Table 4-2 Drive Operating Condition and Run/Fault Relay
Contact Status
Drive Operating
Condition
Description
Run Relay Operation (J5
Installed in “RUN” Position)
(Factory Setting)
Fault Relay Operation (J5
Installed in “FLT” Position)
Normally
Open
Contact
Normally
Closed
Contact
Normally
Open
Contact
Normally
Closed
Contact
Power Off
Main Power
Disconnected
Open
Closed
Open
Closed
Run Mode
1
Normal Drive
Operation
Closed
Open
Closed
Open
Stop Mode
2
Selected by
Operator
Open
Closed
Closed
Open
Fault
3
Drive Tripped
Open
Closed
Open
Closed
Notes:
1. Run Mode is selected with the optional Forward-Stop-Reverse Switch or with the jumper
installed in CON2 (jumper installed in the “F-S” position for forward direction (factory
setting) or jumper installed in the “R-S” position for reverse direction).
2. Stop Mode is selected using the optional Forward-Stop-Reverse Switch.
3. I
2
t, Short Circuit, Undervoltage, Overvoltage.