007 • Toll Free: (800) 922-1103 • Fax: (973) 335-1661 

www.servosystems.com

Содержание LD Series

Страница 1: ...Servo Control Installation Operating Manual 7 98 MN1269 DC SERVO DRIVE Servo Systems Co 115 Main Road P O Box 97 Montville NJ 07045 0097 973 335 1007 Toll Free 800 922 1103 Fax 973 335 1661 www servo...

Страница 2: ...Tools 1 14 Section 2 Installation 2 1 Receiving Inspection 2 1 Location Considerations 2 1 Installing the Servo Control Card 2 1 Mount the Chassis 2 2 General Wiring Considerations 2 3 Power Wiring 2...

Страница 3: ...s 5 1 Current Torque Mode 5 1 Emergency Stop 5 2 Appendix A A 1 Condensed Installation Instructions A 1 Appendix B B 1 Jumper and Personality Module Settings B 1 Personality Module Current Settings B...

Страница 4: ...ith by unauthorized persons misused abused or improperly installed and has been used in accordance with the instructions and or ratings supplied This warranty is in lieu of any other warranty or guara...

Страница 5: ...t the start up procedure or troubleshoot this equipment WARNING Be sure all wiring complies with the National Electrical Code and all regional and local codes Improper wiring may result in unsafe cond...

Страница 6: ...diately above or beside heat generating equipment or directly below water or steam pipes Caution Avoid locating control in the vicinity of corrosive substances or vapors metal particles and dust Cauti...

Страница 7: ...roviding not only converted DC power to the motor but also precisely controlling current and velocity at the motor Its compact design requires very little enclosure space while its modular configurati...

Страница 8: ...us AC Other standard features include 20 kHz Inaudible Switching Test Points to aid during set up Jumper Settings allow easy tailoring for specific applications Personality Module for custom current s...

Страница 9: ...fy the LD Series Servo Control and Chassis The LD Series Servo Control cards can be configured with chassis to support up to four 4 axes at 160 VDC Figure 1 2 Identification Servo Systems Co 115 Main...

Страница 10: ...current and responds to overload conditions beyond rated output If the comparator is tripped it disables the drive lights the Excess Current EC indicator and pulls the interlock line low if P4 is in...

Страница 11: ...95 Shutdown Point Typical V 220 220 General LD2 LD4 Operating Temperature C 0 50 0 50 Weight lbs 14 20 6 Footprint inches Length 9 13 Width 10 5 10 5 Height 7 25 7 25 Notes 1 An isolation transformer...

Страница 12: ...0 50 Notes 1 RMS current limit is a built in function that turns off or folds back the servo control if the continuous current is exceeded for an extended period of time The EC fault indicator identi...

Страница 13: ...lso provided to verify the presence of 15 VDC PV 15 VDC MV AC for fans and logic AC and DC Bus voltage PB or BUS Bus Power Supply The bus power supply converts the 115 VAC input voltage into a DC volt...

Страница 14: ...the installer to vary the overshoot or stiffness of a motor as it is commanded to change speeds Response R R pot is used to adjust the overall velocity loop gain The effect of changing the gain enabl...

Страница 15: ...ule The personality module has 3 after factory adjustable settings for location see Figure 1 4 With the appropriate 1 resistor soldered into the socket peak current RMS current and the foldback level...

Страница 16: ...servo control Excess Current Overtemperature EC The purpose of the EC indicator is to identify either excess RMS current or over temperature condition Ground Fault GF The purpose of the GF indicator i...

Страница 17: ...medium large with 8 long shank required if replacing or adding servo control cards Add or remove modules Phillips screw driver medium Input connections to AC bus power Crescent Wrench 6 or 8 Disassem...

Страница 18: ...steam pipes CAUTION Avoid locating control in the vicinity of corrosive substances or vapors metal particles and dust Several other factors should be carefully evaluated when selecting a location for...

