background image

Installation 2-5

MN1269

Power Wiring  Continued

1.

Connect the negative lead (black wire) from the first servomotor to terminal 1 on
the 12 position terminal block (see Figure 2-2).

2.

Connect the positive lead (red wire) from the first servomotor to terminal 2 on
the 12 position terminal block (see Figure 2-2).

3.

For the second axis servomotor, connect the negative lead (black wire) to
terminal 3; and the positive lead (red wire) to terminal 4. Repeat this procedure
for any other axes (Refer to drawing in Appendix A).

4.

Do not at this time connect any AC power to the chassis.

5.

Wire the AC power input to the screw–type terminals on the rear of the chassis
as shown in Figure 2-2.  Do not connect any AC power at this time.  Phasing is
not critical on the bus power input.  For LD-2 units, use the two terminals
marked L1 and L2 and connect 115VAC 1 phase power.  For LD-4 units, use
the three terminals L1, L2, and L3 and connect 3 phase power.

Signal Wiring

1.

Connect the positive (+) side tachometer lead wire (of the first servomotor) to
the Tach input (pin 5) on the 18 position Phoenix style input signal connector
(see Figure 2-3).

2.

Connect the negative (–) side tachometer lead wire (of the first servomotor) to
the Tach input (pin 6) on the 18 position Phoenix style input signal connector
(see Figure 2-3).  Tie the tachometer cable shield to pin (11) common.

3.

Continue connecting remaining tachometer lead wires for other axes (Refer to
drawing in Appendix A).

Figure 2-3  Input Signal Wiring   

4.

Differential Command input
The “LD” Series Servo Control is configured to operate using a differential
command input signal.  To utilize differential input, jumper P2 (see Figure 2-3)
must be in its right position (pins 1 to 2).  This is the normal position as shipped.
The Servo Control Signal pot (S) will be used to scale the differential voltage
input.

5.

Connect the input velocity command signal to pin 1 and its return to pin 4.

Note: Do not apply voltage at this time.
6.

Verify the first axis tachometer signal by rotating the first axis motor shaft by
hand while monitoring the tach test points with a VOM.  Connect the black lead
of the VOM to test point TP1 and the red to TP6.  When rotating the motor shaft
in a clockwise direction (facing the shaft), the VOM should read positive.

Servo Systems Co. • 115 Main Road • P.O. Box 97 • Montville, NJ, 07045-0097 

(973) 335-1007 • Toll Free: (800) 922-1103 • Fax: (973) 335-1661 

www.servosystems.com

Содержание LD Series

Страница 1: ...Servo Control Installation Operating Manual 7 98 MN1269 DC SERVO DRIVE Servo Systems Co 115 Main Road P O Box 97 Montville NJ 07045 0097 973 335 1007 Toll Free 800 922 1103 Fax 973 335 1661 www servo...

Страница 2: ...Tools 1 14 Section 2 Installation 2 1 Receiving Inspection 2 1 Location Considerations 2 1 Installing the Servo Control Card 2 1 Mount the Chassis 2 2 General Wiring Considerations 2 3 Power Wiring 2...

Страница 3: ...s 5 1 Current Torque Mode 5 1 Emergency Stop 5 2 Appendix A A 1 Condensed Installation Instructions A 1 Appendix B B 1 Jumper and Personality Module Settings B 1 Personality Module Current Settings B...

Страница 4: ...ith by unauthorized persons misused abused or improperly installed and has been used in accordance with the instructions and or ratings supplied This warranty is in lieu of any other warranty or guara...

Страница 5: ...t the start up procedure or troubleshoot this equipment WARNING Be sure all wiring complies with the National Electrical Code and all regional and local codes Improper wiring may result in unsafe cond...

Страница 6: ...diately above or beside heat generating equipment or directly below water or steam pipes Caution Avoid locating control in the vicinity of corrosive substances or vapors metal particles and dust Cauti...

Страница 7: ...roviding not only converted DC power to the motor but also precisely controlling current and velocity at the motor Its compact design requires very little enclosure space while its modular configurati...

Страница 8: ...us AC Other standard features include 20 kHz Inaudible Switching Test Points to aid during set up Jumper Settings allow easy tailoring for specific applications Personality Module for custom current s...

Страница 9: ...fy the LD Series Servo Control and Chassis The LD Series Servo Control cards can be configured with chassis to support up to four 4 axes at 160 VDC Figure 1 2 Identification Servo Systems Co 115 Main...

Страница 10: ...current and responds to overload conditions beyond rated output If the comparator is tripped it disables the drive lights the Excess Current EC indicator and pulls the interlock line low if P4 is in...

Страница 11: ...95 Shutdown Point Typical V 220 220 General LD2 LD4 Operating Temperature C 0 50 0 50 Weight lbs 14 20 6 Footprint inches Length 9 13 Width 10 5 10 5 Height 7 25 7 25 Notes 1 An isolation transformer...

Страница 12: ...0 50 Notes 1 RMS current limit is a built in function that turns off or folds back the servo control if the continuous current is exceeded for an extended period of time The EC fault indicator identi...

Страница 13: ...lso provided to verify the presence of 15 VDC PV 15 VDC MV AC for fans and logic AC and DC Bus voltage PB or BUS Bus Power Supply The bus power supply converts the 115 VAC input voltage into a DC volt...

Страница 14: ...the installer to vary the overshoot or stiffness of a motor as it is commanded to change speeds Response R R pot is used to adjust the overall velocity loop gain The effect of changing the gain enabl...

Страница 15: ...ule The personality module has 3 after factory adjustable settings for location see Figure 1 4 With the appropriate 1 resistor soldered into the socket peak current RMS current and the foldback level...

Страница 16: ...servo control Excess Current Overtemperature EC The purpose of the EC indicator is to identify either excess RMS current or over temperature condition Ground Fault GF The purpose of the GF indicator i...

Страница 17: ...medium large with 8 long shank required if replacing or adding servo control cards Add or remove modules Phillips screw driver medium Input connections to AC bus power Crescent Wrench 6 or 8 Disassem...

Страница 18: ...steam pipes CAUTION Avoid locating control in the vicinity of corrosive substances or vapors metal particles and dust Several other factors should be carefully evaluated when selecting a location for...

Страница 19: ...ted in General Precautions in section 1 3 Lay out the hole pattern according to the dimensions of your chassis Refer to Appendix A for dimensions 4 Cut any wiring openings needed in the cabinet debur...

Страница 20: ...ntly rated wire It is suggested that power wires be run as twisted pairs i e twist the wire carrying current with the same wire returning the current Twisting the wires will reduce radiated electrical...

Страница 21: ...tor and or terminal blocks Try to minimize the length of unshielded cable at these points Electrical Noise Suppression Electrical noise suppression requires a thorough system design using a combinatio...

Страница 22: ...ector see Figure 2 3 2 Connect the negative side tachometer lead wire of the first servomotor to the Tach input pin 6 on the 18 position Phoenix style input signal connector see Figure 2 3 Tie the tac...

Страница 23: ...itch has opened and disable its output in that direction unless the right and left limits pins 17 18 are tied to common Optional Wiring Single Voltage Input pin 4 to 2 The servo control can be configu...

Страница 24: ...d to the interlock line upon switch closure the output stages of all servo control cards will be disabled i e motors will coast to a stop with no holding torque See Section 5 for additional informatio...

Страница 25: ...2 8 Installation MN1269 Servo Systems Co 115 Main Road P O Box 97 Montville NJ 07045 0097 973 335 1007 Toll Free 800 922 1103 Fax 973 335 1661 www servosystems com...

Страница 26: ...y clockwise Low R Response Fully counterclockwise Low C Current Limit One turn clockwise Low B Balance Leave as shipped Center Note All pots have a 15 turn range and are without a hard stop You may he...

Страница 27: ...ssary to turn the T pot a few turns counterclockwise to achieve the desired speed 8 Slowly turn the C pot to the full clockwise position if the servo control s peak current is less than the rated peak...

Страница 28: ...ied personnel should attempt the start up procedure or troubleshoot this equipment WARNING Do not remove cover for at least five 5 minutes after AC power is disconnected to allow capacitors to dischar...

Страница 29: ...reset servo control VE Bus Voltage too high Check fuse on shunt regulator Recheck voltage and if problem still exists disconnect power to each servo control individually and isolate which servo contr...

Страница 30: ...hop dust in some environments tends to be electrically conductive and can cause servo control malfunction 1 If cleaning is needed carefully vacuum loose dirt or use dry compressed air 2 Remove power a...

Страница 31: ...4 4 Troubleshooting and Maintenance MN1269 Servo Systems Co 115 Main Road P O Box 97 Montville NJ 07045 0097 973 335 1007 Toll Free 800 922 1103 Fax 973 335 1661 www servosystems com...

Страница 32: ...op controls the output current proportional to the input voltage VCS Typical applications requiring current mode operation are Web controls Brake applications Bolt tightening Current mode operation is...

Страница 33: ...sted approach using a relay with 4 sets of contacts could be applied as shown in Figure 5 2 providing a power disconnect of motor and servo control in the event of an E stop Figure 5 2 Power Contactor...

Страница 34: ...r injured Step 3 Mount the Chassis Assembly WARNING Do not apply power until all connections are made connections are checked and the safety precautions in Sections 1 are read and understood Step 4 Co...

Страница 35: ...Installation Drawing 115VAC 3 phase input bus power for LD 4 115VAC 1 phase input bus power for LD 2 Servo Systems Co 115 Main Road P O Box 97 Montville NJ 07045 0097 973 335 1007 Toll Free 800 922 11...

Страница 36: ...tor reduces the set values from the specifications in Section 1 Figure B 1 R96 C25 R97 C26 R98 C27 Foldback Current Level LD 3015HS Foldback Current Amps Feedback Resistance Ohms 5 453 7 715 9 1 0K 11...

Страница 37: ...OFF P2 Differential Input 3 2 1 OFF ON P3 Current monitor value DCS 3 2 1 Absolute Actual P4 EC Fault Function 3 2 1 Foldback Latch P6 Amplifier Loop Mode 3 2 1 Velocity Current Potentiometer Settings...

Отзывы: