36
Figure 7-7 I
2
t Trip Time vs. Motor Current
Notes:
1. In order to ensure that the motor is properly protected with the I
2
t
feature, it is required that the CL Trimpot be set for 160% of the motor
nameplate rated current, as described above.
2. This adjustment must be made within 6 seconds or the I
2
t Trip will occur.
The current limit may be adjusted as follows:
A. Connect an AC RMS ammeter in series with one motor phase.
B. Set the CL Trimpot fully counterclockwise.
C. Adjust the speed setting to 30%.
D. Lock the motor shaft and adjust the CL Trimpot to 160% of the motor
nameplate rated current.