Страница 19: ...ted in General Precautions in section 1 3 Lay out the hole pattern according to the dimensions of your chassis Refer to Appendix A for dimensions 4 Cut any wiring openings needed in the cabinet debur...

Страница 20: ...ntly rated wire It is suggested that power wires be run as twisted pairs i e twist the wire carrying current with the same wire returning the current Twisting the wires will reduce radiated electrical...

Страница 21: ...tor and or terminal blocks Try to minimize the length of unshielded cable at these points Electrical Noise Suppression Electrical noise suppression requires a thorough system design using a combinatio...

Страница 22: ...ector see Figure 2 3 2 Connect the negative side tachometer lead wire of the first servomotor to the Tach input pin 6 on the 18 position Phoenix style input signal connector see Figure 2 3 Tie the tac...

Страница 23: ...itch has opened and disable its output in that direction unless the right and left limits pins 17 18 are tied to common Optional Wiring Single Voltage Input pin 4 to 2 The servo control can be configu...

Страница 24: ...d to the interlock line upon switch closure the output stages of all servo control cards will be disabled i e motors will coast to a stop with no holding torque See Section 5 for additional informatio...

Страница 25: ...2 8 Installation MN1269 Servo Systems Co 115 Main Road P O Box 97 Montville NJ 07045 0097 973 335 1007 Toll Free 800 922 1103 Fax 973 335 1661 www servosystems com...

Страница 26: ...y clockwise Low R Response Fully counterclockwise Low C Current Limit One turn clockwise Low B Balance Leave as shipped Center Note All pots have a 15 turn range and are without a hard stop You may he...

Страница 27: ...ssary to turn the T pot a few turns counterclockwise to achieve the desired speed 8 Slowly turn the C pot to the full clockwise position if the servo control s peak current is less than the rated peak...

Страница 28: ...ied personnel should attempt the start up procedure or troubleshoot this equipment WARNING Do not remove cover for at least five 5 minutes after AC power is disconnected to allow capacitors to dischar...

Страница 29: ...reset servo control VE Bus Voltage too high Check fuse on shunt regulator Recheck voltage and if problem still exists disconnect power to each servo control individually and isolate which servo contr...

Страница 30: ...hop dust in some environments tends to be electrically conductive and can cause servo control malfunction 1 If cleaning is needed carefully vacuum loose dirt or use dry compressed air 2 Remove power a...

Страница 31: ...4 4 Troubleshooting and Maintenance MN1269 Servo Systems Co 115 Main Road P O Box 97 Montville NJ 07045 0097 973 335 1007 Toll Free 800 922 1103 Fax 973 335 1661 www servosystems com...

Страница 32: ...op controls the output current proportional to the input voltage VCS Typical applications requiring current mode operation are Web controls Brake applications Bolt tightening Current mode operation is...

Страница 33: ...sted approach using a relay with 4 sets of contacts could be applied as shown in Figure 5 2 providing a power disconnect of motor and servo control in the event of an E stop Figure 5 2 Power Contactor...

Страница 34: ...r injured Step 3 Mount the Chassis Assembly WARNING Do not apply power until all connections are made connections are checked and the safety precautions in Sections 1 are read and understood Step 4 Co...

Страница 35: ...Installation Drawing 115VAC 3 phase input bus power for LD 4 115VAC 1 phase input bus power for LD 2 Servo Systems Co 115 Main Road P O Box 97 Montville NJ 07045 0097 973 335 1007 Toll Free 800 922 11...

Страница 36: ...tor reduces the set values from the specifications in Section 1 Figure B 1 R96 C25 R97 C26 R98 C27 Foldback Current Level LD 3015HS Foldback Current Amps Feedback Resistance Ohms 5 453 7 715 9 1 0K 11...

Страница 37: ...OFF P2 Differential Input 3 2 1 OFF ON P3 Current monitor value DCS 3 2 1 Absolute Actual P4 EC Fault Function 3 2 1 Foldback Latch P6 Amplifier Loop Mode 3 2 1 Velocity Current Potentiometer Settings...

Отзывы: